VICTORVILLE, CA ·
OSHA Inspection: DEPARTMENT OF JUSTICE, BUREAU OF PRISONS
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of DEPARTMENT OF JUSTICE, BUREAU OF PRISONS in FEDERAL CORRECTIONAL INSTITUTE 2 13777 AIR EXPRESSWAY BOULEVARD, VICTORVILLE, CA 92394 (NAICS 922140). OSHA activity number 331900639.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- DEPARTMENT OF JUSTICE, BUREAU OF PRISONS
- Site address
- FEDERAL CORRECTIONAL INSTITUTE 2 13777 AIR EXPRESSWAY BOULEVARD
- City
- VICTORVILLE
- State
- CA
- ZIP
- 92394
- Mailing
- P.O. BOX 5400, ADELANTO, CA 92301
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- Yes
- Union status
- Union (A)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 922140
- Employees
- 938
- Ownership type
- Federal government (D)
Citations
6 citations on file for this inspection.
1910.157 C01
- Issued
- May 24, 2012
- Abate by
- May 30, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries. (a) At the Victorville Medium II FCI, kitchen area, a portable fire extinguisher was staged in the cooks supervisor's office and not securely mounted.
Recent events (1)
- · Z (S) $0
1910.157 C04
- Issued
- May 24, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(c)(4): Portable fire extinguishers were not maintained in a fully charged and operable condition. (a) At the Federal Correctional Institute 2, Officer's Mess room, the portable fire extinguisher's seal was missing or broken.
Recent events (1)
- · Z (S) $0
1910.303 B02
- Issued
- May 24, 2012
- Abate by
- May 30, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling. (a) At the Victorville Medium II FCI, Assistant Food Service Officer's area, a relocatable power tap was used to plug in the Hamilton Beach coffee maker, General Electric refrigerator and a copy machine.
Recent events (1)
- · Z (S) $0
1910.303 B07 I
- Issued
- May 24, 2012
- Abate by
- May 30, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment (a) At the Victorville Meduim II FCI, Recycling bailer #1 is missing the key over ride switch which left an opening in the control panel.
Recent events (1)
- · Z (S) $0
1910.304 B03 I
- Issued
- May 24, 2012
- Abate by
- Jun 5, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.304(b)(3)(i): All 125-volt, single-phase, 15- and 20-ampere receptacles installed in bathrooms or on rooftops did not have ground-fault circuit-interrupter protection for personnel. (a) At the Victorville Medium II FCI, CMS break room, duplex convenience outlet receptacles next to the sink were not ground fault circuit interrupter protected.
Recent events (1)
- · Z (S) $0
1910.305 B03 II
- Issued
- May 24, 2012
- Abate by
- May 30, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(3)(ii): Pull and junction boxes, were not closed by suitable covers securely fastened in place. (a) At the Victorville Medium II FCI, kitchen area, the duplex convenience outlet cover was not properly secured, gap opening showed conductors inside.
Recent events (1)
- · Z (S) $0
More inspections at Department of Justice, Bureau of Prisons
View Department of Justice, Bureau of Prisons's full OSHA safety record →
More inspections in this industry (NAICS 922140)
More inspections in CA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 331900639.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.