CHICAGO, IL ·
OSHA Inspection: BRIDGFORD FOOD PROCESSING CORPORATION
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of BRIDGFORD FOOD PROCESSING CORPORATION in 170 N. GREEN STREET, CHICAGO, IL 60607 (NAICS 311613). OSHA activity number 311371249.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- BRIDGFORD FOOD PROCESSING CORPORATION
- Site address
- 170 N. GREEN STREET
- City
- CHICAGO
- State
- IL
- ZIP
- 60607
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Union (Y)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 311613
- SIC code (legacy)
- 2013
- Employees
- 358
- Ownership type
- Private (A)
- Industry flags
- Manufacturing safety.
Citations
4 citations on file for this inspection.
5(a)(1)
- Issued
- Jun 12, 2008
- Abate by
- Sep 13, 2008
- Penalty
- Initial $1,875 · Current $1,000 Reduced
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment that were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees, in that employees were exposed to inhalation hazards associated with anhydrous ammonia. Machinery room - On or about January 15, 2008, employees were not adequately protected against the potential release of anhydrous ammonia in that: a. The space containing the refrigeration machinery was not separated from other occupancies (such as the boiler room) by tight construction with tight fitting self-closing doors. b. Remote control of the mechanical equipment in the refrigerating machinery room was not provided immediately outside the machinery room door solely for the purpose of shutting down the equipment in an emergency. c. Ventilation fans for the machinery room did not have a control switch located immediately outside the machinery room door. d. Pipes piercing the interior walls of the machinery room were not all tightly sealed to the walls through which they pass (such as the shower pipe). e. Durable signs were not provided designating all valves or switches for controlling the refrigerant flow, the ventilation, and the refrigeration compressors, and the kind of refrigerant contained in exposed piping outside the machinery room (such as the piping in the new smoke house area). f. A schematic drawing or panel giving directions for the operation of the refrigeration system was not provided at a location convenient for the operators of the equipment. g. Entrances to the refrigerating machinery room were not provided with legible permanent signs, securely attached and easily accessible, reading "Machinery Room--Autorized Personnel Only" and further communicating that entry is forbidden except by those personnel trained in emergency procedures when the ammonia alarm has been activated. h. Emergency shutdown procedures, including precautions to be observed in case of a breakdown or leak, were not posted outside the machinery room, immediately adjacent to each door. Among other methods, feasible and acceptable methods to control these hazards are to adhere to the safe design, installation and operation of anhydrous ammonia refrigeration systems as prescribed by ANSI/ASHRAE15-2004, "Safety Standard for Refrigearation Systems", specifically: a. Separate the space containing the machinery room from other occupancies by tightconstruction with tight-fitting doors. (Section 7) b. Provide a remote control of the mechanical equipment in the refrigerating machinery room immediately outside the machinery room door. (Section 8.12) c. Provide a control switch for the ventilation fans immediately outside the machinery room door. (Section 8.12) d. Seal all pipes piercing the interior walls of the machinery room tightly to the walls. (Section 8.12) e. Identify/label all controls and piping in anhydrous ammonia service. (Section 11.2) f. Provide a schematic drawing or panel giving directions for the operation of the refrigeration system in a location convenient for the operators. (Section 11.7) g. Provide legible permanent signs, securely attached and easily accessible, reading "Machinery Room--Authorized Personnel Only" and communicating that entry is forbidden except by personnel trained in emergency procedures when the ammonia alarm has been activated. (Section 11.7) h. Post emergency procedures outside the machinery room immediately adjacent to each door. (Section 11.7)
Recent events (2)
- · I (S) $1000.00
- · Z (S) $1875.00
1910.305 B02
- Issued
- Jun 12, 2008
- Abate by
- Jun 17, 2008
- Penalty
- Initial $1,875 · Current $1,000 Reduced
Recent events (2)
- · I (S) $1000.00
- · Z (S) $1875.00
1910.1200 F05 I
- Issued
- Jun 12, 2008
- Abate by
- Jul 15, 2008
1910.1200 F05 II
- Issued
- Jun 12, 2008
- Abate by
- Jul 15, 2008
More inspections at Bridgford Food Processing Corporation
View Bridgford Food Processing Corporation's full OSHA safety record →
More inspections in this industry (NAICS 311613)
More inspections in IL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 311371249.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.