ALBANY, GA —
OSHA Inspection: U.S. MARINE CORPS
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of U.S. MARINE CORPS in 814 RADFORD BLVD, SUITE 20250 DISTRIBUTION MANAGEMENT CENTER (DMC), ALBANY, GA 31704 (NAICS 493110). OSHA activity number 338437635.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- U.S. MARINE CORPS
- Site address
- 814 RADFORD BLVD, SUITE 20250 DISTRIBUTION MANAGEMENT CENTER (DMC)
- City
- ALBANY
- State
- GA
- ZIP
- 31704
- Mailing
- MARINE DEPOT MANTENANCE COMMAND (MDMC, PLANT ALBANY) 814 RADFORD BLVD, SUITE 20325, ALBANY, GA 31704
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 493110
- Employees
- 250
- Ownership type
- D
Citations
4 citations on file for this inspection.
1960.8 A
- Issued
- May 10, 2013
- Abate by
- Jun 27, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1960.8(a): The Agency head did not furnish employment and a place of employment to each employee that were free from recognized hazards that caused or were likely to cause death or serious physical harm: a) In the battery charging area, on or about and at times prior to April 4, 2013, the agency did not ensure that forklift battery chargers were placed on non-combustible bases, such as, but not limited to steel, exposing employees to the hazards associated with fire, severe and minor burns, and smoke inhalation. ABATEMENT CERTIFICATION IS REQUIRED
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 G01 I A
- Issued
- May 10, 2013
- Abate by
- Jun 27, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1)(i)(A): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the depth of the working space in the direction of access to live parts (as measured from the live parts where they were exposed or from the enclosure front or opening where they were enclosed) was less than indicated in Table S-1 of Subpart S of Part 1910: a) In the battery charging area, on or about and at times prior to April 4, 2013, the agency did not ensure that an electrical breaker box that was used to supply power to electrical outlets had three feet of access clearance, exposing employees to the electrical hazards. ABATEMENT CERTIFICATION IS REQUIRED
Recent events (2)
- — I (O) $0
- — Z (S) $0
1910.305 G02 III
- Issued
- May 10, 2013
- Abate by
- Jun 27, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws: a) In building 1121 of the Distribution Management Center, on or about and at times prior to April 4, 2013, the employer did not ensure the strain relief of an electrical power cable that fed an overhead crane was intact and free of damage, exposing employees to the hazards associated with fire and electrical shock. ABATEMENT CERTIFICATION IS REQUIRED
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.134 G01 I A
- Issued
- May 10, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.134(g)(1)(i)(A): Respirators with tight-fitting facepieces were worn by employees who had facial hair that came between the sealing surface of the facepiece and the face or that interfered with valve function: a) In the Distribution Management Center fueling and storage yard, on April 4, 2013, the agency did not ensure a private contracted employee who was required to wear a tight fitting filtering face piece respirator while applying P-19 corrosive resistant coating to military vehicles was clean-shaven, exposing the employee to a respiratory hazard. ABATEMENT CERTIFICATION IS NOT REQUIRED
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at U.S. Marine Corps