PHILADELPHIA, PA —
OSHA Inspection: SUNOCO PHILADELPHIA REFINERY
Complaint inspection · Health discipline
At a glance
On , OSHA opened a complaint health inspection of SUNOCO PHILADELPHIA REFINERY in 6958 TORRESDALE AVENUE, SUITE 300, PHILADELPHIA, PA 19135 (NAICS 324110). OSHA activity number 312487838.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- SUNOCO PHILADELPHIA REFINERY
- Site address
- 6958 TORRESDALE AVENUE, SUITE 300
- City
- PHILADELPHIA
- State
- PA
- ZIP
- 19135
- Mailing
- 3144 PASSYUNK AVENUE, PHILADELPHIA, PA 19145
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- Y
When did the case open and close?
- Opened
- Closing conference
- Last modified
- Data loaded
Establishment context
- NAICS code
- 324110
- SIC code (legacy)
- 2911
- Employees
- 900
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.119 F01 IF
- Issued
- May 14, 2009
- Abate by
- Jun 8, 2009
- Penalty
- Initial $2,125 · Current $2,125
General-duty citation text
29 CFR 1910.119(f)(1)(i)(F) or, in the alternative, 1910.147(c)(4)(ii)(B): The employer's written operating procedures covering the steps for each operating phase did not address normal shutdown: a. Sunoco Philadelphia Refinery, Light Hydrocarbon Separation Unit # 431 - Two employees sustained first and second degree burns that resulted from a flash fire. The accident occurred when a large flammable vapor cloud of either butane or isobutane was released from a 3 inch drain valve. The documented energy control procedure, "Philadelphia Refinery Operating Procedure HFAU-433 Complex 431 LHSU Maint Prep DIB (V-211), Reboiler (E-214F) and Reflux Drum (V-212) for Maint Procedure Number VIII-E-1," did not clearly and specifically outline all of the steps to be followed by authorized employees to accomplish the lockout/tagout of the E-213 (A through F) Deisobutanizer Overhead Condensers and Reflux Pumps (P-214 and P-214A). It omitted: the process side product inlet and outlet valves for the E-213 (A through F) Deisobutanizer Overhead Condensers; drive steam, exhaust steam, and suction/discharge valves for the P-214 pump; and the drive steam and suction/discharge valves for the P- 214A pump. On or About 02/03/09. ABATEMENT NOTE: ABATEMENT DOCUMENTATION IS REQUIRED.TION
1910.147 D03
- Issued
- May 14, 2009
- Abate by
- May 27, 2009
General-duty citation text
29 CFR 1910.147(d)(3): All energy isolating devices that were needed to control the energy to the machine or equipment were not physically located and operated in such a manner as to isolate the machine or equipment from the energy source(s): a. Sunoco Philadelphia Refinery, Light Hydrocarbon Separation Unit # 431, Deisobutanizer - During the evening of February 3, 2009, at approximately 7:00 PM, two employees sustained first and second degree burns that resulted from a flash fire. The accident occurred when a large flammable vapor cloud of either butane or isobutane was released from an opened 3 inch drain valve. The employer failed to isolate the process sides of the Deisobutanizer Reflux Pumps,P-214 and P-214A. On or About 02/03/09. ABATEMENT NOTE: ABATEMENT DOCUMENTATION IS REQUIRED.TION
1910.147 D05 I
- Issued
- May 14, 2009
- Abate by
- May 27, 2009
General-duty citation text
29 CFR 1910.147(d)(5)(i): Following the application of lockout or tagout device(s) to energy isolating device(s), all potentially hazardous stored or residual energy was not relieved, disconnected, restrained or otherwise rendered safe: a. Sunoco Philadelphia Refinery, Light Hydrocarbon Separation Unit # 431 - During the evening of February 3, 2009, at approximately 7:00 PM, two employees sustained first and second degree burns that resulted from a flash fire. The accident occurred when a large flammable vapor cloud of either butane or isobutane was released from the 3 inch drain valve. The Deisobutanizer Reflux Drum (V-212) had not been completely purged of hydrocarbons. On or About 02/03/09. ABATEMENT NOTE: ABATEMENT DOCUMENTATION IS REQUIRED.TION
More inspections at Sunoco Philadelphia Refinery
View Sunoco Philadelphia Refinery's full OSHA safety record →
More inspections in this industry (NAICS 324110)
More inspections in PA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 312487838.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.