OSHA Inspection: LORD CORPORATION

Referral inspection · Health discipline

On , OSHA opened a referral health inspection of LORD CORPORATION in 601 SOUTH STREET, SAEGERTOWN, PA 16433 (NAICS 325510). OSHA activity number 348040767.

Watch Lord Corporation — free Get an email when a new federal OSHA severe-injury report for Lord Corporation is published. One employer, no account, unsubscribe in one click.
Establishment
LORD CORPORATION
Site address
601 SOUTH STREET
City
SAEGERTOWN
State
PA
ZIP
16433
Mailing
601 SOUTH STREET, SAEGERTOWN, PA 16433
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
325510
Employees
230
Ownership type
A

4 citations on file for this inspection.

1910.134 G04 I

Serious Gravity 10 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $16550.00 · Current $9000.00 Reduced
29 CFR  1910.134(g)(4)(i):During interior structural firefighting, employees who entered Immediately Dangerous to Life and Health atmospheres did not remain in visual or voice contact with one another at all times:  a. LORD Corporation, Building 8, on or about 02/09/25, and times prior thereto:  employee entered into the east section of building 8 while donning a self contained breathing apparatus during an emergency event that contained toxic smoke, and resulted in an explosion.  In addition, visual or voice contact was not established during the interior structural fire fighting event.  Four Fire brigade members responded to a "fire/smoke" event that occurred on February 9th, 2025 that subsequently lead to an explosion in mix tank #2 in building 8 of the facility.
Recent events (2)
  • — I (S) $9000
  • — Z (S) $16550

1910.134 G04 II

Serious Gravity 10 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.134(g)(4)(ii): During interior structural firefighting, at least two employees were not located outside the immediately dangerous to life or health atmosphere to provide assistance or emergency rescue:  a. LORD Corporation, Building 8, on or about 02/09/25, and times prior thereto:  four fire brigade members entered into building 8 while donning self contained breathing apparatus's during an emergency event that contained toxic smoke, and resulted in an explosion.    At least two employees were not located outside of the building 8 area to provided potential rescue or assistance.  Four Fire brigade members responded to a "fire/smoke" event that occurred on February 9th, 2025 that subsequently lead to an explosion in mix tank #2 in building 8 of the facility.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.156 C04

Serious Gravity 10 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.156(c)(4): Written procedures that describe the actions to be taken in situations involving special hazards were not included in the training and education program:  a.) LORD Corporation, Building 8, on or about 02/09/25, and times prior thereto: Written procedures were not developed to describe the actions to be taken by the fire brigade members in the event of special hazards including, but not limited to, fire events that could lead to explosions in mix tanks and other equipment onsite.  Four Fire brigade members responded to a "fire/smoke" event that occurred on February 9th, 2025 that subsequently lead to an explosion in mix tank #2 in building 8 of the facility.  b.) LORD Corporation, Building 8, on or about 02/09/25, and times prior thereto: Written procedures were not developed to describe the actions to be taken by the fire brigade members in the event of special hazards including, but not limited to, fire events that involve water reactive materials/chemicals.   The job site included water reactive materials/chemicals including, but not limited to Triethoxyvinylsilane.   c.) LORD Corporation, Building 8, on or about 02/09/25, and times prior thereto: Written procedures were not developed to describe the actions to be taken by the fire brigade members in the event of special hazards including, but not limited to, how the fire brigade would coordinate with outside fire departments, and local agencies, in the event of fire or other emergency and establishment of the incident command structure.
Recent events (3)
  • — P (S) $0
  • — I (S) $0
  • — Z (S) $0

1910.307 C

Serious Gravity 5 1 instance 10 exposed
Issued
Penalty
Initial $10050.00 · Current $9000.00 Reduced
29 CFR 1910.307(c): Equipment, wiring methods, and installations of equipment in hazardous (classified) locations were not intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location:  a.)LORD Corporation, Building 8, on or about 02/09/25, and times prior thereto: A junction box and conduit powering a Newson Gale Earth-Rite PLUS bonding/grounding system, that was attached to Mix tank #2 in Building 8, was located in a designated class I division 2 location.  The junction box and associated conduit were not rated for class I division 2 locations.
Recent events (2)
  • — I (S) $9000
  • — Z (S) $10050

View LORD CORPORATION's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 348040767.