SAN DIEGO, CA —
OSHA Inspection: MARINE CORPS COMMUNITY SERVICES SAN DIEGO
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of MARINE CORPS COMMUNITY SERVICES SAN DIEGO in 3800 CHOSIN AVE, SAN DIEGO, CA 92140 (NAICS 928110). OSHA activity number 106395981.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- MARINE CORPS COMMUNITY SERVICES SAN DIEGO
- Site address
- 3800 CHOSIN AVE
- City
- SAN DIEGO
- State
- CA
- ZIP
- 92140
- Mailing
- 1600 HENDERSON AVE., BLDG. 31, STE. 109, SAN DIEGO, CA 92140
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- N
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 928110
- SIC code (legacy)
- 9711
- Employees
- 300
- Ownership type
- D
Citations
6 citations on file for this inspection.
1960.8 A
- Issued
- Nov 15, 2004
- Abate by
- Dec 10, 2004
General-duty citation text
1960.(8)(a) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to the of electrical shock, burns or electrocution due to the lack of Ground Fault Circuit Interrupter(GFCI) protection on circuits in wet locations(s) such as, along the outside of Bldg #148. Thirteen portable 120 volts battery charges are used on a daily bases. Wet weather exposes employees while connecting the battery charger cables to their EZ Carts. Among other methods, one feasible and acceptable abatement method to correct these hazards is to install GFCI protected outlets and/or circuit breakers on all receptacles and equipment in required areas per the National Electrical Code Section 210-8(a)(3): a)Marine Corps Community Services: Thirteen EZ Go Cart battery chargers are not equipped with a ground-fault circuit-interrupter to protect personnel from electrocution. Battery chargers are located outside the Bldg. #148 and exposed to wet weather.
1910.213 D01
- Issued
- Nov 15, 2004
- Abate by
- Dec 10, 2004
1910.213 H04
- Issued
- Nov 15, 2004
- Abate by
- Dec 10, 2004
1910.178 L06
- Issued
- Nov 15, 2004
- Abate by
- Dec 10, 2004
1910.212 A01
- Issued
- Nov 15, 2004
- Abate by
- Dec 10, 2004
1910.253 B04 III
- Issued
- Nov 15, 2004
- Abate by
- Dec 10, 2004
More inspections at Marine Corps Community Services SAN Diego
View Marine Corps Community Services SAN Diego's full OSHA safety record →
More inspections in this industry (NAICS 928110)
More inspections in CA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 106395981.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.