NEW CASTLE, PA —
OSHA Inspection: NEW CASTLE COLD STORAGE, INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of NEW CASTLE COLD STORAGE, INC. in 424 SOUTH CASCADE STREET, NEW CASTLE, PA 16101 (NAICS 493120). OSHA activity number 348182395.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- NEW CASTLE COLD STORAGE, INC.
- Site address
- 424 SOUTH CASCADE STREET
- City
- NEW CASTLE
- State
- PA
- ZIP
- 16101
- Mailing
- PO BOX 7128, NEW CASTLE, PA 16107
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 493120
- Employees
- 15
- Ownership type
- A
Citations
9 citations on file for this inspection.
1910.37 A04
- Issued
- Aug 14, 2025
- Abate by
- Sep 10, 2025
- Penalty
- Initial $3,618 · Current $2,533 Reduced
General-duty citation text
29 CFR 1910.37(a)(4):Safeguard(s) designed to protect employees during an emergency (e.g., sprinkler systems, alarm systems, fire doors, exit lighting), were not in proper working order at all times: A.) New Castle Cold Storage, Inc., New Building, on or about 4/15/25 and times prior thereto: the Exit sign to the door in the freezer had been damaged and no longer clearly indicated the presence of an exit. B.) New Castle Cold Storage, Inc., New Building, on or about 4/15/25 and times prior thereto: Ice was built up on the panic bar of the exit door. The panic bar was not able to be opened without excessive force. ABATEMENT CERTIFICATION REQUIRED: Abatement certification is required within 10 days after the abatement date noted on the citation (see below). This certification shall include a statement that abatement is complete, the date abatement was completed, method of abatement, and state that employees and their representatives were informed of this abatement.
Recent events (2)
- — I (S) $2532.6
- — Z (S) $3618
1910.101 B
- Issued
- Aug 14, 2025
- Abate by
- Sep 10, 2025
- Penalty
- Initial $1,809 · Current $1,266 Reduced
General-duty citation text
29 CFR 1910.101(b):The in-plant handling, storage, and utilization of all compressed gases in cylinders, portable tanks, rail tankcars, or motor vehicle cargo tanks were not in accordance with Compressed Gas Association Pamphlet P-1-1965, which is incorporated by reference as specified in CFR 1910.6: A.) New Castle Cold Storage, Inc., Back dock, on or about 4/15/25 and times prior thereto: A compressed gas cylinder of nitrogen on the scissor lift work platform was not in a secure upright position, was laying on its side, and not secured by any device to prevent the cylinder from falling, rolling, or getting knocked over. ABATEMENT CERTIFICATION REQUIRED: Abatement certification is required within 10 days after the abatement date noted on the citation (see below). This certification shall include a statement that abatement is complete, the date abatement was completed, method of abatement, and state that employees and their representatives were informed of this abatement.
Recent events (2)
- — I (S) $1266.3
- — Z (S) $1809
1910.157 E03
- Issued
- Aug 14, 2025
- Penalty
- Initial $1,809 · Current $1,266 Reduced
General-duty citation text
29 CFR 1910.157(e)(3):Portable fire extinguishers were not subjected to an annual maintenance check: A.) New Castle Cold Storage, Inc., New Building, on or about 4/15/25 and times prior thereto: the employer was not ensuring that all portable fire extinguishers were receiving annual inspections. The last inspection of the fire extinguishers had occurred in 2022. NO ABATEMENT CERTIFICATION OR DOCUMENATION REQUIRED
Recent events (2)
- — I (S) $1266.3
- — Z (S) $1809
1910.157 G01
- Issued
- Aug 14, 2025
- Abate by
- Sep 10, 2025
- Penalty
- Initial $1,809 · Current $1,266 Reduced
General-duty citation text
29 CFR 1910.157(g)(1):An educational program was not provided for all employees to familiarize them with the general principles of fire extinguisher use and the hazards involved with incipient stage fire fighting: A.) New Castle Cold Storage, Inc., New Building, on or about 4/15/25 and times prior thereto: Portable multi-purpose dry chemical fire extinguishers were distributed throughout the facility for employees to use in the event of an incipient stage fire. Employees did not have fire extinguisher training. ABATEMENT CERTIFICATION REQUIRED: Abatement certification is required within 10 days after the abatement date noted on the citation (see below). This certification shall include a statement that abatement is complete, the date abatement was completed, method of abatement, and state that employees and their representatives were informed of this abatement.
