Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: DEPARTMENT OF INTERIOR - BUREAU OF LAND MANAGEMENT

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of DEPARTMENT OF INTERIOR - BUREAU OF LAND MANAGEMENT in BLM - WELLS FIELD OFFICE 3900 E. IDAHO STREET, ELKO, NV 89801 (NAICS 924120). OSHA activity number 335130985.

Watch Department OF Interior - Bureau OF Land Management — free Get an email when a new federal OSHA severe-injury report for Department OF Interior - Bureau OF Land Management is published. One employer, no account, unsubscribe in one click.
Site address
BLM - WELLS FIELD OFFICE 3900 E. IDAHO STREET
City
ELKO
State
NV
ZIP
89801
Mailing
3900 E. IDAHO STREET, ELKO, NV 89801
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
924120
Employees
130
Ownership type
D

8 citations on file for this inspection.

1910.22 A01

Serious Gravity 1 1 instance 2 exposed
Issued
Nov 14, 2012
Abate by
Nov 29, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.22(a)(1):   All places of employment, passageways, storerooms or service rooms were not kept clean and orderly or in a sanitary condition.    (a) At BLM Bldg. #3B radio technician's office, excess materials, tools, used brown boxes, cables and test equipment were placed on the floor, poor housekeeping.
Recent events (1)
  • — Z (S) $0

1910.36 G02

Serious Gravity 1 3 instances 20 exposed
Issued
Nov 14, 2012
Abate by
Nov 29, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.36(g)(2):   Exit access(es) were not at least 28 inches (71.1 cm) wide at all points.    (a) At BLM, operations ESR warehouse desk and at the engineering technicians desks, exit access were obstructed by file cabinet, map rack and cubicle partition hardware.
Recent events (1)
  • — Z (S) $0

1910.37 B02

Serious Gravity 1 2 instances 2 exposed
Issued
Nov 14, 2012
Abate by
Nov 29, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(2):   Each exit was not clearly visible and marked by a sign reading "Exit":    (a) At BLM, Bldg. #2, I.T. office, exit doors were not clearly marked by a sign reading "EXIT".
Recent events (1)
  • — Z (S) $0

1910.157 C01

Serious Gravity 1 2 instances 2 exposed
Issued
Nov 14, 2012
Abate by
Nov 29, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.157(c)(1):   Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries.    (a) At BLM Bldg. #3B radio technician's office, portable fire extinguishers were obstructed Milwaukee heavy duty tool box, Husky halogen light box and trash can filled with boxes.
Recent events (1)
  • — Z (S) $0

1910.253 B04 III

Serious Gravity 5 1 instance 30 exposed
Issued
Nov 14, 2012
Abate by
Nov 29, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.253(b)(4)(iii):   Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least one-half hour.    (a) At BLM, Bldg. #3C Shop, oxygen cylinders in storage were not separated from acetylene gas cylinder for a minimum distance of 20 feet.
Recent events (1)
  • — Z (S) $0

1910.303 B02

Serious Gravity 1 2 instances 20 exposed
Issued
Nov 14, 2012
Abate by
Nov 29, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2):   Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling.    (a) At Bldg. #3B, a relocatable power tap was used to plug in a microwave oven, a coffee maker and a refrigerator.
Recent events (1)
  • — Z (S) $0

1910.303 F02

Serious Gravity 5 2 instances 20 exposed
Issued
Nov 14, 2012
Abate by
Jan 31, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.303(f)(2):   Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident.    (a) At Bldg. #9, ATV storage shed and at Bldg. 3B, electrical power panels and branch circuit breakers were not legibly marked.
Recent events (1)
  • — Z (S) $0

1910.334 A02 I

Serious Gravity 1 1 instance 10 exposed
Issued
Nov 14, 2012
Abate by
Nov 29, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.334(a)(2)(i):   Portable cord and plug connected equipment and flexible cord sets (extension cords) were not visually inspected before use on any shift for external defects (such as loose parts, deformed and missing pins, or damage to outer jacket or insulation) and for evidence of possible internal damage (such as pinched or crushed outer jacket):    (a) At BLM, Bldg. #5 engine barn, an orange extension cord had the ground pin missing and damaged insulation outer jacket.
Recent events (1)
  • — Z (S) $0

View Department OF Interior - Bureau OF Land Management's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 335130985.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.