OSHA Inspection: HORMEL FOODS CORPORATION

Referral inspection · Health discipline

On , OSHA opened a referral health inspection of HORMEL FOODS CORPORATION in 3000 KENNEDY DRIVE, BELOIT, WI 53511 (NAICS 311422). OSHA activity number 331902395.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Hormel Foods Corporation for free Get an email when a new federal OSHA severe-injury report for Hormel Foods Corporation is published. One employer, no account, unsubscribe in one click.
Site address
3000 KENNEDY DRIVE
City
BELOIT
State
WI
ZIP
53511
Mailing
3000 KENNEDY DRIVE, BELOIT, WI 53511
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
Union (A)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
311422
Employees
289
Ownership type
Private (A)

2 citations on file for this inspection.

1910.119 D03 II

Serious Gravity 10 11 instances 9 exposed
Issued
Feb 10, 2012
Abate by
Feb 27, 2012
Penalty
Initial $7,000 · Current $4,800 Reduced
29 CFR 1910.119(d)(3)(ii): The employer did not document that equipment complies with recognized and generally accepted good engineering practices.    The employer failed to document that the Main Compressor Room and the South Compressor Room complied with recognized and generally accepted good engineering practices.    a) The employer did not comply with ANSI/IIAR 2 when it failed to ensure that there were nameplates on compressors 3, 4 and 5 in the Main Compressor Room.    b) The employer did not comply with ANSI/IIAR 2 when it failed to ensure that pipes piercing the interior walls of the Main Compressor Room were tightly sealed.     c) The employer did not comply with ANSI/IIAR 2 when it failed to ensure that an eyewash and body shower unit was located external to the Main Compressor Room and South Compressor Room.     d) The employer did not comply with ANSI/IIAR 2 when it failed to ensure that doors to the Main Compressor Room were tight fitting.    e) The employer did not comply with ANSI/IIAR 2 when it failed to ensure that exit doors from the Main Compressor Room and South Compressor Room were equipped with panic-type hardware.    f) The employer did not comply with ANSI/IIAR 2 when it failed to ensure that the Main Compressor Room and South Compressor Room were each equipped with two refrigerant detectors.     g) The employer did not comply with ANSI/IIAR 2 when it failed to ensure that the Main Compressor Room and South Compressor Room refrigerant detectors provided a visual alarm outside each entrance to the respective rooms.     h) The employer did not comply with ANSI/IIAR 2 when it failed to ensure that the Main Compressor Room and South Compressor Room had normal mechanical ventilation that provided at least 20 air exchanges per hour.    i) The employer did not comply with ANSI/IIAR 2 when it failed to ensure that there was no airflow to the maintenance shop from the Main Compressor Room.    j) The employer did not comply with ANSI/IIAR 2 when it failed to ensure that there were no combustible materials stored in the Main Compressor Room.    k) The employer did not comply with ANSI/IIAR 2 when it failed to ensure that the oil drain valve on the York freezer evaporator was equipped with a self-closing or manual quick closing emergency stop valve.
Recent events (2)
  • · I (S) $4800
  • · Z (S) $7000

1910.119 J04 III

Other-than-serious 1 instance 9 exposed
Issued
Feb 10, 2012
Abate by
Feb 27, 2012
Penalty
Initial $5,500 · Current $2,700 Reduced
29 CFR 1910.119(j)(4)(iii): The frequency of inspections and tests of process equipment was not consistent with applicable manufacturers' recommendations and good engineering practices, and more frequently if determined to be necessary by prior operating experience.    The employer did not ensure that the frequency of testing for ammonia detector in the Main Compressor Room was consistent with the manufacture's recommendations and good engineering practices.