Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,191,871Inspections Most recent open 2026-07-30 Last loaded 2026-08-03

OSHA Inspection: SOLVE COMPOSITES, LLC

Follow-up inspection · Safety discipline

On , OSHA opened a follow-up safety inspection of SOLVE COMPOSITES, LLC in 29 DISTRIBUTION WAY, PLATTSBURGH, NY 12901 (NAICS 326199). OSHA activity number 338853237.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Solve Composites, LLC for free Get an email when a new federal OSHA severe-injury report for Solve Composites, LLC is published. One employer, no account, unsubscribe in one click.
Site address
29 DISTRIBUTION WAY
City
PLATTSBURGH
State
NY
ZIP
12901
Mailing
29 DISTRIBUTION WAY, PLATTSBURGH, NY 12901
Inspection type
Follow-up (F)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
326199
Employees
32
Ownership type
A

7 citations on file for this inspection.

5(a)(1)

Repeat Gravity 10 1 instance 3 exposed
Issued
Aug 7, 2013
Abate by
Aug 19, 2013
Penalty
Initial $9,800 · Current $5,880 Reduced
OSH ACT of 1970 Section (5)(a)(1): The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that: employees were exposed to explosion and deflagration hazards.       a) Trim Booth- On and before 02/12/2013- The dust collector system was not adequately designed, installed and maintained to protect employees from fire and explosion hazards associated with accumulation of combustible dust.  Hazardous accumulations of combustible dust were identified in and around the trim booth and the associated ventilation system.      Solve Composites, LLC was previously cited for a violation of this occupational safety and health standard or its equivalent standard, OSH ACT of 1970 Section (5)(a)(1): The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that: the employees were exposed to explosion and deflagration hazards, which was contained in OSHA inspection number 313761355, citation number 1, item number 3 and was affirmed as a final order on 05/09/2012, with respect to a workplace located at 29 Distribution Way Plattsburgh, NY 12901.    Among other methods, a feasible and acceptable method to correct this hazard is to ensure that the trim booth and associated dust collection systems comply with applicable requirements of NFPA 654 -- Standard for the Prevention of Fire and Dust Explosions from the Manufacturing, Processing, and Handling of Combustible Particulate Solids, 2006 Edition, and ensure that the following requirements are met:
Recent events (3)
  • · J (R) $5880
  • · C (R) $9800
  • · Z (R) $9800

1910.106 H04 I D

Repeat Gravity 5 1 instance 3 exposed
Issued
Aug 7, 2013
Abate by
Aug 19, 2013
Penalty
Initial $7,700 · Current $4,620 Reduced
29 CFR 1910.106(h)(4)(i)(d): The storage of flammable or combustible liquids in containers shall be in accordance with the applicable provisions of paragraph (d) of this section.      a) Flammable Storage Area - on or about 02/11/13 - Storage containment room containing approximately 1780 gallons of Category 2 and Category 3 flammable liquids stored in (55 gal.) fifty gallon drums and (5 gal.) five gallon pails, including but not limited to: Acetone, Styrene, K133, Poly Lite, Poly Core Gel Coat, Sirpol General Purpose Resin, Gray Gel Coat, Air Dry Mask Gray was not designed in accordance with 1910.106(d)(4) (iv), in that:  the storage room was not equipped with either a gravity or mechanical ventilation system to prevent the accumulation of flammable vapors and/or migration of flammable vapors to ignition sources.    Solve Composites, LLC was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.106(h)(4)(i)(d), which was contained in OSHA inspection number 313761355, citation number 01, item number 009 and was affirmed as a final order on 05/09/2012, with respect to a workplace located at 29 Distribution Way Plattsburgh, NY 12901.
Recent events (3)
  • · J (R) $4620
  • · C (R) $7700
  • · Z (R) $7700

