KODIAK, AK —
OSHA Inspection: KODIAK SUPPORT SERVICES, JV
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of KODIAK SUPPORT SERVICES, JV in BOSS PROJECT FACILITIES, KODIAK, AK 99615 (NAICS 561210). OSHA activity number 331087262.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- KODIAK SUPPORT SERVICES, JV
- Site address
- BOSS PROJECT FACILITIES
- City
- KODIAK
- State
- AK
- ZIP
- 99615
- Mailing
- P.O. BOX 1547, KODIAK, AK 99615
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 561210
- Employees
- 120
- Ownership type
- A
Citations
9 citations on file for this inspection.
1910.132 C
- Issued
- Dec 9, 2011
- Penalty
- Initial $3,825 · Current $2,678 Reduced
General-duty citation text
29 CFR 1910.132(c): Design. All personal protective equipment shall be of safe design and construction for the work to be performed. Steam Plant: On or about November 1, 2011 and times prior thereto, employees were using a 1/2 screw pin shackle as part of their fall arrest system. This exposed employees to fall hazards from using a shackle that was not designed or tested as part of a fall arrest system.
Recent events (2)
- — I (S) $2677.5
- — Z (S) $3825
1910.212 A01
- Issued
- Dec 9, 2011
- Abate by
- Jan 10, 2012
- Penalty
- Initial $3,060 · Current $2,142 Reduced
General-duty citation text
29 CFR 1910.212(a)(1): Types of guarding. One or more methods of machine guarding shall be provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks. Examples of guarding methods are-barrier guards, two-hand tripping devices, electronic safety devices, etc Building 19: On or about November 1, 2011 the Oster Williams pipe threading machine had no guards installed. This exposed employees to caught-in/struckby hazards from being at the point of operation or walking by the machine.
Recent events (2)
- — I (S) $2142
- — Z (S) $3060
1910.213 A12
- Issued
- Dec 9, 2011
- Abate by
- Jan 10, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.213(a)(12): For all circular saws where conditions are such that there is a possibility of contact with the portion of the saw either beneath or behind the table, that portion of the saw shall be covered with an exhaust hood, or, if no exhaust system is required, with a guard that shall be so arranged as to prevent accidental contact with the saw. Shipping and Receiving: On or about October 31, 2011 and times prior thereto the Delta table saw S/N 87E69415 had an inoperative guard. This exposed employees to amputation hazards to the hands from accidentall contact with the blade during cutting operations.
Recent events (1)
- — Z (S) $0
1910.304 G05
- Issued
- Dec 9, 2011
- Abate by
- Dec 23, 2011
- Penalty
- Initial $2,295 · Current $1,607 Reduced
General-duty citation text
29 CFR 1910.304(g)(5): Grounding path. The path to ground from circuits, equipment, and enclosures shall be permanent, continuous, and effective. Water Treatment Plant: On or about November 1, 2011 and times prior thereto, a 120 volt receptacle with a heater plugged into it had faulty ground. This exposed employees to shock hazards from using equipment and receptacle that did not having a ground
Recent events (2)
- — I (S) $1606.5
- — Z (S) $2295
1910.305 J07
- Issued
- Dec 9, 2011
- Abate by
- Jan 10, 2012
- Penalty
- Initial $3,060 · Current $2,142 Reduced
General-duty citation text
29 CFR 1910.305(j)(7): Storage Batteries. Provisions shall be made for sufficient diffusion and ventilation of gases from storage batteries to prevent the accumulation of explosive mixtures: Building N-1 (Battery Charging Area): The ventilation system in the battery charging / storage area was not functioning; exposing employees to fire and explosion hazards in the event of hydrogen build-up in the room.
Recent events (2)
- — I (S) $2142
- — Z (S) $3060
1926.405 B02
- Issued
- Dec 9, 2011
- Penalty
- Initial $2,295 · Current $0 Reduced
General-duty citation text
29 CFR 1926.405(b)(2): Covers and canopies. All pull boxes, junction boxes, and fittings shall be provided with covers. If metal covers are used, they shall be grounded. In energized installations each outlet box shall have a cover, faceplate, or fixture canopy. Covers of outlet boxes having holes through which flexible cord pendants pass shall be provided with bushings designed for the purpose or shall have smooth,well-rounded surfaces on which the cords may bear. Water Treatment Plant (Filter Area): On or about 11/1/2011, and times prior thereto, employees were exposed to live electrical wiring hanging from 2 duplex receptacles in the filter area of the plant.
Recent events (2)
- — I (S) $0
- — Z (S) $2295
1910.157 C04
- Issued
- Dec 9, 2011
- Abate by
- Jan 10, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(c)(4): The employer shall assure that portable fire extinguishers are maintained in a fully charged and operable condition and kept in their designated places at all times except during use. (a) Warehouse Area 1st floor: On or about 10/31/2011, and times prior thereto, a portable fire extinguisher was mounted in the work area, not marked or identified as being out of service in a discharged condition. (b) Building N-1: On or about 10/31/2011, and times prior thereto, a portable fire extinguisher was laying in the shop area on the ground, not marked or identified as being out of service in a discharged condition. (c) Building N-1A: On or about 10/31/2011, and times prior thereto, 3 portable fire extinguishers were laying in the welding shop area on the ground, not marked or identified as being out of service; 1 of which was in a discharged condition. (d) Building 19: On or about 10/31/2011, and times prior thereto, a portable fire extinguisher was not mounted in the work area.
Recent events (1)
- — Z (O) $0
1910.179 H04
- Issued
- Dec 9, 2011
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.179(h)(4): Hooks. Hooks shall meet the manufacturer's recommendations and shall not be overloaded. Building 19: On or about November 1, 2011 and times prior thereto, the DZ chain hoist did not have a latch installed on the upper hook. This exposed employees to possible struck-by hazards if the load were to disengage from the hook since there was no latch to stop it.
Recent events (1)
- — Z (O) $0
1910.242 B
- Issued
- Dec 9, 2011
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.242(b): Compressed air used for cleaning. Compressed air shall not be used for cleaning purposes except where reduced to less than 30 p.s.i. and then only with effective chip guarding and personal protective equipment. Auto repair shop: On or about October 31, 2011 and times prior thereto, employees were using an air nozzle that was operating at 110 psi. This exposed employees to laceration or air embolism hazards if it were to contact their body.
Recent events (1)
- — Z (O) $0
More inspections at Kodiak Support Services, JV
View Kodiak Support Services, JV's full OSHA safety record →
More inspections in this industry (NAICS 561210)
More inspections in AK
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 331087262.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.