NEWPORT, OR —
OSHA Inspection: BUREAU OF LAND MANAGEMENT, YAQUINA HEAD
Planned inspection · Health discipline
At a glance
On , OSHA opened a planned health inspection of BUREAU OF LAND MANAGEMENT, YAQUINA HEAD in 750 LIGHTHOUSE DR., NEWPORT, OR 97365 (NAICS 924120). OSHA activity number 333295020.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- BUREAU OF LAND MANAGEMENT, YAQUINA HEAD
- Site address
- 750 LIGHTHOUSE DR.
- City
- NEWPORT
- State
- OR
- ZIP
- 97365
- Mailing
- P.O. BOX 936, NEWPORT, OR 97365
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 924120
- Employees
- 15
- Ownership type
- D
Citations
3 citations on file for this inspection.
1910.253 B04 III
- Issued
- Aug 15, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.253(b)(4)(iii): Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least a) Oxygen cylinders and fuel-gas cylinders were stored together on a cart when not in use.
Recent events (1)
- — Z (S) $0
1910.303 B02
- Issued
- Aug 15, 2012
- Abate by
- Sep 6, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a) In the Interpretive Center air handling room, a junction box listed and labeled to be installed in the structure of a building was used to construct a conversion plug that allowed a piece of equipment wired with a 20 amp male plug to be powered through a 15 amp receptacle. b) Radio equipment equipped with a 20 amp male plug was powered through a 15 amp receptacle by using the above conversion plug and wiring.
Recent events (1)
- — Z (S) $0
1910.303 G02 I
- Issued
- Aug 15, 2012
- Abate by
- Sep 6, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i): a) In the Interpretive Center, air handling and communications room, in the breaker box an opening approximately 5 inches tall by 8 inches wide exposed employees to the live bus bar; b) In the Interpretive Center main office, the base plate at the bottom of the partition was loose exposing employees to the live bus bar. The employer was cited for a violation of the same standard and/or same hazard on 03/09/2011 Inspection #307507285, date 03/21/2011 of Final Order/settlement, and means of abatement.
Recent events (1)
- — Z (R) $0
More inspections at Bureau of Land Management, Yaquina Head
View Bureau of Land Management, Yaquina Head's full OSHA safety record →
More inspections in this industry (NAICS 924120)
More inspections in OR
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 333295020.