OSHA Inspection: FEDERAL AVIATION ADMINISTRATION PAINE FIELD ATCT

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of FEDERAL AVIATION ADMINISTRATION PAINE FIELD ATCT in 3310 - 100TH STREET SW, EVERETT, WA 98204 (NAICS 488111). OSHA activity number 309094001.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Federal Aviation Administration Paine Field Atct — free Get an email when a new federal OSHA severe-injury report for Federal Aviation Administration Paine Field Atct is published. One employer, no account, unsubscribe in one click.
Site address
3310 - 100TH STREET SW
City
EVERETT
State
WA
ZIP
98204
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Health
Advance notice
No
Union status
Y
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
488111
SIC code (legacy)
9621
Employees
14
Ownership type
D

5 citations on file for this inspection.

1960.8 B

Serious Gravity 02 1 instance 2 exposed
Issued
Nov 4, 2008
Abate by
Dec 23, 2008
29 CFR 1960.8(b):  The head of each agency shall comply with the
Occupational Safety and
Health Administration standards applicable to the agency.
A.On or about June 17, 2008 at the Paine Field Air Traffic Control Center
facility, a
written Emergency Action Plan describing the emergency procedures and/or
assignments to
be followed was not available at the worksite for employee review.
Reference:
29 CFR 1910.38(b):  An Emergency Action Plan must be in writing, kept in
the
workplace, and available to employees for review.
Alternate Standard, G.4:  The written program shall be submitted upon
request to the
Assistant secretary, and shall be available at the worksite for
examination and copying by the
Assistant Secretary, and affected employees or authorized employee
representatives.

1960.8 B

Serious Gravity 02 1 instance 2 exposed
Issued
Nov 4, 2008
Abate by
Dec 23, 2008
29 CFR 1960.8(b):  The head of each agency shall comply with the
Occupational
Safety and
Health Administration standards applicable to the agency.
A.On or about June 17, 2008 at the Paine Field Air Traffic Control Center
facility, a
written Fire Prevention Plan describing the potential fire hazards, the
control maintenance
procedures and/or the responsible name/job assignments was not available
to employees for
review.
Reference:
29 CFR 1910.39(b):  A fire prevention plan must be in writing, kept in the
workplace, and be made available to employees for review.
Alternate Standard, G.4:  The written program shall be submitted upon
request to the
Assistant secretary, and shall be available at the worksite for
examination and copying by the
Assistant Secretary, and affected employees or authorized employee
representatives.

1960.8 A

Serious Gravity 02 1 instance 2 exposed
Issued
Nov 4, 2008
Abate by
Dec 23, 2008

1960.8 B

Other-than-serious Gravity 01 1 instance 2 exposed
Issued
Nov 4, 2008
Abate by
Nov 7, 2008
29 CFR 1960.8(b):  The head of each agency shall comply with the
Occupational Safety and
Health Administration standards applicable to the agency.
A.On or about June 17, 2008 in the 6th Floor Break Room/NATCO Office area,
a
relocatable power strip was used to provide power to a high amperage draw
electrical piece
of equipment (i.e. Fellows P45c shredder) contrary to the listing for the
power strip.
Complied with at time of inspection.
Reference:
29 CFR 1910.303(b)(2):  Listed or labeled electrical equipment was not
used or
installed in accordance with instructions included in the listing or
labeling:

1960.8 B

Other-than-serious Gravity 01 2 instances 2 exposed
Issued
Nov 4, 2008
Abate by
Nov 7, 2008
29 CFR 1960.8(b):  The head of each agency shall comply with the
Occupational Safety and
Health Administration standards applicable to the agency.
A.On or about June 17, 2008 in the 10th Floor Equipment Room, access to the
electrical circuit panel box identified as "EE" was blocked by a PS-52C
Fellows shredder
and a waste basket.  Complied with at time of inspection.
B.On or about June 17, 2008 in the 3rd Floor Pressurization Fan Room,
access to the
electrical circuit panel box identified as "SPF" was blocked by a
30-gallon garbage can.
Complied with at time of inspection.
Reference:
29 CFR 1910.304(e)(1)(iv): Overcurrent devices for circuits rated 600
volts, nominal,
or less were not readily accessible to each employee or authorized
building management
personnel: