On , OSHA opened a planned safety inspection of INNTRUSTED, LLC in 2500 CHANNING WAY, IDAHO FALLS, ID 83404 (NAICS 721110). OSHA activity number 348649179.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- INNTRUSTED, LLC
- Site address
- 2500 CHANNING WAY
- City
- IDAHO FALLS
- State
- ID
- ZIP
- 83404
- Mailing
- PO BOX 1491, IDAHO FALLS, ID 83403
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 721110
- Employees
- 26
- Ownership type
- A
Citations
7 citations on file for this inspection.
1910.303 B02
- Issued
- Apr 13, 2026
- Abate by
- May 7, 2026
- Penalty
- Initial $6,431 · Current $2,412 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a) Pantry Room: On December 17, 2025, a refrigerator was observed plugged into an extension cord, plugged into a surge protector, plugged into another extension cord then plugged into a 110v outlet in another part of the room. Note: Abatement certification is required for this item.
Recent events (2)
- — I (S) $2412
- — Z (S) $6431
1910.305 G01 IV A
- Issued
- Apr 13, 2026
- Abate by
- May 7, 2026
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A):Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: a) Pantry room: On December 17, 2025, multiple extension cords were observed supplying power to a refrigerator. Note: Abatement certification is required for this item.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 B02 I
- Issued
- Apr 13, 2026
- Abate by
- May 7, 2026
- Penalty
- Initial $6,431 · Current $3,215 Reduced
General-duty citation text
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy: a) Laundry Room: On December 17, 2025, the faceplate was missing from the receptacle behind the washing machine. NOTE: Abatement certification is required for this item.
Recent events (2)
- — I (S) $3215
- — Z (S) $6431
1910.305 D02
- Issued
- Apr 13, 2026
- Abate by
- May 7, 2026
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(d)(2): Panelboards mounted in cabinets, cutout boxes, or enclosures designed for the purpose and were not dead front: a) Electrical Room, On December 17, 2025: the MPDSS, 600 volt, electrical panel did not have a dead front. NOTE: Abatement certification is required for this item.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.334 A01
- Issued
- Apr 13, 2026
- Penalty
- Initial $6,431 · Current $3,215 Reduced
General-duty citation text
29 CFR 1910.334(a)(1): Flexible electric cords were fastened with staples or otherwise hung in such a fashion as could damage the outer jacket or insulation: a) Pump Room: On December 17, 2025, the power cord suppling power to a pipe thermometer was attached to the wall by staples. Note: Abatement certification is required for this item.
Recent events (2)
- — I (S) $3215
- — Z (S) $6431
1910.334 A02 II
- Issued
- Apr 13, 2026
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.334(a)(2)(ii):There was a defect or evidence of damage that could have exposed an employee to injury and the defective or damaged item was not removed from service and an employee was using it before repairs and tests necessary to render the equipment safe were made: a) Pump Room: On December 17, 2025, a damaged cord suppling power to a pipe thermometer was observed with multiple field repairs using wire nuts. Note: Abatement certification is required for this item.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 G01
- Issued
- Apr 13, 2026
- Abate by
- May 7, 2026
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1):Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: a) Communications Room: On December 17, 2025, miscellaneous items were stacked in front of three electrical panels. NOTE: Abatement certification is required for this item.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Inntrusted, LLC
View Inntrusted, LLC's full OSHA safety record →
More inspections in this industry (NAICS 721110)
More inspections in ID
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 348649179.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.