Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: WILMINGTON FIBRE SPECIALTY COMPANY, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of WILMINGTON FIBRE SPECIALTY COMPANY, INC. in 700 WASHINGTON STREET, NEW CASTLE, DE 19720 (NAICS 326199). OSHA activity number 347982746.

Watch Wilmington Fibre Specialty Company, INC. — free Get an email when a new federal OSHA severe-injury report for Wilmington Fibre Specialty Company, INC. is published. One employer, no account, unsubscribe in one click.
Site address
700 WASHINGTON STREET
City
NEW CASTLE
State
DE
ZIP
19720
Mailing
700 WASHINGTON STREET, NEW CASTLE, DE 19720
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Last modified
Data loaded
NAICS code
326199
Employees
22
Ownership type
A

11 citations on file for this inspection.

1910.36 D01

Serious Gravity 5 2 instances 7 exposed
Issued
Apr 9, 2025
Abate by
May 5, 2025
Penalty
Initial $3,783 · Current $2,648 Reduced
29 CFR 1910.36(d)(1): Employee(s) were not able to open an exit route door from the inside at all times without keys, tools, or special knowledge:  a) 700 Washington Street New Castle, De 19720 (side entry door near screw machines): On or about January 16, 2025, employees were exposed to delayed egress hazards due to observed turn knob locks attachment on the exit door.   b) 700 Washington Street New Castle, De 19720 (Guitar Pick Printing Department-Barn Door): On or about January 16, 2025, employees were exposed to delayed egress hazards due to a barn style door that opened left to right and did not open with the path of egress.
Recent events (1)
  • — Z (S) $3783

1910.37 B02

Serious Gravity 5 2 instances 7 exposed
Issued
Apr 9, 2025
Abate by
May 5, 2025
Penalty
Initial $3,783 · Current $2,648 Reduced
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit":  a) 700 Washington Street New Castle, De 19720 (Tool Room): On or about January 16, 2025, emergency exits were not visible or marked with an "exit" sign as required.  b) 700 Washington Street New Castle, De 19720 (Guitar Pick Printing Department- Barn Door): On or about January 16, 2025, emergency exits were not visible or marked with an "exit" sign as required.
Recent events (1)
  • — Z (S) $3783

1910.37 B04

Serious Gravity 5 1 instance 16 exposed
Issued
Apr 9, 2025
Abate by
May 5, 2025
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(4): Signs were not posted along the exit access indicating the direction of travel to the nearest exit and exit discharge when the direction of travel to the exit or exit discharge was not immediately apparent:  a) 700 Washington Street New Castle, De 19720: On or about January 16, 2025, the employer failed to provide directional signs along the exit access to provide direction of travel to the nearest exit and exit discharge of an approximately 25,000 ft.� warehouse.
Recent events (1)
  • — Z (S) $0

1910.38 D

Serious Gravity 5 1 instance 16 exposed
Issued
Apr 9, 2025
Abate by
May 5, 2025
Penalty
Initial $0 · Current $0
29 CFR 1910.38(d): Employee alarm system. An employer must have and maintain an employee alarm system. The employee alarm system must use a distinctive signal for each purpose and comply with the requirements in �� 1910.165.  a) 700 Washington St., New Castle, DE 19720 (warehouse): On or about January 16, 2025, the building was not provided with an alarm, paging system or other method to alert employees to evacuate in the event of an emergency.
Recent events (1)
  • — Z (S) $0

1910.38 E

Serious Gravity 5 1 instance 16 exposed
Issued
Apr 9, 2025
Abate by
May 5, 2025
Penalty
Initial $0 · Current $0
29 CFR 1910.38(e): Training. An employer must designate and train employees to assist in a safe and orderly evacuation of other employees.  a) 700 Washington St., New Castle, DE 19720 (Throughout): On or about January 16, 2025, the employer failed to train employees in the safe and orderly evacuation procedures to be used at the facility in the event of an emergency.
Recent events (1)
  • — Z (S) $0

1910.212 A01

Serious Gravity 10 7 instances 2 exposed
Issued
Apr 9, 2025
Abate by
May 5, 2025
Penalty
Initial $6,620 · Current $4,634 Reduced
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks:    a) 700 Washington St., New Castle, DE 19720 (Lathe-tool room): On or about January 16, 2025, employees were exposed to unguarded rotating parts on the #15 Rathbone lathe unknown model exposing employees to caught in/struck by hazards.  b) 700 Washington St., New Castle, DE 19720 (#7 mechanical power press- ODI-punch press): On or about January 16, 2025 and days prior to thereto, employees were exposed to unguarded rotating parts on the #7 mechanical power press-V&O Presses OBI-punch press Serial #25ST-294 exposing employees to caught in  hazards.  c) 700 Washington St., New Castle, DE 19720 (Screw Machines): On or about January 16, 2025, employees were exposed to unguarded rotating parts on the Brown & Sharpe Screw Machine Serial # 542-00-9513-1/2 exposing employees to caught in hazards.  d) 700 Washington St., New Castle, DE 19720 (Screw Machines): On or about January 16, 2025, employees were exposed to unguarded rotating parts on the Brown & Sharpe Screw Machine Serial # 5422-8616-1 1/4 exposing employees to caught in hazards.  e) 700 Washington St., New Castle, DE 19720 (Screw Machines): On or about January 16, 2025, employees were exposed to unguarded rotating parts on the Brown & Sharpe Screw Machine Serial # 542-00-7393 exposing employees to caught in hazards.  f) 700 Washington St., New Castle, DE 19720 (Screw Machines): On or about January 16, 2025, employees were exposed to unguarded rotating parts on the Brown & Sharpe Screw Machine Serial # 542-00-9707 -2/4 exposing employees to caught in hazards.  g) 700 Washington St., New Castle, DE 19720 (Bridgeport - mill machine): On or about January 16, 2025, employees were exposed to rotating parts on the Bridgeport-mill machine serial #A-25 model 6-X005 when the employer failed to provide guarding at the point of operation.
Recent events (1)
  • — Z (S) $6620

