On , OSHA opened a planned safety inspection of DEPARTMENT OF JUSTICE, BUREAU OF PRISONS in FEDERAL CORRECTIONAL INSTITUTE 2 13777 AIR EXPRESSWAY BOULEVARD, VICTORVILLE, CA 92394 (NAICS 922140). OSHA activity number 331900639.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Department of Justice, Bureau of Prisons for free Get an email when a new federal OSHA severe-injury report for Department of Justice, Bureau of Prisons is published. One employer, no account, unsubscribe in one click.
Site address
FEDERAL CORRECTIONAL INSTITUTE 2 13777 AIR EXPRESSWAY BOULEVARD
City
VICTORVILLE
State
CA
ZIP
92394
Mailing
P.O. BOX 5400, ADELANTO, CA 92301
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
Yes
Union status
Union (A)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
922140
Employees
938
Ownership type
Federal government (D)

6 citations on file for this inspection.

1910.157 C01

Serious Gravity 1 1 instance 5 exposed
Issued
May 24, 2012
Abate by
May 30, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.157(c)(1):   Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries.    (a) At the Victorville Medium II FCI, kitchen area, a portable fire extinguisher was staged in the cooks supervisor's office and not securely mounted.
Recent events (1)
  • · Z (S) $0

1910.157 C04

Serious Gravity 1 1 instance 15 exposed
Issued
May 24, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.157(c)(4):  Portable fire extinguishers were not maintained in a fully charged and operable condition.    (a) At the Federal Correctional Institute 2, Officer's Mess room, the portable fire extinguisher's seal was missing or broken.
Recent events (1)
  • · Z (S) $0

1910.303 B02

Serious Gravity 5 1 instance 4 exposed
Issued
May 24, 2012
Abate by
May 30, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2):   Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling.    (a)  At the Victorville Medium II FCI, Assistant Food Service Officer's area, a relocatable power tap was used to plug in the Hamilton Beach coffee maker, General Electric refrigerator and a copy machine.
Recent events (1)
  • · Z (S) $0

1910.303 B07 I

Serious Gravity 5 1 instance 6 exposed
Issued
May 24, 2012
Abate by
May 30, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(7)(i):  Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment    (a) At the Victorville Meduim II FCI, Recycling bailer #1 is missing the key over ride switch which left an opening in the control panel.
Recent events (1)
  • · Z (S) $0

1910.304 B03 I

Serious Gravity 5 5 instances 8 exposed
Issued
May 24, 2012
Abate by
Jun 5, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.304(b)(3)(i):  All 125-volt, single-phase, 15- and 20-ampere receptacles installed in bathrooms or on rooftops did not have ground-fault circuit-interrupter protection for personnel.    (a)  At the Victorville Medium II FCI, CMS break room, duplex convenience outlet receptacles next to the sink were not ground fault circuit interrupter protected.
Recent events (1)
  • · Z (S) $0

1910.305 B03 II

Serious Gravity 5 1 instance 8 exposed
Issued
May 24, 2012
Abate by
May 30, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(3)(ii):  Pull and junction boxes, were not closed by suitable covers securely fastened in place.    (a) At the Victorville Medium II FCI, kitchen area, the duplex convenience outlet cover was not properly secured, gap opening showed conductors inside.
Recent events (1)
  • · Z (S) $0

View Department of Justice, Bureau of Prisons's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 331900639.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.