Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: CLASSIC COIL COMPANY, INC.

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of CLASSIC COIL COMPANY, INC. in 205 CENTURY DRIVE, BRISTOL, CT 06010 (NAICS 334416). OSHA activity number 333902427.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Classic Coil Company, INC. — free Get an email when a new federal OSHA severe-injury report for Classic Coil Company, INC. is published. One employer, no account, unsubscribe in one click.
Site address
205 CENTURY DRIVE
City
BRISTOL
State
CT
ZIP
06010
Mailing
205 CENTURY DRIVE, BRISTOL, CT 06010
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
334416
Employees
95
Ownership type
A

10 citations on file for this inspection.

1910.106 E06 I

Serious Gravity 5 1 instance 3 exposed
Issued
Sep 18, 2012
Penalty
Initial $2,380 · Current $1,190 Reduced
29 CFR 1910.106(e)(6)(i):  Adequate precautions were not taken to prevent the ignition of flammable vapors:  Liquid Molding: Employees dispensed Dow Corning 997(R) Varnish, which has a flash point of 77 degrees Fahrenheit, toluene and/or xylol into a plastic five gallon container for mixing. The resulting mixture was then poured into a metal vessel. Neither the container, nor the vessel were grounded.
Recent events (2)
  • — I (S) $1190
  • — Z (S) $2380

1910.106 E06 II

Serious Gravity 5 1 instance 2 exposed
Issued
Sep 18, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.106(e)(6)(ii):   Class I liquids were  dispensed into containers without the nozzle and container electrically interconnected:  Liquid Molding: Employees dispense Class 1B, Dow Corning 997(R) Varnish, Toluol and/or xylol  from a metal five gallon container into a plastic five gallon container for mixing. The resulting mixture is then dispensed into a metal vessel. Neither the metal containers, mixing containers, or the vessels were bonded.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 G01 VII A 2

Serious Gravity 5 1 instance 3 exposed
Issued
Sep 18, 2012
Penalty
Initial $2,380 · Current $1,190 Reduced
29 CFR 1910.303(g)(1)(vii)(A)(2): The space equal to the width and depth of the equipment was not kept clear of foreign systems to avoid damage from condensation, leaks, or breaks in such foreign systems. This area shall extend from the top of the electric equipment to the structural ceiling:  Main Electrical Room:  The varnish system's vacuum pump exhausted vapors from flammable liquids through polyvinyl chloride piping. The piping was located between the top of the electrical equipment and the structural ceiling. The vapors were from Dow Corning 997(R) and BC346, both of which are flammable coatings.
Recent events (2)
  • — I (S) $1190
  • — Z (S) $2380

1910.304 G05

Serious Gravity 5 1 instance 3 exposed
Issued
Sep 18, 2012
Penalty
Initial $2,380 · Current $1,190 Reduced
29 CFR 1910.304(g)(5):  The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective:  Liquid Molding Department: A Plason Manufacturing Company work lamp, mounted to a two foot by two foot dip tank, was missing its ground pin, thereby exposing employees to electric shock hazards. The tank contained residual amounts of Dow Corning 997(R) Varnish which had a flash point of 77 degrees Fahrenheit.
Recent events (2)
  • — I (S) $1190
  • — Z (S) $2380

1910.125 E01 I

Serious Gravity 1 1 instance 4 exposed
Issued
Sep 18, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.125(e)(1)(i): All electrical wiring and equipment in each vapor area and any adjacent area did not conform to the applicable hazardous (classified)-area requirements of subpart S of this part (except as specifically permitted in paragraph (g):   Liquid Molding:   A Plason Manufacturing drop light mounted on the vacuum coating tank was used for illumination during the varnish coating process.  Dow Corning 997(R) Varnish had a flashpoint of 77 degrees F and the light was located in the Class I area around the tank.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.125 E04 I

Serious Gravity 5 1 instance 3 exposed
Issued
Sep 18, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.125(e)(4)(i):  All vapor areas were not kept free of combustible debris and were not kept as free as practicable of combustible stock:  Liquid Molding:   A wood plank was used as a cover for the vacuum coating tank.  Dow Corning 997(R) Varnish which has a flashpoint of 77 degrees Fahrenheit and BC346 baking varnish which has a flashpoint of 45 degrees Fahrenheit was used in the coating process.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 A02 IX

Serious Gravity 5 1 instance 3 exposed
Issued
Sep 18, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.305(a)(2)(ix):   Lamps for general illumination were not protected from accidental contact or breakage by a suitable fixture or lampholder with a guard:  Liquid Molding Department: A Plason Manufacturing Company work lamp, mounted to a two foot by two foot dip tank, was not protected from breakage by a guard or a lampholder, thereby exposing employees to electric shock hazards. The tank contained residual amounts of Dow Corning 997(R) Varnish which had a flash point of 77 degrees Fahrenheit.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.1200 F05 I

Serious Gravity 1 1 instance 3 exposed
Issued
Sep 18, 2012
Penalty
Initial $1,785 · Current $893 Reduced
29 CFR 1910.1200(f)(5)(i): The employer did not ensure that each container of hazardous chemicals in the workplace was labeled, tagged or marked with the identity of the hazardous chemical(s) contained therein:     Liquid Molding Department: A container containing toluene and/or acetone, used to remove excess paint and varnish from coils, was not labeled with its contents.
Recent events (2)
  • — I (S) $892.5
  • — Z (S) $1785

1910.1200 F05 II

Serious Gravity 1 1 instance 2 exposed
Issued
Sep 18, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.1200(f)(5)(ii):  The employer did not ensure that each container of hazardous chemicals in the workplace was labeled, tagged or marked with the appropriate hazard warnings:  Liquid Molding Department:  A container containing toluene and/or acetone, used to remove excess paint and varnish from coils, was not labeled, tagged or marked with the appropriate hazard warnings.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.134 K06

Other-than-serious 2 instances 2 exposed
Issued
Sep 18, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.134(k)(6):  The employer did not provide the basic advisory information on respirators, as presented in Appendix D of 29 CFR 1910.134, in written or oral format to employees who wear respirators when such use was not required by the employer:    Facility: Employees that voluntarily used 3M, 8210, N95 dust masks were not provided with the advisory information found in Appendix D of 29 CFR 1910.134.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Classic Coil Company, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 333902427.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.