TRAVIS AFB, CA —
OSHA Inspection: U.S. AIR FORCE 60TH AERIAL PORT SQUADRON
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of U.S. AIR FORCE 60TH AERIAL PORT SQUADRON in 90 RAGSDALE STREET BLDG. 977, TRAVIS AFB, CA 94535 (NAICS 928110). OSHA activity number 331905422.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- U.S. AIR FORCE 60TH AERIAL PORT SQUADRON
- Site address
- 90 RAGSDALE STREET BLDG. 977
- City
- TRAVIS AFB
- State
- CA
- ZIP
- 94535
- Mailing
- 540 AIRLIFT DRIVE BLDG. 381 WING 2-C, TRAVIS AFB, CA 94535
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 928110
- Employees
- 107
- Ownership type
- D
Citations
9 citations on file for this inspection.
1910.303 B02
- Issued
- Jul 30, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: Bldg. 977: On January 20, 2012 and at times prior thereto, in the following locations, homemade electrical outlets were not used or installed in accordance with their listing or labeling; A. Wood Shop: A four-plug outlet box was secured to a wooden board with a flexible cord coming out of it was used as relocatable power tap. B. The east facing dock lamp outlets; 1. Dock 4 2. Dock 6 3. Dock 8
Recent events (1)
- — Z (S) $0
1910.303 G01 I
- Issued
- Jul 30, 2012
- Abate by
- Sep 11, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1)(i): The dimension of the working space in the direction of access to live parts operating at 600 volts or less and likely to require examination, adjustment, servicing, or maintenance while alive was less than indicated in Table S1: West side of Bldg. 977: On January 20, 2012 and at times prior thereto, in the following locations, electrical control and breaker panels were not provided with adequate working clearance due to crash posts located in front of the face of the panels: A. Panel LP4: The 277/480v circuit panel door only had a nine inch clearance and could not open all the way. This panel energized the west, grid, and exterior lights. B. Control Panel CP05: The 480v control panel door for the pallet lift systems had only twenty-eight inches of clearance and could not open all the way.
Recent events (1)
- — Z (S) $0
1910.305 B01 II
- Issued
- Jul 30, 2012
- Abate by
- Sep 11, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: Bldg. 977: On January 20, 2012 and at times prior thereto, in the following locations, circuit breaker panels and disconnects were not effectively closed; A. West facing JB35 ETV#2/#3: No face cover B. South facing DP5: No face cover C. South facing PP6 ETV#1/#4: No face cover D. East facing DP4: No face cover E. East facing panel LP5: A half inch wide and ten inch long opening inside the circuit breaker panel
Recent events (1)
- — Z (S) $0
1910.305 G01 IV A
- Issued
- Jul 30, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and cables were used as a substitute for permanent wiring: Bldg. 977, Outside Loading Dock: On January 20, 2012 and at times prior thereto, a Sear MultiPlug Reel was used in lieu of permanent wiring to energize a vertical panel saw.
Recent events (1)
- — Z (S) $0
1910.305 G01 IV D
- Issued
- Jul 30, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(D): Flexible cords and cables may not be used where attached to building surfaces: Bldg. 977, 3rd dock from Wood Shop: On January 20, 2012 and at times prior thereto, an orange extension cord was plugged in and permanently secured to the building surface surrounding the overhead door with plastic ties.
Recent events (1)
- — Z (S) $0
1910.332 B01
- Issued
- Jul 30, 2012
- Abate by
- Sep 11, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety related work practices required by 29 CFR 1910.331 through 29 CFR 1910.335 that pertained to their respective job assignments: a)Bldg. 977: On January 23, 2012 and at times prior thereto, MMHS civilian employees had not been trained regarding what work practices and protective equipment were required to protect them against electric shock, arc flash and arc blast hazards while performing contact testing to confirm de-energization on control panel terminal strips.
Recent events (1)
- — Z (S) $0
1910.335 A01 I
- Issued
- Jul 30, 2012
- Abate by
- Sep 11, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with and/or did not use electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed: Bldg. 977: On January 23, 2012 and at times prior thereto, personal protective equipment such as, but not limited to, voltage rated gloves, FR clothing, face shields, balaclavas, hard hats and hearing protection were not provided to employees who performed contact testing to confirm de-energization on electrical equipment like 80 amp/480 volt control panel terminal strips.
Recent events (1)
- — Z (S) $0
1910.335 A02 II
- Issued
- Jul 30, 2012
- Abate by
- Sep 11, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.335(a)(2)(ii): Protective shields, protective barriers, or insulating materials were not used to protect each employee from shock, burns, or other electrically related injuries while that employee is working near exposed energized parts which might be accidentally contacted or where dangerous electric heating or arcing might occur: Bldg. 977: On January 23, 2012 and at times prior thereto, the voltage rated tools provided to the MMHS employees were damaged and the insulation had nicks and slices visible to the naked eye. These tools are used near live conductors and circuit parts up to 600 volts.
Recent events (1)
- — Z (S) $0
1910.334 A02 II
- Issued
- Jul 30, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.334(a)(2)(ii): When there was a defect or evidence of damage that could expose an employee to injury, the defective or damaged item was not removed from service until the repairs and tests necessary to render the electrical equipment safe had been made: Bldg. 977, East Facing Loading Docks: On January 20, 2012 and at times prior thereto, in the following locations, dock lamp power cords had several slices in them. A. Dock 17: Electrical tape was used to hide some of the slices B. Dock 16: Electrical tape was used to hide some of the slices. C. Dock 15: Electrical tape was used to hide some of the slices. D. Dock 12 E. Dock 10 F. Dock 5 G. Dock 2
Recent events (1)
- — Z (S) $0
More inspections at U.S. AIR Force 60TH Aerial Port Squadron
View U.S. AIR Force 60TH Aerial Port Squadron's full OSHA safety record →
More inspections in this industry (NAICS 928110)
More inspections in CA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 331905422.