Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,195,903Inspections Most recent open 2026-08-18 Last loaded 2026-08-21

OSHA Inspection: PEPSI BEVERAGES CO.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of PEPSI BEVERAGES CO. in 1400 PONTIAC AVE, CRANSTON, RI 02920 (NAICS 312111). OSHA activity number 334260924.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Pepsi Beverages CO. for free Get an email when a new federal OSHA severe-injury report for Pepsi Beverages CO. is published. One employer, no account, unsubscribe in one click.
Establishment
PEPSI BEVERAGES CO.
Site address
1400 PONTIAC AVE
City
CRANSTON
State
RI
ZIP
02920
Mailing
1400 PONTIAC AVE, CRANSTON, RI 02920
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
Union (A)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
312111
Employees
182
Ownership type
Private (A)

2 citations on file for this inspection.

5(a)(1)

Deleted Serious Gravity 5 1 instance 182 exposed
Issued
Aug 28, 2012
Abate by
Oct 11, 2012
Penalty
Initial $4,250 · Current $0 Reduced
OSH ACT of 1970 Section (5)(a)(1):     Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which was free from recognized hazards that were causing or likely to cause death or serious physical harm to his employees in that employees were exposed to the hazard of inhalation of anhydrous ammonia from potential releases from the ammonia refrigeration system.  (a) Anhydrous Ammonia Refrigeration System: On or about 5-8-12, a Hansen Technologies Float Switch was observed with significant rust accumulated on the tank assembly. Pepsi Beverages Co. did not have a program of scheduled inspections of the system to ensure that the system and its individual components were in proper working order and suitable for continued service.
Recent events (2)
  • · I (S) $0
  • · Z (S) $4250

1910.137 B02 VIII

Other-than-serious 1 instance 1 exposed
Issued
Aug 28, 2012
Abate by
Sep 12, 2012
Penalty
Initial $3,400 · Current $1,700 Reduced
29 CFR 1910.137(b)(2)(viii):     Electrical protective equipment was not subjected to periodic electrical tests in accordance with Tables I-5 and I-6:  (a) Maintenance shop: The Salisbury class 00 electrical protective gloves in service and being used by a maintenance mechanic were last tested on 6-13-11, and not tested at least every six months as required by Table I-6, on or about 5-8-12.
Recent events (2)
  • · I (O) $1700
  • · Z (S) $3400

View Pepsi Beverages CO.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 334260924.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.