OSHA Inspection: FAA SIOUX FALLS AIR TRAFFIC CONTROL TOWER

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of FAA SIOUX FALLS AIR TRAFFIC CONTROL TOWER in 2601 JAYCEE LANE, SIOUX FALLS, SD 57104 (NAICS 488111). OSHA activity number 312518079.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch FAA Sioux Falls AIR Traffic Control Tower — free Get an email when a new federal OSHA severe-injury report for FAA Sioux Falls AIR Traffic Control Tower is published. One employer, no account, unsubscribe in one click.
Site address
2601 JAYCEE LANE
City
SIOUX FALLS
State
SD
ZIP
57104
Mailing
2601 JAYCEE LANE, SIOUX FALLS, SD 57104
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
Y
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
488111
SIC code (legacy)
9621
Employees
30
Ownership type
D

7 citations on file for this inspection.

1960.8 A

Serious Gravity 02 1 instance 1 exposed
Issued
Dec 11, 2008
Abate by
Jan 30, 2009
Recent events (2)
  • — A (S)
  • — Z (S)

1960.8 A

Serious Gravity 02 1 instance 2 exposed
Issued
Dec 11, 2008
Abate by
Jan 30, 2009
Recent events (2)
  • — A (S)
  • — Z (S)

1960.8 B

Serious Gravity 02 1 instance 2 exposed
Issued
Dec 11, 2008
Abate by
Jan 30, 2009
29 CFR 1960.8(b):  The agency shall comply with the Occupational Safety
and Health
Administration standards applicable to the agency:
(a)  Accumulations of flammable and combustible waste materials were not
controlled
so that they do not contribute to a fire emergency.  The employees were
exposed to the
hazard of fire.  Excess accumulations of cardboard boxes were noted on the
fourth floor
technical operations equipment room of the air traffic control tower.
Reference:
1) 29 CFR 1910.176(c): Storage areas shall be kept free from accumulation
of materials
that constitute hazards from tripping, fire, explosion, or pest harborage.
2) The Alternate Standard for Fire Safety in Airport Traffic Control
Towers, paragraph
1.3, states "The FAA shall control accumulations of flammable and
combustible waste
materials and residues so that they do not contribute to a fire emergency.
The
housekeeping procedures shall be included in the written fire protection
plan.
Abatement Note:  Abatement certification is required for this item (see
enclosed "Sample
Abatement Certification Letter").tion
Recent events (2)
  • — A (S)
  • — Z (S)

1960.8 B

Serious Gravity 02 1 instance 2 exposed
Issued
Dec 11, 2008
Abate by
Jan 30, 2009
29 CFR 1960.8(b):  The agency shall comply with the Occupational Safety
and Health
Administration standards applicable to the agency:
(a) The fire extinguisher on the second floor of the air traffic control
tower had not had
an annual maintenance check since July of 2003.
(b) The fire extinguisher on the first floor Environmental Room of the air
traffic control
tower had not had an annual maintenance check since May of 2001.
(c) The fire extinguisher in the cab of the air traffic control tower did
not have a tag
showing the last annual maintenance check.
(d) The Dry Chemical ABC portable fire extinguishers in the air traffic
control
tower had
not been hydrostatically tested at the intervals established in Table L-1
of 29 CFR
1910.157.
Reference:
1) 29 CFR 1910.157(e)(3): Stored pressure extinguishers do not require an
internal
examination.  The employer shall record the annual maintenance date and
retain this
record for one year after the last entry or the life of the shell,
whichever is less.  The
record shall be available to the Assistant Secretary upon request.
2) 29 CFR 1910.157(f)(2): The employer shall assure that portable
extinguishers are
hydrostatically tested at the intervals listed in Table L-1 of this
section.
Abatement Note:  Abatement certification is required for this item (see
enclosed "Sample
Abatement Certification Letter").tion
Recent events (2)
  • — A (S)
  • — Z (S)

1960.8 B

Serious Gravity 02 1 instance 2 exposed
Issued
Dec 11, 2008
Abate by
Jan 30, 2009
29 CFR 1960.8(b):  The agency shall comply with the Occupational Safety
and
Health
Administration standards applicable to the agency:
(a) Employees were exposed to the hazards of fire.  Throughout the air
traffic control
tower, doors other than the only exit door were not marked as being "Not
an Exit".
Reference: 29 CFR 1910.37(b)(5): Each doorway or passage along an exit
access that could be
mistaken for an exit must be marked "Not an Exit" or similar designation,
or be identified by
a sign indicating its actual use (e.g., closet).
Abatement Note:  Abatement certification is required for this item (see
enclosed "Sample
Abatement Certification Letter").tion
Recent events (2)
  • — A (S)
  • — Z (S)

1960.8 B

Serious Gravity 02 1 instance 2 exposed
Issued
Dec 11, 2008
Abate by
Jan 30, 2009
29 CFR 1960.8(b):  The agency shall comply with the Occupational Safety
and Health
Administration standards applicable to the agency:
(a) Air Traffic Control Tower employees and Technical Operations employees
as well
as a sub-contracted employee had not had annual training on how to use the
fire
extinguisher.  At a minimum, the training must cover the fire hazards of
the materials
and processes to which employees are exposed.
Reference: 29 CFR 1910.157(g)(2): The employer shall provide the education
required in
paragraph (g)(1) of this section upon initial assignment and at least
annually thereafter.
Abatement Note:  Abatement certification is required for this item (see
enclosed "Sample
Abatement Certification Letter").tion
Recent events (2)
  • — A (S)
  • — Z (S)

1960.8 B

Serious Gravity 02 1 instance 2 exposed
Issued
Dec 11, 2008
Abate by
Jan 30, 2009
29 CFR 1960.8(b):  The agency shall comply with the Occupational Safety
and Health
Administration standards applicable to the agency:
(a) Hazard of employees suffering electrical shock when accessing the
electrical cabinet.
The electrical cabinet in the technical operations room on the fourth
floor was blocked
with storage.
(b) The electrical cabinet in the first floor environmental center was
blocked
with large
boxes containing florescent fixtures.
Reference: 29 CFR 1910.303(g)(1): Sufficient access and working space
shall be provided and
maintained about all electrical equipment to permit ready and safe
operation and maintenance
of such equipment.
Abatement Note:  Abatement certification is required for this item (see
enclosed "Sample
Abatement Certification Letter").tion