1910.215 A01

Serious Gravity 5 1 instance 1 exposed
Issued
Apr 9, 2025
Penalty
Initial $4,729 · Current $3,310 Reduced
29 CFR 1910.215(a)(1): Abrasive wheel(s) used on grinding machinery were not used with safety guard(s)  a) 700 Washington St., New Castle, DE 19720 (Cincinnati 2MT Cutter and Tool Grinding Machine -tool room): On or about January 16, 2025 and days prior thereto, employees were exposed to struck by hazards when the employer failed to provide guards on the Cincinnati 2MT Cutter and Tool Grinding Machine serial # 102F-1ABF-154 with a Norton A60-OBNA2 reenforced abrasive wheel.
Recent events (1)
  • — Z (S) $4729

1910.303 B07 I

Serious Gravity 5 1 instance 1 exposed
Issued
Apr 9, 2025
Abate by
May 5, 2025
Penalty
Initial $5,675 · Current $3,973 Reduced
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment.  a) 700 Washington Street New Castle, De 19720 (Hallway to Print room): On or about January 16, 2025, and at times prior thereto and thereafter, employees were exposed to hazards when the 120 V light switch was observed energized and was not effectively closed exposing employees to shock hazards.
Recent events (1)
  • — Z (S) $5675

1910.303 E01 II

Serious Gravity 5 2 instances 3 exposed
Issued
Apr 9, 2025
Abate by
May 5, 2025
Penalty
Initial $5,675 · Current $3,973 Reduced
29 CFR 1910.303(e)(1)(ii): Electric equipment shall not be used unless markings have been placed on equipment such as voltage, current, wattage and other ratings as necessary:  a) 700 Washington St., New Castle, DE 19720: On or about January 16, 2025, and at times prior thereto and thereafter, employees were exposed to hazards when 120 V energized electrical equipment were entered without proper markings of voltage, current, wattage, or arc flash rating.  b) 700 Washington St., New Castle, DE 19720: On or about January 16, 2025, and at times prior thereto and thereafter, employees were exposed to hazards when 120 V energized electrical equipment were entered without proper markings of voltage, current, wattage, or arc flash rating.
Recent events (1)
  • — Z (S) $5675

1910.303 F02

Serious Gravity 5 3 instances 2 exposed
Issued
Apr 9, 2025
Abate by
May 5, 2025
Penalty
Initial $0 · Current $0
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:  a) 700 Washington St., New Castle, DE 19720 (Tool room): On or about January 16, 2025, and at times prior thereto and thereafter, the employer failed to properly identify all disconnect switched on the QMB SAFLEX 480V panel.  b) 700 Washington St., New Castle, DE 19720 (side entrance): On or about January 16, 2025, and at times prior thereto and thereafter, the employer failed to properly identify all breaker switches inside the Square D panel.  c) 700 Washington St., New Castle, DE 19720 (Wall next to screw department): On or about January 16, 2025, and at times prior thereto and thereafter, the employer failed to properly identify all breaker switches inside the Square D panels.
Recent events (1)
  • — Z (S) $0

1910.304 F01 VIII

Serious Gravity 5 2 instances 2 exposed
Issued
Apr 9, 2025
Abate by
May 5, 2025
Penalty
Initial $0 · Current $0
29 CFR 1910.304(f)(1)(viii):29 CFR 1910.304(f)(1)(viii): Circuit breakers used as switches in 120-volt and 277-volt, fluorescent lighting circuits were not listed and marked "SWD."  a) 700 Washington St., New Castle, DE 19720 (side entrance): On or about January 16, 2025, and at times prior thereto and thereafter, the employer failed to install "SWD" listed and labeled circuit breakers inside the Square D panel used to activate overhead lighting daily.  b) 700 Washington St., New Castle, DE 19720 (Wall next to screw department): On or about January 16, 2025, and at times prior thereto and thereafter, the employer failed to install "SWD" listed and labeled circuit breakers inside the Square D panel used to activate overhead lighting daily.
Recent events (1)
  • — Z (S) $0

View Wilmington Fibre Specialty Company, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347982746.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.