OSHA Inspection: GARCES CONTRACTORS, L.L.C.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of GARCES CONTRACTORS, L.L.C. in 1832 W. 21ST ST., CHICAGO, IL 60608 (NAICS 237110). OSHA activity number 330771924.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Garces Contractors, L.L.C. — free Get an email when a new federal OSHA severe-injury report for Garces Contractors, L.L.C. is published. One employer, no account, unsubscribe in one click.
Site address
1832 W. 21ST ST.
City
CHICAGO
State
IL
ZIP
60608
Mailing
5423 W. DIVISION ST., CHICAGO, IL 60651
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
237110
Employees
9
Ownership type
A

5 citations on file for this inspection.

1926.651 C02

Serious Gravity 5 1 instance 1 exposed
Issued
Aug 19, 2011
Abate by
Aug 22, 2011
Penalty
Initial $3,000 · Current $1,500 Reduced
29 CFR 1926.651(c)(2): Means of egress from trench excavations. A stairway, ladder, ramp or other safe means of egress shall be located in trench excavations that are 4 feet (1.22 m) or more in depth so as to require no more than 25 feet (7.62 m) of lateral travel for employees:    a. On or about June 17, 2011, at the above addressed jobsite, an employee installing a water line in a trench, eight (8) feet four (4) inches deep, was not provided a safe means of egress.
Recent events (2)
  • — I (S) $1500
  • — Z (S) $3000

1926.651 I03

Serious Gravity 10 1 instance 1 exposed
Issued
Aug 19, 2011
Abate by
Aug 22, 2011
Penalty
Initial $4,200 · Current $2,100 Reduced
29 CFR 1926.651(i)(3): Sidewalks, pavements and appurtenant structure shall not be undermined unless a support system or another method of protection is provided to protect employees from the possible collapse of such structures:    a.  On or about June 17, 2011, at the above addressed jobsite, an employee was installing a water line in a trench measured at eight (8) feet four (4) inches in depth.  The trench undermined the street.  The street was not supported nor provided a means of protection from the possible collapse of the street, thereby exposing the employee to cave in hazards.
Recent events (2)
  • — I (S) $2100
  • — Z (S) $4200

1926.652 A01

Serious Gravity 10 2 instances 2 exposed
Issued
Aug 19, 2011
Abate by
Aug 22, 2011
Penalty
Initial $0 · Current $0
29 CFR 1926.652(a)(1): Each employee in an excavation shall be protected from cave-ins by an adequate protective system designed in accordance with paragraph (b) or (c) of this section:    a.  On or about June 17, 2011, at the above addressed jobsite, an employee was installing a water line in a trench measured at eight (8) feet four (4) inches in depth.  The trench was not provided with adequate cave in protection, threby exposing the employee to cave in hazards.    b.  On or about June 17, 2011, at the above addressed jobsite, an employee was installing a water line in a trench measured at nine (9) feet in depth.  The trench was not provided with adequate cave in protection, thereby exposing the employee to cave in hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.652 G01 II

Serious Gravity 10 1 instance 1 exposed
Issued
Aug 19, 2011
Abate by
Aug 22, 2011
Penalty
Initial $4,200 · Current $2,100 Reduced
29 CFR 1926.652(g)(1)(ii): Shields shall be installed in a manner to restrict lateral or other hazardous movement of the shield in the event of the application of sudden lateral loads:    a.  On or about June 17, 2011, at the above addressed jobsite, an employee was installing a water line in a trench measured at eight (8) feet four (4) inches in depth.  The trench shield was not restricted against lateral movement, thereby exposing the employee to cave in hazards.
Recent events (2)
  • — I (S) $2100
  • — Z (S) $4200

1926.652 G02

Serious Gravity 10 1 instance 1 exposed
Issued
Aug 19, 2011
Abate by
Aug 22, 2011
Penalty
Initial $0 · Current $0
29 CFR 1926.652(g)(2):  Additional requirement for shield systems used in trench excavations. Excavations of earth material to a level not greater than 2 feet (.61 m) below the bottom of a shield shall be permitted, but only if the shield is designed to resist the forces calculated for the full depth of the trench, and there are no indications while the trench is open of a possible loss of soil from behind or below the bottom of the shield:    a. On or about June 17, 2011, at the above addressed jobsite, an employee was installing a water line in a trench measured at eight (8) feet four (4) inches in depth and four (4) feet of soil was below the trench sheild, thereby exposing the employee to cave in hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View Garces Contractors, L.L.C.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 330771924.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.