SAN DIEGO, CA —
OSHA Inspection: MARINE CORPS COMMUNITY SERVICES SAN DIEGO
Unprogrammed Other inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Other safety inspection of MARINE CORPS COMMUNITY SERVICES SAN DIEGO in 3800 CHOSIN AVE MCEX, BLDS 11 & 16, SAN DIEGO, CA 92140 (NAICS 452111). OSHA activity number 336161997.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- MARINE CORPS COMMUNITY SERVICES SAN DIEGO
- Site address
- 3800 CHOSIN AVE MCEX, BLDS 11 & 16
- City
- SAN DIEGO
- State
- CA
- ZIP
- 92140
- Mailing
- 1600 HENDERSON AVE, BLDG 5W, SAN DIEGO, CA 92140
What kind of inspection was it?
- Inspection type
- Unprogrammed Other (I)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 452111
- Employees
- 75
- Ownership type
- D
Citations
12 citations on file for this inspection.
1910.36 G02
- Issued
- Oct 4, 2012
- Abate by
- Oct 24, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.36(g)(2): Exit access(es) were not at least 28 inches (71.1 cm) wide at all points. Building 16 MCEX Outdoor Store: On or about 04SEP12, 1251 hours, shopping carts reduced the exit access from the back office to twelve inches wide.
Recent events (1)
- — Z (S) $0
1910.157 E02
- Issued
- Oct 4, 2012
- Abate by
- Oct 24, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(e)(2): Portable fire extinguishers were not visually inspected at least monthly: Bluilding 16 MCEX Candle Storage: On or about 04SEP12, 1222 hrs, a fire extinguisher was last visually inspected October, 2011.
Recent events (1)
- — Z (S) $0
1910.157 E03
- Issued
- Oct 4, 2012
- Abate by
- Oct 24, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(e)(3): Portable fire extinguishers were not subjected to an annual maintenance check: (a) Building 16 MCEX Small Appliance Storage: On or about 04SEP12, 1222 hrs, a fire extinguisher was not inspected annually, lacking any record of annual inspection. (b) Building 11 MCEX Shoe Department: On or about 04SEP12, 1333 hrs, a fire extinguisher was last inspected annually in September 2006. (c) Building 11 MCEX Elevator Foyer: On or about 04SEP12, 1336 hrs, a fire extinguisher was last inspected annually in January 1997.
Recent events (1)
- — Z (S) $0
1910.157 G01
- Issued
- Oct 4, 2012
- Abate by
- Oct 24, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(g)(1): An educational program was not provided for all employees to familiarize them with the general principles of fire extinguisher use and the hazards involved with incipient stage fire fighting: Building 11 and 16, On or about 04SEP12, 1300 hrs, the employer did not train its employees in the principles and hazards of the use of fire extinguishers in the incipient stage firefighting, additionally, the employer did not establish a written fire safety policy which requiring the immediate and total evacuation of employees upon the sounding of a fire alarm signal and which includes an emergency action plan and a fire prevention plan which meets the requirements of 29 CFR 1910.38 and 29 CFR 1910.39 respectively.
Recent events (1)
- — Z (S) $0
1910.303 B02
- Issued
- Oct 4, 2012
- Abate by
- Oct 24, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: (a) Bluilding16 MCEX Tickets/Tours: On or about 04SEP12, 1239 hrs, a surge suppressor was used to provide 115VAC electrical service to a refrigerator and microwave. (b) Building 16 MCEX Outdoor Store: On or about 04SEP12, 1246 hrs, a surge suppressor was used to provide 115VAC electrical service to a refrigerator. (c) Building 16 MCEX Outdoor Store: On or about 04SEP12, 1248 hrs, a surge suppressor was used to provide 115VAC electrical service to a microwave oven. (d) Building 11 MCEX Special Order Office: On or about 04SEP12, 1322 hrs, a surge suppressor was used to provide 115VAC electuildingcal service to a microwave oven and a refrigerator. (e) Building 11 MCEX Break Room: On or about 04SEP12, 1327 hrs, a surge suppressor was used to provide 115VAC electrical service to a microwave oven.
