Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: FIBER COMPOSITES, LLC

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of FIBER COMPOSITES, LLC in 181 RANDOM DRIVE, NEW LONDON, NC 28127 (NAICS 326199). OSHA activity number 309329233.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Fiber Composites, LLC — free Get an email when a new federal OSHA severe-injury report for Fiber Composites, LLC is published. One employer, no account, unsubscribe in one click.
Site address
181 RANDOM DRIVE
City
NEW LONDON
State
NC
ZIP
28127
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
N
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
326199
SIC code (legacy)
3089
Employees
250
Ownership type
A
Industry flags
Manufacturing health.

5 citations on file for this inspection.

95012901

Serious 1 instance 10 exposed
Issued
Jan 4, 2006
Abate by
Jan 12, 2006
Penalty
Initial $2,100 · Current $1,500 Reduced
North Carolina General Statute 95-129(1) of the Occupational Safety and
Health Act of North
Carolina:  The employer did not furnish employment and a place of
employment which were
free from recognized hazards that were causing or likely to cause death or
serious physical harm
to employees in that employees were exposed to potential hazards in the
workplace associated
with fire and explosion.
a)facility - extruder lines 11-15, employees were exposed to a build-up of
combustible dust up to 4-inches thick on horizonal surfaces including
piping,
ductwork, I-beams, and electrical equipment such as the top of lighting
fixtures,
electrical panels and electrical disconnects due to numerous leaks
thoughout the
process and poor housekeeping.
One feasible and acceptable method of abatement, among others, to correct
this hazard
is for the employer to follow the procedures in the NFPA document 654,
Standard for
the Prevention of Fire and Dust Explosions from Manufacturing, Processing,
and
Handling of Combustible Particulate Solids.
Recent events (2)
  • — I (S) $1500.00
  • — Z (S) $2100.00

1910.252 A01 III

Serious 1 instance 2 exposed
Issued
Jan 4, 2006
Abate by
Jan 12, 2006
Penalty
Initial $450 · Current $450

1910.252 A02 IV

Serious 1 instance 2 exposed
Issued
Jan 4, 2006
Abate by
Jan 12, 2006

1910.307 B

Serious 3 instances 10 exposed
Issued
Jan 4, 2006
Abate by
Jan 24, 2006
Penalty
Initial $2,100 · Current $1,500 Reduced
Recent events (2)
  • — I (S) $1500.00
  • — Z (S) $2100.00

1910.37 A03

Other-than-serious 1 instance 10 exposed
Issued
Jan 4, 2006
Abate by
Jan 12, 2006

View Fiber Composites, LLC's full OSHA safety record →