Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: RAVEN BUTENE-1, LLC

Unprogrammed Related inspection · Safety discipline

On , OSHA opened an unprogrammed Related safety inspection of RAVEN BUTENE-1, LLC in 10328 INTERSTATE 10 SERVICE ROAD, BAYTOWN, TX 77521 (NAICS 325110). OSHA activity number 348346701.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Raven Butene-1, LLC — free Get an email when a new federal OSHA severe-injury report for Raven Butene-1, LLC is published. One employer, no account, unsubscribe in one click.
Establishment
RAVEN BUTENE-1, LLC
Site address
10328 INTERSTATE 10 SERVICE ROAD
City
BAYTOWN
State
TX
ZIP
77521
Mailing
602 SAWYER STREET SUITE 200, HOUSTON, TX 77007
Inspection type
Unprogrammed Related (G)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Last modified
Data loaded
NAICS code
325110
Employees
56
Ownership type
A

6 citations on file for this inspection.

1910.119 F04

Other-than-serious Gravity 10 1 instance 4 exposed
Issued
Dec 17, 2025
Abate by
Feb 5, 2026
Penalty
Initial $11,585 · Current $11,585
29 CFR 1910.119(f)(4): The employer did not develop and implement safe work practices to provide for the control of hazards during operations such as lockout/tagout; confined space entry; opening process equipment or piping; and control over entrance into a facility by maintenance, contractor, laboratory, or other support personnel:  On or about June 24, 2025, in the Raven facility, the host employer (Raven Butene-1) did not fully implement all elements of its existing safe work practices intended to control entrance into certain PSM covered process units by contract personnel, in that the host employer relied on permit authorization and supervision controls rather than a process-unit-specific method to verify contract employees on the unit.
Recent events (2)
  • — I (O) $11585
  • — Z (S) $11585

1910.119 J02

Serious Gravity 10 2 instances 6 exposed
Issued
Dec 17, 2025
Abate by
Feb 5, 2026
Penalty
Initial $11,585 · Current $11,585
29 CFR 1910.119(j)(2): The employer did not establish and implement written procedures to maintain the on-going integrity of process equipment:  a) On or about June 24, 2025, in Raven facility, the host employer, did not fully document a task-specific procedure addressing the cleaning and decontamination activities associated with Vessel 307 A/B within its existing maintenance work practice programs.
Recent events (2)
  • — I (S) $11585
  • — Z (S) $11585

1910.132 D02

Serious Gravity 10 1 instance 6 exposed
Issued
Dec 17, 2025
Abate by
Feb 5, 2026
Penalty
Initial $11,585 · Current $11,585
29 CFR 1910.132(d)(2): The employer did not verify that the required workplace hazard assessment had been performed through a written certification that identifies the workplace evaluated; the person certifying that the evaluation has been performed; the date(s) of the hazard assessment; and, which identified the document as a certification of hazard assessment.  On or about June 24, 2025, at the Raven facility, the employer did not maintain written certification verifying that a workplace hazard assessment addressing personal protective equipment requirements had been performed for an initial line break activity.
Recent events (2)
  • — I (S) $11585
  • — Z (S) $11585

1910.134 C01

Serious Gravity 10 1 instance 6 exposed
Issued
Dec 17, 2025
Abate by
Feb 5, 2026
Penalty
Initial $11,585 · Current $11,585
29 CFR 1910.134(c)(1): A written respiratory protection program that included the provisions in 29 CFR 1910.134(c)(1)(i) - (ix) with worksite specific procedures was not established and implemented for required respirator use:   On or about June 24, 2025, and at times prior, at the Raven facility, the employer did not fully document task-specific criteria for determining when respiratory protection would be required for employees observing initial line break activities involving hazardous chemicals.
Recent events (2)
  • — I (S) $11585
  • — Z (S) $11585

1910.134 E01

Deleted Serious Gravity 10 1 instance 6 exposed
Issued
Dec 17, 2025
Abate by
Feb 5, 2026
Penalty
Initial $0 · Current $0
29 CFR 1910.134(e)(1): The employer did not provide a medical evaluation to determine the employee's ability to use a respirator, before the employee was fit tested or required to use the respirator in the workplace:   On or about June 24, 2025 and times prior too, in the Raven Butene-1 facility, the employees were not medically evaluated to determine their ability to use the respirator, while working with the hazardous chemicals.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.134 F02

Deleted Serious Gravity 10 1 instance 6 exposed
Issued
Dec 17, 2025
Abate by
Feb 5, 2026
Penalty
Initial $0 · Current $0
29 CFR 1910.134(f)(2): The employer did not ensure that an employee using a tight-fitting facepiece respirator is fit tested prior to initial use of the respirator, whenever a different respirator facepiece (size, style, model or make) is used, and at least annually thereafter.  On or about June 24, 2025 and time prior too, in the Raven Butene-1 facility, the employees were not fit tested for the respirators, while working with the hazardous chemicals.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 348346701.