Recent events (1)
- — Z (S) $0
1910.303 B07 I
- Issued
- Oct 4, 2012
- Abate by
- Oct 24, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment: (a) Building 16 Marine Mart receiving: On or about 04SEP12, 1143 hrs, 115VAC live conductors were exposed to inadvertent employee contact where an opening on a receptacle outlet was left uncovered. (b) Building 16 MCEX Electronics: On or about 04SEP12, 1211 hrs, 115VAC live conductors were exposed to inadvertent employee contact where an opening on a receptacle outlet was left uncovered. (c) Bluilding16 MCEX Luggage Storage: On or about 04SEP12, 1228 hrs, 115VAC live conductors were exposed to inadvertent employee contact where an opening on a receptacle outlet was left uncovered.
Recent events (1)
- — Z (S) $0
1910.303 B07 IV
- Issued
- Oct 4, 2012
- Abate by
- Oct 24, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(7)(iv): There were damaged parts that could adversely affect safe operation or mechanical strength of the equipment, such as parts that were broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating: (a) Bluilding16 Marine Mart receiving: On or about 04SEP12, 1140 hrs, an opening on the front of a circuit breaker panel box was left uncovered where the locking hasp was removed, and the door was allowed to swing open. (b) Building 16 Marine Mart receiving: On or about 04SEP12, 1143 hrs, duct tape was used to cover the lower receptacle outlet which was broken on a receptacle outlet box mounted on the wall.
Recent events (1)
- — Z (S) $0
1910.303 F02
- Issued
- Oct 4, 2012
- Abate by
- Oct 24, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CDR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: Building 16 MCEX Candle Storage: On or about 04SEP12, 1217 hrs, the employer did not provide labels to indicate the purpose of the circuit breakers in a circuit breaker panel box.
Recent events (1)
- — Z (S) $0
1910.305 G01 III
- Issued
- Oct 4, 2012
- Abate by
- Oct 24, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iii): Flexible cords used as permitted in paragraphs (g)(1)(ii)(C), (g)(1)(ii)(G), or (g)(1)(ii)(I) of 29 CFR 1910.305 were not energized from an approved receptacle outlet: Building 16 Marine Mart receiving: On or about 04SEP12, 1155 hrs, a surge suppressor was plugged into another surge suppressor to provide 115VAC service to a water cooler.
Recent events (1)
- — Z (S) $0
1910.305 G01 IV A
- Issued
- Oct 4, 2012
- Abate by
- Oct 24, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and cables were used as a substitute for the fixed wiring of a structure: Building 16 Marine Mart receiving: On or about 04SEP12, 1143 hrs, an extension cord providing 115VAC service to a pedestal fan was in use for over six months.
Recent events (1)
- — Z (S) $0
1910.305 G01 IV C
- Issued
- Oct 4, 2012
- Abate by
- Oct 24, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(C): Flexible cords and cables were run through doorways, windows, or similar openings: Building 16 Marine Mart receiving: On or about 04SEP12, 1140 hrs, an flexible cord providing 115VAC service to a pedestal fan was run through a doorway where a vertical door was in use.
Recent events (1)
- — Z (S) $0
1910.305 G01 IV D
- Issued
- Oct 4, 2012
- Abate by
- Oct 24, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(D): Flexible cords and cables were attached to building surfaces: Building 16 Marine Mart receiving: On or about 04SEP12, 1143 hrs, an extension cord providing 115VAC service to a pedestal fan was wrapped around the support frame of machinery on the wall of the building.
Recent events (1)
- — Z (S) $0
More inspections at Marine Corps Community Services SAN Diego
View Marine Corps Community Services SAN Diego's full OSHA safety record →
More inspections in this industry (NAICS 452111)
More inspections in CA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 336161997.