Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: GREAT LAKES PACKAGING CORPORATION

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of GREAT LAKES PACKAGING CORPORATION in W190 N11393 CARNEGIE DR., GERMANTOWN, WI 53022 (NAICS 322211). OSHA activity number 336895198.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Great Lakes Packaging Corporation — free Get an email when a new federal OSHA severe-injury report for Great Lakes Packaging Corporation is published. One employer, no account, unsubscribe in one click.
Site address
W190 N11393 CARNEGIE DR.
City
GERMANTOWN
State
WI
ZIP
53022
Mailing
ATTN: JOHN FRIDDELL W190 N11393 CARNEGIE DR., GERMANTOWN, WI 53022
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
322211
Employees
119
Ownership type
A

5 citations on file for this inspection.

1910.22 A01

Serious Gravity 5 1 instance 2 exposed
Issued
Feb 8, 2013
Abate by
Mar 7, 2013
Penalty
Initial $4,208 · Current $2,945 Reduced
29 CFR 1910.22(a)(1):     All places of employment, passageways, storerooms or service rooms were not kept clean and orderly or in a sanitary condition:    (a) Excessive accumulations of paper dust were observed on various high surfaces in the Baling Room: atop horizontal runs of ducts, pipes, and structural steel; on inclined structural steel, on ledges along walls, and atop some of the equipment.
Recent events (2)
  • — I (S) $2945
  • — Z (S) $4208

1910.307 C

Serious Gravity 5 1 instance 2 exposed
Issued
Feb 8, 2013
Abate by
Mar 7, 2013
Penalty
Initial $4,208 · Current $0 Reduced

Hazardous substances E101

29 CFR 1910.307(c):     Equipment, wiring methods, and installations of equipment in hazardous (classified) locations were not intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location: (a) In the Baling Room, open motor fans, control panels, disconnect switches, over-head lighting, portable vacuum cleaner units, and outlets, were not intrinsically safe, approved for a Class II, Division II location, or safe for a Class II, Division II location.
Recent events (2)
  • — I (S) $0
  • — Z (S) $4208

1910.178 C02 VI A

Serious Gravity 5 1 instance 2 exposed
Issued
Feb 8, 2013
Abate by
May 31, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.178(c)(2)(vi)(a):     The employer did not provide powered industrial trucks designated as EX for use in an atmosphere in which combustible dust is or may be in suspension continuously, intermittently, or periodically under normal operating conditions, in quantities sufficient to produce explosive or ignitable mixtures, or where mechanical failure or abnormal operation of machinery or equipment might cause such mixtures to be produced:    (a) In the Baling Room, powered industrial vehicles, such as the Dawoo Type LP, were not approved or safe for use where the potential existed for occurence of a hazardous combustible dust atmosphere.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.133 A01

Other-than-serious 1 instance 2 exposed
Issued
Feb 8, 2013
Penalty
Initial $2,525 · Current $0 Reduced
29 CFR 1910.133(a)(1):     The employer did not ensure that each affected employee uses appropriate eye or face protection when exposed to eye or face hazards from flying particles, molten metal, liquid chemicals, acids or caustic liquids, chemical gases or vapors, or potentially injurious light radiation:(a) In the Baling Room, adequate safety eye protection was not provided for the Baling Machine Operator(s) who have exposure to paper dust and debris generated by the baling process and during use of compressed air to clean the equipment.
Recent events (2)
  • — I (O) $0
  • — Z (S) $2525

1910.134 C02 I

Other-than-serious 1 instance 2 exposed
Issued
Feb 8, 2013
Abate by
Mar 7, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.134(c)(2)(i):     Respirator users were not provided with the information contained in Appendix D to 29 CFR 1910.134 when the employer determined that any voluntary respirator use was permissible:  (a) In the Baling Room, the Baling Machine Operator was permitted to use a disposable dust mask, but had not been informed of the contents of Appendix D of the Respiratory Protection standard.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Great Lakes Packaging Corporation's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 336895198.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.