SIOUX FALLS, SD —
OSHA Inspection: FAA SIOUX FALLS AIR TRAFFIC CONTROL TOWER
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of FAA SIOUX FALLS AIR TRAFFIC CONTROL TOWER in 2601 JAYCEE LANE, SIOUX FALLS, SD 57104 (NAICS 488111). OSHA activity number 312518079.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- FAA SIOUX FALLS AIR TRAFFIC CONTROL TOWER
- Site address
- 2601 JAYCEE LANE
- City
- SIOUX FALLS
- State
- SD
- ZIP
- 57104
- Mailing
- 2601 JAYCEE LANE, SIOUX FALLS, SD 57104
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Y
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 488111
- SIC code (legacy)
- 9621
- Employees
- 30
- Ownership type
- D
Citations
7 citations on file for this inspection.
1960.8 A
- Issued
- Dec 11, 2008
- Abate by
- Jan 30, 2009
Recent events (2)
- — A (S)
- — Z (S)
1960.8 A
- Issued
- Dec 11, 2008
- Abate by
- Jan 30, 2009
Recent events (2)
- — A (S)
- — Z (S)
1960.8 B
- Issued
- Dec 11, 2008
- Abate by
- Jan 30, 2009
General-duty citation text
29 CFR 1960.8(b): The agency shall comply with the Occupational Safety and Health Administration standards applicable to the agency: (a) Accumulations of flammable and combustible waste materials were not controlled so that they do not contribute to a fire emergency. The employees were exposed to the hazard of fire. Excess accumulations of cardboard boxes were noted on the fourth floor technical operations equipment room of the air traffic control tower. Reference: 1) 29 CFR 1910.176(c): Storage areas shall be kept free from accumulation of materials that constitute hazards from tripping, fire, explosion, or pest harborage. 2) The Alternate Standard for Fire Safety in Airport Traffic Control Towers, paragraph 1.3, states "The FAA shall control accumulations of flammable and combustible waste materials and residues so that they do not contribute to a fire emergency. The housekeeping procedures shall be included in the written fire protection plan. Abatement Note: Abatement certification is required for this item (see enclosed "Sample Abatement Certification Letter").tion
Recent events (2)
- — A (S)
- — Z (S)
1960.8 B
- Issued
- Dec 11, 2008
- Abate by
- Jan 30, 2009
General-duty citation text
29 CFR 1960.8(b): The agency shall comply with the Occupational Safety and Health Administration standards applicable to the agency: (a) The fire extinguisher on the second floor of the air traffic control tower had not had an annual maintenance check since July of 2003. (b) The fire extinguisher on the first floor Environmental Room of the air traffic control tower had not had an annual maintenance check since May of 2001. (c) The fire extinguisher in the cab of the air traffic control tower did not have a tag showing the last annual maintenance check. (d) The Dry Chemical ABC portable fire extinguishers in the air traffic control tower had not been hydrostatically tested at the intervals established in Table L-1 of 29 CFR 1910.157. Reference: 1) 29 CFR 1910.157(e)(3): Stored pressure extinguishers do not require an internal examination. The employer shall record the annual maintenance date and retain this record for one year after the last entry or the life of the shell, whichever is less. The record shall be available to the Assistant Secretary upon request. 2) 29 CFR 1910.157(f)(2): The employer shall assure that portable extinguishers are hydrostatically tested at the intervals listed in Table L-1 of this section. Abatement Note: Abatement certification is required for this item (see enclosed "Sample Abatement Certification Letter").tion
Recent events (2)
- — A (S)
- — Z (S)
1960.8 B
- Issued
- Dec 11, 2008
- Abate by
- Jan 30, 2009
General-duty citation text
29 CFR 1960.8(b): The agency shall comply with the Occupational Safety and Health Administration standards applicable to the agency: (a) Employees were exposed to the hazards of fire. Throughout the air traffic control tower, doors other than the only exit door were not marked as being "Not an Exit". Reference: 29 CFR 1910.37(b)(5): Each doorway or passage along an exit access that could be mistaken for an exit must be marked "Not an Exit" or similar designation, or be identified by a sign indicating its actual use (e.g., closet). Abatement Note: Abatement certification is required for this item (see enclosed "Sample Abatement Certification Letter").tion
Recent events (2)
- — A (S)
- — Z (S)
1960.8 B
- Issued
- Dec 11, 2008
- Abate by
- Jan 30, 2009
General-duty citation text
29 CFR 1960.8(b): The agency shall comply with the Occupational Safety and Health Administration standards applicable to the agency: (a) Air Traffic Control Tower employees and Technical Operations employees as well as a sub-contracted employee had not had annual training on how to use the fire extinguisher. At a minimum, the training must cover the fire hazards of the materials and processes to which employees are exposed. Reference: 29 CFR 1910.157(g)(2): The employer shall provide the education required in paragraph (g)(1) of this section upon initial assignment and at least annually thereafter. Abatement Note: Abatement certification is required for this item (see enclosed "Sample Abatement Certification Letter").tion
Recent events (2)
- — A (S)
- — Z (S)
1960.8 B
- Issued
- Dec 11, 2008
- Abate by
- Jan 30, 2009
General-duty citation text
29 CFR 1960.8(b): The agency shall comply with the Occupational Safety and Health Administration standards applicable to the agency: (a) Hazard of employees suffering electrical shock when accessing the electrical cabinet. The electrical cabinet in the technical operations room on the fourth floor was blocked with storage. (b) The electrical cabinet in the first floor environmental center was blocked with large boxes containing florescent fixtures. Reference: 29 CFR 1910.303(g)(1): Sufficient access and working space shall be provided and maintained about all electrical equipment to permit ready and safe operation and maintenance of such equipment. Abatement Note: Abatement certification is required for this item (see enclosed "Sample Abatement Certification Letter").tion