RINCON, GA —
OSHA Inspection: DRT AMERICA LLC
Referral inspection · Health discipline
At a glance
On , OSHA opened a referral health inspection of DRT AMERICA LLC in 400 GOVERNOR TREUTLEN, RINCON, GA 31326 (NAICS 325194). OSHA activity number 348232299.
Where did this inspection happen?
- Establishment
- DRT AMERICA LLC
- Site address
- 400 GOVERNOR TREUTLEN
- City
- RINCON
- State
- GA
- ZIP
- 31326
- Mailing
- 400 GOVERNOR TREUTLEN, RINCON, GA 31326
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 325194
- Employees
- 44
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.119 D03 I D
- Issued
- Abate by
- Penalty
- Initial $13240.00 · Current $9268.00 Reduced
F006P127
General-duty citation text
29 CFR 1910.119(d)(3)(i)(D): The employer did not include, in the process safety information compilation, the relief system design and the design basis. (a) In the production area, on or about August 20, 2025 and at times prior to, the employer exposed employees to fire and explosion hazards in that process safety information (PSI) for pressure relief devices (PRD) was not maintained or available for PRDs in use on the production unit.
Recent events (2)
- — I (S) $9268
- — Z (S) $13240
1910.119 J02
- Issued
- Abate by
- Penalty
- Initial $13240.00 · Current $9268.00 Reduced
P127
General-duty citation text
29 CFR 1910.119(j)(2): The employer failed to develop and/or implement mechanical integrity inspection and test procedures. (a) The employer failed to develop an effective written mechanical integrity (MI) procedure for pressurized piping inspections when pressurized piping was inspected using procedures that did not establish a set of specific actions and strategies detailing the scope, extent, methods and timing of specific inspection activities in order to determine the condition of pressurized piping based on defined/expected damage. Actions and strategies that were not addressed in the inadequate procedure include but are not limited to the following: 1) define the type(s) of inspection needed, (e.g. internal, external, on-stream, nonintrusive); 2) identify the next inspection date for each inspection type; 3) describe the inspection methods and NDE techniques; 4) describe the extent and locations of inspection and NDE at CMLs; 5) describe the surface cleaning requirements needed for inspection and examinations for each type of inspection; 6) describe the requirements of any needed pressure test (e.g. type of test, test pressure, test temperature, and duration); 7) describe any required repairs if known or previously planned before the upcoming inspection. 8) describe the types of damage anticipated or experienced in the piping systems; 9) define the location of the expected damage; 10) define any special access and preparation needed. Pressurized piping inspected using inadequate written procedures include at least the alpha-pinene piping. This condition exposed employees to the hazard of explosion/fire. This violation was observed at DRT America LLC on or about August 20, 2025, located at 400 Governor Treutlen Drive, Rincon, Georgia.
Recent events (2)
- — I (S) $9268
- — Z (S) $13240
1910.119 J04 I
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
P127
General-duty citation text
29 CFR 1910.119(j)(4)(i): The employer did not perform inspection and tests on process equipment. (a) In the production area, on or about August 20, 2025 and at time prior to, the employer exposed employees to fire and explosion hazards in that piping systems containing crude sulfate turpentine and alpha-pinene were not inspected or tested for integrity.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections at DRT AMERICA LLC
RINCON, GA—2026-04-07
DRT AMERICA LLC
RINCON, GA—2026-01-29
DRT AMERICA LLC
View DRT AMERICA LLC's full OSHA safety record →
More inspections in this industry (NAICS 325194)
RINCON, GA—2026-04-07
DRT AMERICA LLC
PANAMA CITY, FL—2026-02-10
KRATON CHEMICAL COMPANY
RINCON, GA—2026-01-29
DRT AMERICA LLC
SLOANS VALLEY, KY—2025-06-04
68044 - KINGSFORD MANUFACTURING COMPANY
FAIRMONT, WV—2025-04-08
PRIME 6, LLC
More inspections in GA
ROME, GA—2026-07-13
CAMP INDUSTRIES
SOUTH FULTON, GA—2026-07-10
REEDWICK, LLC
CONYERS, GA—2026-07-10
GOLDEN STATE FOODS
DALTON, GA—2026-07-10
ENGINEERED FLOORS, LLC
METTER, GA—2026-07-10
M.A.P.C CONSTRUCTION, LLC
Source