1910.106 H07 I B

Repeat Gravity 5 1 instance 1 exposed
Issued
Aug 7, 2013
Abate by
Aug 19, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.106(h)(7)(i)(b): Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), shall not be dispensed into containers unless the nozzle and container are electrically interconnected. Where the metallic floorplate on which the container stands while filling is electrically connected to the fill stem or where the fill stem is bonded to the container during filling operations by means of a bond wire, the provisions of this section shall be deemed to have been complied with.   a) Reclaim area between mixing room and gel coat paint booth - On and before 2/11/13 - Emloyees did not interconnect the nozzle of a barrel containing acetone, a Category 2 flammable liquid, when open pouring into a metal parts wash bucket.   Solve Composites, LLC was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.106(h)(7)(i)(b), which was contained in OSHA inspection number 313761355, citation number 1, item number 10 and was affirmed as a final order on 05/09/2012, with respect to a workplace located at 29 Distribution Way Plattsburgh, NY 12901.
Recent events (3)
  • · J (R) $0
  • · C (R) $0
  • · Z (R) $0

1910.106 H08 I

Repeat Gravity 5 1 instance 3 exposed
Issued
Aug 7, 2013
Abate by
Aug 19, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.106(h)(8)(i): "General." Maintenance and operating practices shall be in accordance with established procedures which will tend to control leakage and prevent the accidental escape of flammable or combustible liquids. Spills shall be cleaned up promptly.   a) Between paint mixing room and gel coat paint booth - On or about 02/11/13 - Employees drained gel coat paint lines containing category 3 flammable polymerizing paints into four open quart containers; containers were left in the path of travel where they could be easily knocked over and spilled.  The Solve Composites, LLC was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.106(h)(8)(i), which was contained in OSHA inspection number 313761355, citation number 1, item number 11 and was affirmed as a final order on 05/09/2012, with respect to a workplace located at 29 Distribution Way Plattsburgh, NY 12901.
Recent events (3)
  • · J (R) $0
  • · C (R) $0
  • · Z (R) $0

1910.157 G02

Repeat Gravity 5 2 instances 1 exposed
Issued
Aug 7, 2013
Abate by
Aug 19, 2013
Penalty
Initial $7,700 · Current $4,620 Reduced
29 CFR 1910.157(g)(2): The employer shall provide the education required in paragraph (g)(1) of this section upon initial employment and at least annually thereafter.        a) Spray painting area- On or about 02/11/13- Employee working in an area requiring the installation of portable fire extinguishers was not trained in the use of the fire extinguishers.     b) Spray painting area- On or about 02/11/13- Employee working in an area requiring the installation of portable fire extinguishers was not provided annual training in the use of the fire extinguishers.     Solve Composites, LLC was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.157(g)(1), which was contained in OSHA inspection number 313761355, citation number 1, item number 16 and was affirmed as a final order on 05/09/2012, with respect to a workplace located at 29 Distribution Way Plattsburgh, NY 12901.
Recent events (3)
  • · J (R) $4620
  • · C (R) $7700
  • · Z (R) $7700

1910.305 G01 IV B

Repeat 1 instance 3 exposed
Issued
Aug 7, 2013
Abate by
Aug 19, 2013
Penalty
Initial $154 · Current $0 Reduced
29 CFR 1910.305(g)(1)(iv)(B): Flexible cords and/or cables were run through holes in walls, ceilings, or floors:     a) Office- On or about 02/11/13- Temporary flexible lead cord was run through a wall and used to supply 120v electrical power to an air conditioner.     Solve Composites, LLC was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29CFR 1910.305(g)(1)(iv)(C), which was contained in OSHA inspection number 313761355, citation number 1, item number 18 and was affirmed as a final order on 5/09/2012, with respect to a workplace located at 29 Distribution Way, Plattsburgh, NY 12901.
Recent events (3)
  • · J (R) $0
  • · C (R) $154
  • · Z (R) $154

1910.305 G01 IV A

Other-than-serious 1 instance 3 exposed
Issued
Aug 7, 2013
Abate by
Aug 19, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:     a) Office- On or about 02/11/12- Temporary flexible lead cord was used in the place of permanent building wire to supply 120v electrical power to the office computer server.