BISMARCK, ND —
OSHA Inspection: MAGNUM ELECTRIC, INC.
Unprogrammed Other inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Other safety inspection of MAGNUM ELECTRIC, INC. in 8580 43RD AVENUE NORTHEAST, BISMARCK, ND 58503 (NAICS 238210). OSHA activity number 348131590.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- MAGNUM ELECTRIC, INC.
- Site address
- 8580 43RD AVENUE NORTHEAST
- City
- BISMARCK
- State
- ND
- ZIP
- 58503
- Mailing
- 471 CHRISTIANSON DRIVE, WEST FARGO, ND 58078
What kind of inspection was it?
- Inspection type
- Unprogrammed Other (I)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 30
- Ownership type
- A
Citations
4 citations on file for this inspection.
1926.403 B02
- Issued
- Aug 12, 2025
- Abate by
- Sep 15, 2025
- Penalty
- Initial $16,550 · Current $0 Reduced
General-duty citation text
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification. (a) On March 25, 2025, at 8580 43rd Ave Northeast in Bismarck, North Dakota, employees engaged in electrical installations on a commercial building were exposed to arcing and fire hazards where NM type cabling was used in various areas of the building as a cord and plug set that powered various lights, junction boxes, and female ends. (b) On March 25, 2025, at 8508 43rd Ave Northeast in Bismarck, North Dakota, employees engaged in electrical installations on a commercial building were exposed to arcing and fire hazards where two 4" junction boxes were suspended freely between lights.
Recent events (2)
- — I (O) $0
- — Z (S) $16550
1926.405 G02 III
- Issued
- Aug 12, 2025
- Abate by
- Sep 15, 2025
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.405(g)(2)(iii):Flexible cords were not used in continuous lengths without splice or tap: (a) On March 25, 2025, at 8580 43rd Ave Northeast in Bismarck, North Dakota, employees engaged in electrical installations on a commercial building were exposed to arcing and fire hazards where two 4" junction boxes contained splices of unknown internal continuity were suspended freely between its powered temporary flexible corded lights.
Recent events (2)
- — I (O) $0
- — Z (S) $0
1926.405 G02 IV
- Issued
- Aug 12, 2025
- Abate by
- Sep 15, 2025
- Penalty
- Initial $0 · Current $9,930
General-duty citation text
29 CFR 1926.405(g)(2)(iv): Flexible cords were not connected to devices and fittings so that strain relief is provided to prevent pull from being directly transmitted to joints or terminal screws: (a) On March 25, 2025, at 8580 43rd Ave Northeast in Bismarck, North Dakota, employees engaged in electrical installations on a commercial building were exposed to arcing and fire hazards where two 4" junction boxes were suspended freely between its powered temporary flexible corded lights allowed wiring to be pulled at the connection point.
Recent events (2)
- — I (S) $9930
- — Z (S) $0
1926.416 A01
- Issued
- Aug 12, 2025
- Abate by
- Sep 15, 2025
- Penalty
- Initial $9,457 · Current $5,674 Reduced
General-duty citation text
29 CFR 1926.416(a)(1):The employer permitted employees to work in close proximity to energized, unguarded, and ungrounded electric power circuits that the employee could contact in the course of their work: (a) On March 25, 2025, at 8580 43rd Ave Northeast in Bismarck, North Dakota, an employee engaged in electrical installations on a commercial building was exposed to fire hazards when working in the accessibility zone without the proper PPE when the two electrical panels had exposed energized components around the circuit breaker trim plate.
Recent events (2)
- — I (S) $5674.2
- — Z (S) $9457
More inspections at Magnum Electric, INC.
View Magnum Electric, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 238210)
More inspections in ND
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 348131590.