OSHA Inspection: OMNOVA SOLUTIONS INC

Referral inspection · Health discipline

On , OSHA opened a referral health inspection of OMNOVA SOLUTIONS INC in 1380 TECH WAY DRIVE, AKRON, OH 44306 (NAICS 325212). OSHA activity number 331074500.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Omnova Solutions INC for free Get an email when a new federal OSHA severe-injury report for Omnova Solutions INC is published. One employer, no account, unsubscribe in one click.
Site address
1380 TECH WAY DRIVE
City
AKRON
State
OH
ZIP
44306
Mailing
1380 TECH WAY DRIVE, AKRON, OH 44306
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
Union (A)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
325212
Employees
60
Ownership type
Private (A)

6 citations on file for this inspection.

1910.119 E01

Serious Gravity 5 4 instances 1 exposed
Issued
Mar 27, 2012
Abate by
Apr 26, 2012
Penalty
Initial $4,250 · Current $2,975 Reduced
29 CFR 1910.119(e)(1):     The process hazard analysis was not appropriate to the complexity of the process and did not identify, evaluate, and address the control of the hazards involved in the process:    a)  The hazards from toxic or flammable chemicals, which could collect in the floor trench, in the event of a spill, and be directed to the sewer pit, were not addressed in the process hazard analysis.     b)  The process hazard analysis did not address the possibility of leaks from the ammonia cooling coils into the reactors or the possibility of leaks from the reactors into the ammonia cooling coils.    c)  The possibility of leaks from the ammonia system into the machine room, resulting in fires or explosions, was not addressed in the process hazard analysis.    c)  The process hazard analysis did not address the location of the control room adjacent to the reactor building where an incident could impact the ability to control the process.
Recent events (2)
  • · I (S) $2975
  • · Z (S) $4250

1910.119 E05

Deleted Serious Gravity 5 1 instance 1 exposed
Issued
Mar 27, 2012
Abate by
Apr 26, 2012
Penalty
Initial $4,250 · Current $0 Reduced
29 CFR 1910.119(e)(5):     The employer did not establish a system to promptly address the PHA's team findings and recommendations:    A facility siting PHA done for the reactor control room location states that the control room is under positive pressure to reduce hazards from the release of flammable vapors; this room is not under positive pressure and no recommendations were made to address this deficiency.
Recent events (2)
  • · I (S) $0
  • · Z (S) $4250

1910.119 F01

Other-than-serious 1 instance 1 exposed
Issued
Mar 27, 2012
Abate by
Apr 11, 2012
Penalty
Initial $4,250 · Current $0 Reduced
29 CFR 1910.119(f)(1):     The employer did not develop and implement written operating procedures that provided clear instructions for safety conducting activities in each covered process consistent with the process safety information and which addressed the elements listed in 29 CFR 1910.119(f)(1)(i) through (f)(1)(v):    No written procedures were developed for shift changes to assure that reactor operators, maintenance staff and other employees were advised on the current operating conditions in the process.
Recent events (2)
  • · I (O) $0
  • · Z (S) $4250

1910.119 J04 III

Serious Gravity 10 4 instances 1 exposed
Issued
Mar 27, 2012
Abate by
Apr 26, 2012
Penalty
Initial $7,000 · Current $4,900 Reduced
29 CFR 1910.119(j)(4)(iii):     The frequency of inspections and tests of process equipment to maintain its mechanical integrity, was not consistent with applicable manufacturers' recommendations and good engineering practices, or more frequently determined to be necessary by prior operating experience:    Inspection scheduling for some portions of the ammonia system did not meet the intervals delineated in the applicable RAGAGEP, International Institute of Ammonia Refrigeration (IIAR) Guidelines for: Start-up, Inspection and Maintenance of Ammonia Mechanical Refrigerating Systems, Bulletin No.110.      a)  No annual inspections were conducted of ammonia heat exchangers located adjacent to the machinery building.    b)  No independent 5 year inspections were conducted of the ammonia shell and tube heat exchangers located adjacent to the machinery building.    c)   No inspections were conducted every six months for the pressure relief valves, PRV-8051 and PRV-8050, on the ammonia heat exchangers located adjacent to the machinery building.    d)  No annual pipe inspections were done on the AML-101-2 pipe located outside the machinery building.
Recent events (2)
  • · I (S) $4900
  • · Z (S) $7000

1910.146 F

Serious Gravity 5 1 instance 1 exposed
Issued
Mar 27, 2012
Abate by
Apr 11, 2012
Penalty
Initial $4,250 · Current $4,250
29 CFR 1910.146(f):     The entry permit that documents compliance with this  section and authorizes entry to a permit space include the elements listed in 29 CFR 1910.146(f) (1) through (15):    The entry permit for an entry made to a reactor on 10/4/2011 did not have the purpose of the entry, the attendant, the hazards of the space, acceptable entry conditions,  results of air sampling for chemicals, rescue and emergency services, communication procedures and equipment required for the entry.
Recent events (2)
  • · I (S) $4250
  • · Z (S) $4250

1910.212 A05

Serious Gravity 5 1 instance 1 exposed
Issued
Mar 27, 2012
Abate by
Apr 1, 2012
Penalty
Initial $3,400 · Current $2,380 Reduced
29 CFR 1910.212(a)(5):     Fan blade guards, where the periphery of the blades was less than seven feet above the floor or working level, had openings larger than one half inch:    The low level exhaust fan installed in building 1211 had no guard.
Recent events (2)
  • · I (S) $2380
  • · Z (S) $3400

View Omnova Solutions INC's full OSHA safety record →