Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,195,903Inspections Most recent open 2026-08-18 Last loaded 2026-08-21

OSHA Inspection: DEPARTMENT OF JUSTICE, BUREAU OF PRISONS

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of DEPARTMENT OF JUSTICE, BUREAU OF PRISONS in FEDERAL CORRECTIONAL INSTITUTE 1 13777 AIR EXPRESSWAY BOULEVARD, VICTORVILLE, CA 92394 (NAICS 922140). OSHA activity number 331900563.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Department of Justice, Bureau of Prisons for free Get an email when a new federal OSHA severe-injury report for Department of Justice, Bureau of Prisons is published. One employer, no account, unsubscribe in one click.
Site address
FEDERAL CORRECTIONAL INSTITUTE 1 13777 AIR EXPRESSWAY BOULEVARD
City
VICTORVILLE
State
CA
ZIP
92394
Mailing
P.O. BOX 5400, ADELANTO, CA 92301
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
Yes
Union status
Union (A)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
922140
Employees
930
Ownership type
Federal government (D)

10 citations on file for this inspection.

1910.303 B02

Serious Gravity 1 2 instances 8 exposed
Issued
May 24, 2012
Abate by
May 30, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2):  Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling.      (a) At the Federal Correctional Institute 1, Electrical Shop, two relocatable power taps were daisy chained in series.      (b) At the HVAC Shop, three relocatable power taps were daisy chained in series.
Recent events (1)
  • · Z (S) $0

1910.253 E06 II

Serious Gravity 5 1 instance 6 exposed
Issued
May 24, 2012
Abate by
Jun 5, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.253(e)(6)(ii): When regulators or parts of regulators, including gages, needed repair, the work was not performed by skilled mechanics who had been properly instructed:      (a) At the Federal Crrectional Institute 1, Unicor area machine shop, the argon gas regulator gauge cover was broken.
Recent events (1)
  • · Z (S) $0

1910.303 B07 I

Serious Gravity 5 2 instances 8 exposed
Issued
May 24, 2012
Abate by
May 30, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(7)(i):   Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment.      (a)  At the Federal Correctional Institute 1, Unicor Machine Shop, 2 Bay 8, the box for the light switch/outlet was missing knockouts.
Recent events (1)
  • · Z (S) $0

1910.303 F02

Serious Gravity 5 1 instance 6 exposed
Issued
May 24, 2012
Abate by
Jun 5, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.303(f)(2):  Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident.      (a) At the Federal Correctional Institute 1, Wood Shop, the electrical power panel was not marked and several circuit breakers were not designated to which equipment or circuit they were protecting.
Recent events (1)
  • · Z (S) $0

1910.305 A02 IX

Serious Gravity 1 2 instances 6 exposed
Issued
May 24, 2012
Abate by
May 30, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.305(a)(2)(ix):  Lamps for general illumination were not protected from accidental contact or breakage by a suitable fixture or lampholder with a guard.      (a) At the Federal Correctional Institute 1, Electrical Shop and HVAC Shop, the work bench incandescent lamp and pre-fab lamp did not have covers.
Recent events (1)
  • · Z (S) $0

1910.305 B02

Serious Gravity 5 1 instance 3 exposed
Issued
May 24, 2012
Abate by
May 30, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(2):   Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose.      (a) At the Federal Correctional Institute 1, Cook Supervisor's Office, the duplex convenience outlet cover was broken.
Recent events (1)
  • · Z (S) $0

1910.305 G02 II

Serious Gravity 5 2 instances 6 exposed
Issued
May 24, 2012
Abate by
May 30, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(ii):  Flexible cords were not used in continuous lengths without splice or tap.      (a)  At the Federal Correctional Institute 1, Unicor machine shop area, power cords for the vertical mill lamp and the Airflow Air Systems Inc., air cleaning system were repaired with electrical tape.
Recent events (1)
  • · Z (S) $0

1910.334 A03 II

Serious Gravity 1 3 instances 6 exposed
Issued
May 24, 2012
Abate by
May 30, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.334(a)(3)(ii): Attachment plugs and receptacles were connected or altered in a manner which prevented proper continuity of the electric equipment grounding conductor at the point where plugs were attached to receptacles:      (a) At the Federal Crrectional Institute 1, Unicor area machine shop, the magnifying lamp power cord is missing a ground pin.
Recent events (1)
  • · Z (S) $0

1910.157 C01

Other-than-serious 1 instance 4 exposed
Issued
May 24, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.157(c)(1):  Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries.      (a) At the Federal Correctional Institute 1, Electrical Shop, the portable fire extinguisher was blocked by a trash container.
Recent events (1)
  • · Z (O) $0

1910.305 G01 IV A

Other-than-serious 1 instance 4 exposed
Issued
May 24, 2012
Abate by
May 30, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A):   Flexible cords and cables were used as a substitute for the fixed wiring of a structure.      (a)  At the Federal Correctional Institute 1, HVAC Shop, a relocatable power tap was permanently mounted on the side of employee's desk.
Recent events (1)
  • · Z (O) $0

View Department of Justice, Bureau of Prisons's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 331900563.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.