Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: U.S. ARMY CORPS OF ENGINEERS CHITTENDEN LOCKS

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of U.S. ARMY CORPS OF ENGINEERS CHITTENDEN LOCKS in 3015 NW 54TH ST., SEATTLE, WA 98107 (NAICS 921190). OSHA activity number 334590361.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch U.S. Army Corps of Engineers Chittenden Locks — free Get an email when a new federal OSHA severe-injury report for U.S. Army Corps of Engineers Chittenden Locks is published. One employer, no account, unsubscribe in one click.
Site address
3015 NW 54TH ST.
City
SEATTLE
State
WA
ZIP
98107
Mailing
3015 NW 54TH ST., SEATTLE, WA 98107
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
921190
Employees
60
Ownership type
D

4 citations on file for this inspection.

1910.303 G02 I

Serious Gravity 5 2 exposed
Issued
Jun 21, 2012
Abate by
Aug 3, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(2)(i):  Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i):      (a) Crane house access to behind the switch board operating at 440VAC was not guarded.
Recent events (1)
  • — Z (S) $0

1910.305 B02 I

Serious Gravity 1 1 exposed
Issued
Jun 21, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(2)(i):  Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy:    (a) Welding Shop drop cord outlet over workbench did not have an outlet cover.
Recent events (1)
  • — Z (S) $0

1910.215 B09

Repeat Gravity 1 1 exposed
Issued
Jun 21, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.215(b)(9):  Guard for abrasive wheel machine where the operator stands in front of the machine was not constructed so that the peripheral protecting member could be adjusted to the constantly decreasing diameter of the wheel:    (a) Welding shop, Tongue guard on Milwaukee bench grinder was not installed.    The U.S. Army Corp of Engineers was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.215(b)(9) Abrasive wheel machinery, which was contained in OSHA inspection number 314899196 Citation number 2, Item 4 and was affirmed as a final order on July 12, 2011, with respect to  a workplace located at Enumclaw, WA.
Recent events (1)
  • — Z (R) $0

1910.106 G09

Other-than-serious 10 exposed
Issued
Jun 21, 2012
Abate by
Jul 13, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.106(g)(9):  Fire extinguisher(s) having a minimum approved classification of 6 B, C were not provided and located so as to be within 75 feet of each pump, dispenser, underground fill pipe opening, or lubrication or service room:      (a) Fuel tank near power building did not have an extinguisher within  75 ft.
Recent events (1)
  • — Z (O) $0

View U.S. Army Corps of Engineers Chittenden Locks's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 334590361.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.