Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: EAST COAST REPAIR AND FABRICATION, LLC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of EAST COAST REPAIR AND FABRICATION, LLC in 1201 TERMINAL AVENUE, NEWPORT NEWS, VA 23607 (NAICS 336611). OSHA activity number 348258591.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch East Coast Repair and Fabrication, LLC — free Get an email when a new federal OSHA severe-injury report for East Coast Repair and Fabrication, LLC is published. One employer, no account, unsubscribe in one click.
Site address
1201 TERMINAL AVENUE
City
NEWPORT NEWS
State
VA
ZIP
23607
Mailing
1201 TERMINAL AVENUE, NEWPORT NEWS, VA 23607
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
336611
Employees
120
Ownership type
A

12 citations on file for this inspection.

1910.212 A01

Serious Gravity 5 1 instance 1 exposed
Issued
Aug 5, 2025
Penalty
Initial $11,491 · Current $8,044 Reduced
29 CFR 1910.212(a)(1): Machine guarding was not provided to protect operator(s) and other employees from hazard(s) created by:   a) 1201 Terminal Ave., Newport News, Virginia 23607 (shipyard): On or about May 20, 2025, employees were exposed to unguarded cutting edges on a Jet 8�14 Horizontal Geared Head Band Saw, Model: HPS-814GH.
Recent events (2)
  • — I (S) $8043.7
  • — Z (S) $11491

1910.253 B02 II

Serious Gravity 5 1 instance 4 exposed
Issued
Aug 5, 2025
Penalty
Initial $11,491 · Current $8,044 Reduced
29 CFR 1910.253(b)(2)(ii): Assigned storage spaces for compressed gas cylinders were not located where the cylinders will not be knocked over or damaged by passing or falling objects, or subject to tampering by unauthorized persons.  a) 1201 Terminal Ave., Newport News, Virginia 23607 (shipyard): On or about May 20, 2025, and times prior thereto, compressed gas cylinders ( Argon/ Oxygen) was not chained or secured from falling exposing employees to potential struck-by hazards.
Recent events (2)
  • — I (S) $8043.7
  • — Z (S) $11491

1910.303 B01

Serious Gravity 5 1 instance 2 exposed
Issued
Aug 5, 2025
Penalty
Initial $10,215 · Current $7,151 Reduced
29 CFR  1910.303(b)(1):Electrical equipment was not free from recognized hazards that were likely to cause death or serious physical harm to employees:  a) 1201 Terminal Ave., Newport News, Virginia 23607 (Fabrication Shop): On or about May 20, 2025, employees were exposed to potential electrical shock hazards when the employer failed to ensure the 480 V Square D panel were installed to manufacturer specifications and were free of recognized hazards.
Recent events (2)
  • — I (S) $7150.5
  • — Z (S) $10215

1910.303 B02

Serious Gravity 5 4 instances 4 exposed
Issued
Aug 5, 2025
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:    a) 1201 Terminal Ave., Newport News, Virginia 23607 (Fabrication Shop): On or about May 20, 2025, employees were exposed to potential electrical shock hazards when the employer allowed employees to improperly install  a 480 V Square D panel with gauge wire and pigtails.   b) 1201 Terminal Ave., Newport News, Virginia 23607 (Fabrication Shop -Shop Load Center): On or about May 20, 2025, employees were exposed to potential electrical shock hazards when the employer allowed employees to improperly install pigtails in a 240/120 V panel.    c) 1201 Terminal Ave., Newport News, Virginia 23607 (Fabrication Shop): On or about May 20, 2025, employees were exposed to potential electrical shock hazards when the employer allowed employees to use flexible cords that were not used in accordance with the manufacturer's specifications.   d) 1201 Terminal Ave., Newport News, Virginia 23607 (Tool Room-Shipping and Receiving): On or about May 20, 2025, employees were exposed to potential electrical shock hazards when the employer allowed employees to use flexible cords that were not used in accordance with the manufacturer's specifications.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 B08 I

Serious Gravity 5 1 instance 1 exposed
Issued
Aug 5, 2025
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(8)(i): Electrical equipment was not firmly secured to the surface on which it was mounted.    a) 1201 Terminal Ave., Newport News, Virginia 23607 (Fabrication Shop): On or about May 20, 2025, employees were exposed to potential electrical shock hazards when the employer failed to ensure the 480 V Square D panel was installed to manufacturer specifications.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 B07

Serious Gravity 5 1 instance 2 exposed
Issued
Aug 5, 2025
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(7): Mechanical execution of work. Electric equipment was not installed in a neat and workmanlike manner.   a) 1201 Terminal Ave., Newport News, Virginia 23607 (Fabrication Shop): On or about May 20, 2025, and at times prior thereto and thereafter, the brand electrical junction box was not effectively closed exposing employees to shock hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 E01 II

