Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,193,745Inspections Most recent open 2026-08-06 Last loaded 2026-08-10

OSHA Inspection: SOUTHERN CRAFTSMEN ASSOCIATES, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of SOUTHERN CRAFTSMEN ASSOCIATES, INC. in 420 HOSEA ROAD, LAWRENCEVILLE, GA 30046 (NAICS 321918). OSHA activity number 338914526.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Southern Craftsmen Associates, INC. for free Get an email when a new federal OSHA severe-injury report for Southern Craftsmen Associates, INC. is published. One employer, no account, unsubscribe in one click.
Site address
420 HOSEA ROAD
City
LAWRENCEVILLE
State
GA
ZIP
30046
Mailing
420 HOSEA ROAD, LAWRENCEVILLE, GA 30046
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
321918
Employees
13
Ownership type
A

10 citations on file for this inspection.

1910.147 C01

Serious Gravity 10 2 instances 2 exposed
Issued
Jun 28, 2013
Abate by
Aug 30, 2013
Penalty
Initial $2,800 · Current $2,000 Reduced
29 CFR 1910.147(c)(1): The employer did not establish a program consisting of an energy control procedure and employee training to ensure that before any employee performed any servicing or maintenance on a machine or equipment where the unexpected energizing, start up or release of stored energy could occur and cause injury, the machine or equipment would be isolated, and rendered inoperative in accordance with 29 CFR 1910.147(c)(4):    On or about February 19, 2013, in the shop production area:   a) Two employees performing millwork were exposed to amputation hazards while changing saw blades on the Grizzly 12" Table saw when the employer did not have a program developed and implemented that informed the employees how to recognize and minimize lockout tagout/hazards.   b) One employee performing millwork was exposed to amputation hazards while changing blades on the Edge bander when the employer did not have a program developed and implemented that informed the employees how to recognize and minimize lockout/tagout hazards.
Recent events (2)
  • · I (S) $2000
  • · Z (S) $2800

1910.212 A01

Deleted Serious Gravity 10 1 instance 4 exposed
Issued
Jun 28, 2013
Abate by
Jul 25, 2013
Penalty
Initial $2,800 · Current $0 Reduced
29 CFR 1910.212(a)(1): Machine guarding was not provided to protect operator(s) and other employees from hazard(s) created by unguarded saw(s):   On or about February 19, 2013, in the shop production area:   Four employees performing millwork were exposed to an amputation hazard when they used the Delta 10" Compound Miter saw without a blade guard.
Recent events (2)
  • · I (S) $0
  • · Z (S) $2800

1910.213 D01

Serious Gravity 10 2 instances 4 exposed
Issued
Jun 28, 2013
Abate by
Jul 25, 2013
Penalty
Initial $2,800 · Current $1,600 Reduced
29 CFR 1910.213(d)(1): Circular handfed crosscut table saw(s) were not guarded by an automatically adjusting hood which completely enclosed that portion of the saw above the table and above the material being cut:  On or about February 19, 2013, in the shop production area:  a) Four employees performing millwork were exposed to an amputation hazard while using a Grizzly 12" table saw without a blade guard.
Recent events (2)
  • · I (S) $1600
  • · Z (S) $2800

1910.303 B02

Serious Gravity 5 1 instance 4 exposed
Issued
Jun 28, 2013
Abate by
Jul 25, 2013
Penalty
Initial $2,000 · Current $1,600 Reduced
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  On or about February 19, 2013, in the shop production area:  Four employees performing millwork were exposed to electric shock and electrocution hazard while they used the Edge bander when the employer spliced the power cord for the Grizzly dust collector to a metal junction box and cord that was designed to be mounted to the wall.
Recent events (2)
  • · I (S) $1600
  • · Z (S) $2000

1910.305 G01 IV A

Deleted Serious Gravity 5 2 instances 4 exposed
Issued
Jun 28, 2013
Abate by
Jul 25, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:  On or about February 19, 2013, in the shop production area:  a) Employees performing millwork were exposed to an electric shock hazard while using the Grizzly Dust collector when a flexible cord was spliced to a junction box and the control box of the machine.   b) Employees performing millwork were exposed to an electric shock hazard when flexible cord was connected to the 120-volt, 3-phase electrical panel #3 as permanent wiring.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.305 G02 III

Deleted Serious Gravity 5 2 instances 4 exposed
Issued
Jun 28, 2013
Abate by
Jul 25, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws:  On or about February 19, 2013, in the shop production area:  a) Employees performing millwork were exposed to an electric shock hazard when they used the 115 volt, 17 amp, Kreg machine that had strain relief damage on the pedal cord leading into the machine and the end leading to the pedal.  b) Employees performing millwork were exposed to an electric shock hazard when they used the Grizzly dust collector connected to the edge bander that had strain relief damage to the end of the power cord leading into the control box and the end of the cord spliced into a metal junction box.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.305 B01 II

Deleted Serious Gravity 5 2 instances 5 exposed
Issued
Jun 28, 2013
Abate by
Jul 25, 2013
Penalty
Initial $2,000 · Current $0 Reduced
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:  On or about February 19, 2013, in the shop production area:  a) Employees performing millwork were exposed to electric shock and electrocution hazards while working with and around equipment placed in front of a 120-volt, 3-phase electrical panel #3 that had missing circuit breakers and blanks.  b) Employees performing millwork were exposed to electric shock and electrocution hazards while working with electrical powered equipment placed in front of electrical panel #3 that had a missing punch-out exposing the wiring of the electrical panel.
Recent events (2)
  • · I (S) $0
  • · Z (S) $2000

1910.305 B02 I

Deleted Serious Gravity 5 2 instances 5 exposed
Issued
Jun 28, 2013
Abate by
Jul 25, 2013
Penalty
Initial $2,000 · Current $0 Reduced
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy:  On or about February 19, 2013, in the shop production:  a) Employees performing millwork were exposed to electric shock and electrocution hazards while picking up cabinet materials stored in front of an uncovered 110-volt receptacle with exposed wires.   b) Employees performing millwork were exposed to electric shock and electrocution hazards while using the 115-volt, 17-amp Kreg machine with a damaged cover exposing the wires.
Recent events (2)
  • · I (S) $0
  • · Z (S) $2000

1910.305 D02

Deleted Serious Gravity 5 1 instance 4 exposed
Issued
Jun 28, 2013
Abate by
Jul 25, 2013
Penalty
Initial $2,000 · Current $0 Reduced
29 CFR 1910.305(d)(2): Panelboards were not mounted in cabinets, cutout boxes, or enclosures designed for the purpose and/or were not dead front:   On or about February 19, 2013, in the storage area outside of the paint booth.   Employees performing millwork were exposed to electrical shock and electrocution hazards while storing equipment in front of the 120-volt, 3-phase electrical panel that was missing the dead front.
Recent events (2)
  • · I (S) $0
  • · Z (S) $2000

1904.4 A

Other-than-serious 1 instance 13 exposed
Issued
Jun 28, 2013
Abate by
Aug 2, 2013
Penalty
Initial $400 · Current $400
29 CFR 1904.4(a): The employer did not record each work-related fatality, injury or illness case that resulted in the general recording criteria on the OSHA Form 300 or equivalent.   On or about February 9, 2013, in the shop production area:   An employee received stitches due to a laceration of his ring and third finger operating an unguarded table saw.  The employer did not record the injury resulting in medical treatment beyond first aid on an OSHA 300 or equivalent form.
Recent events (2)
  • · I (O) $400
  • · Z (O) $400

View Southern Craftsmen Associates, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 338914526.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.