Recent events (2)
- — I (S) $1266.3
- — Z (S) $1809
1910.305 B01 II
- Issued
- Aug 14, 2025
- Abate by
- Sep 10, 2025
- Penalty
- Initial $1,809 · Current $1,266 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(ii):Unused openings in boxes, cabinets, or fittings were not effectively closed: A.) New Castle Cold Storage, Inc., Back Dock, on or about 4/15/25 and times prior thereto: two knockout box electrical receptacles were stacked on top of each other at dock 8. There was space between the boxes that was open exposing employees to unguarded live parts. ABATEMENT CERTIFICATION REQUIRED: Abatement certification is required within 10 days after the abatement date noted on the citation (see below). This certification shall include a statement that abatement is complete, the date abatement was completed, method of abatement, and state that employees and their representatives were informed of this abatement.
Recent events (2)
- — I (S) $1266.3
- — Z (S) $1809
1910.145 C03
- Issued
- Aug 14, 2025
- Abate by
- Sep 10, 2025
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.145(c)(3):Safety instruction sign(s) were not used where there was a need for general instructions and suggestions relative to safety measure(s): A.) New Castle Cold Storage, Inc., on or about 4/15/25 and times prior thereto: the storage racking systems in the facility were not marked with the load capacity limits. ABATEMENT CERTIFICATION REQUIRED: Abatement certification is required within 10 days after the abatement date noted on the citation (see below). This certification shall include a statement that abatement is complete, the date abatement was completed, method of abatement, and state that employees and their representatives were informed of this abatement.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.145 F03
- Issued
- Aug 14, 2025
- Abate by
- Sep 10, 2025
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.145(f)(3): Tags were not used as a means to prevent accidental injury of illness to employees who are exposed to hazardous or potentially hazardous conditions, equipment, or operations which were out of the ordinary, unexpected, or not readily apparent: A.) New Castle Cold Storage, Inc., Middle Dock, on or about 4/15/25 and times prior thereto: The insulation on the charging cable of Crown Forklift Model 4700 Serial Number 1A558850 was stripped back exposing employees to the internal copper wiring. The forklift was not tagged or posted with signs to alert employees that there was a problem with the forklift and that it must not be used. ABATEMENT CERTIFICATION REQUIRED: Abatement certification is required within 10 days after the abatement date noted on the citation (see below). This certification shall include a statement that abatement is complete, the date abatement was completed, method of abatement, and state that employees and their representatives were informed of this abatement.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.303 G01 II
- Issued
- Aug 14, 2025
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1)(ii):The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage: A.) New Castle Cold Storage, Inc., Front Dock, on or about 4/15/25 and times prior thereto: The area in front of the electrical panel boxes were used for storage. Items being stored in the area are boxes on top of pallets. NO ABATEMENT CERTIFICATION OR DOCUMENATION REQUIRED
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.1200 F06
- Issued
- Aug 14, 2025
- Abate by
- Sep 10, 2025
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.1200(f)(6):The employer did not ensure that each container of hazardous chemicals in the workplace was labeled, tagged or marked with the information specified under paragraphs (f)(6)(i) through (ii) of this section: A.) New Castle Cold Storage, Inc., Back Dock, on or about 4/15/25 and times prior thereto: The spray bottle on the JLG Lift was not labeled to identify the chemical(s) nor the hazardous properties of the chemical(s) contained within the container ABATEMENT CERTIFICATION REQUIRED: Abatement certification is required within 10 days after the abatement date noted on the citation (see below). This certification shall include a statement that abatement is complete, the date abatement was completed, method of abatement, and state that employees and their representatives were informed of this abatement.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at NEW Castle Cold Storage, INC.
View NEW Castle Cold Storage, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 493120)
More inspections in PA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 348182395.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.