Serious Gravity 5 2 instances 2 exposed
Issued
Aug 5, 2025
Penalty
Initial $0 · Current $0
29 CFR 1910.303(e)(1)(ii): Electric equipment shall not be used unless markings have been placed on equipment such as voltage, current, wattage and other ratings as necessary:    a) 1201 Terminal Ave., Newport News, Virginia 23607 (Fabrication Shop): On or about May 20, 2025 and at times prior thereto and thereafter, electrical maintenance employees were exposed to hazards when 480 V/240 V energized electrical equipment were installed/repaired without proper markings of voltage, current, wattage, or arc flash rating.    b) 1201 Terminal Ave., Newport News, Virginia 23607 (ECR Base A - CS-11): On or about May 20, 2025, and at times prior thereto and thereafter, electrical maintenance employees were exposed to hazards when 480 V/220 V energized electrical equipment were installed/repaired without proper markings of voltage, current, wattage, or arc flash rating.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 G01 II

Serious Gravity 5 1 instance 1 exposed
Issued
Aug 5, 2025
Penalty
Initial $7,660 · Current $5,362 Reduced
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:      a) 1201 Terminal Ave., Newport News, Virginia 23607 (Fabrication Shop): On or about May 20, 2025, employees were exposed to trip and fall hazards due to unauthorized materials stored within 36 inches of energized electrical panels.
Recent events (2)
  • — I (S) $5362
  • — Z (S) $7660

1910.304 B03 II A

Serious Gravity 5 1 instance 1 exposed
Issued
Aug 5, 2025
Penalty
Initial $11,491 · Current $8,044 Reduced
29 CFR 1910.304(b)(3)(ii)(A): All 125-volt, single-phase, 15, 20 and 30-ampere receptacle outlets that are not part of the permanent wiring of the building or structure and that are in use by personnel did not have ground-fault circuit-interrupter protection for personnel.    a) 1201 Terminal Ave., Newport News, Virginia 23607 (Bay A-COW Shed CS-11): On or about May 20, 2025, employees were exposed to electrical shock hazards when the employer allowed a temporary electric shed (CS-11) to be utilized without ground fault circuit interruption protection.
Recent events (2)
  • — I (S) $8043.7
  • — Z (S) $11491

1910.1200 G08

Serious Gravity 5 1 instance 1 exposed
Issued
Aug 5, 2025
Penalty
Initial $11,491 · Current $8,044 Reduced
29 CFR 1910.1200(g)(8): The employer did not maintain in the workplace copies of the required safety data sheets for each hazardous chemical, and did not ensure that they were readily accessible during each work shift to employees when they were in their work area(s)    a) 1201 Terminal Ave., Newport News, Virginia 23607 (Fabrication Shop): On or about May 20, 2025, and at times prior thereto, employees were exposed to hazardous chemicals such as but not limited to gear oils(s) (Shell Spirax S4 AX 80W-90) and Radcolube Hydraulic Fluid without having safety data sheets (SDS) sheets readily available.
Recent events (2)
  • — I (S) $8043.7
  • — Z (S) $11491

1910.1200 G11

Serious Gravity 5 1 instance 1 exposed
Issued
Aug 5, 2025
Penalty
Initial $0 · Current $0
29 CFR 1910.1200(g)(11): Safety data sheets were not made readily available, upon request, to designated representatives, the Assistant Secretary, and the Director, in accordance with the requirements of 29 CFR 1910.1020(e)   a) 1201 Terminal Ave., Newport News, Virginia 23607 (shipyard): On or about May 20, 2025, the employer failed to provide safety data sheets for Shell Spirax S4 AX 80W-90 and Radcolube Hydraulic Fluid upon request by CSHO's on May 20, 2025 for review.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 A02 I A

Other-than-serious 2 instances 2 exposed
Issued
Aug 5, 2025
Penalty
Initial $0 · Current $0
29 CFR 1910.305(a)(2)(i)(A): Temporary electrical power and lighting installations of 600 volts, nominal, or less may be used only during and for remodeling, maintenance, or repair of buildings, structures, or equipment, and similar activities.    a) 1201 Terminal Ave., Newport News, Virginia 23607 (Fabrication Shop): On or about May 20, 2025, the employer did not ensure that temporary lighting used was removed and permanent lighting installed.      b) 1201 Terminal Ave., Newport News, Virginia 23607 (Tool Room-Shipping and Receiving Area): On or about May 20, 2025, the employer did not ensure that temporary lighting used was removed and permanent lighting installed.  Employees engaged in the shipping and receiving window installed temporary lighting that was used as permanent lighting.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0