Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,197,549Inspections Most recent open 2026-08-27 Last loaded 2026-08-31

OSHA Inspection: HILAND DAIRY FOODS, LLC

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of HILAND DAIRY FOODS, LLC in 700 E. CENTRAL AVE., WICHITA, KS 67202 (NAICS 311511). OSHA activity number 338930662.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Hiland Dairy Foods, LLC for free Get an email when a new federal OSHA severe-injury report for Hiland Dairy Foods, LLC is published. One employer, no account, unsubscribe in one click.
Site address
700 E. CENTRAL AVE.
City
WICHITA
State
KS
ZIP
67202
Mailing
P.O. BOX 2199, WICHITA, KS 67201
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Health
Advance notice
No
Union status
Union (A)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
311511
Employees
153
Ownership type
Private (A)

2 citations on file for this inspection.

1910.119 D03 I B

Other-than-serious 2 instances 153 exposed
Issued
May 30, 2013
Abate by
Jul 17, 2013
Penalty
Initial $5,500 · Current $2,750 Reduced
29 CFR 1910.119(d)(3)(i)(B): The employer did not include all equipment that was part of the process on piping and instrument diagrams:     Employees were exposed to hazards associated with release of ammonia in that the employer had not verified that all P&IDs were up-to-date and accurate for use by Hiland Dairy Foods employees and contractors for the equipment listed below:       a)      High Stage Compressor #1 did not have the high temperature cutout instrument listed on PID6.   b)      High Stage Compressor #2 did not have the high temperature cutout instrument listed on PID8.   c)      Oil Drain valves show a cap on the P&IDs instead of the quick disconnects that are actually installed.
Recent events (2)
  • · I (O) $2750
  • · Z (S) $5500

1910.119 D03 II

Deleted Serious Gravity 5 1 instance 153 exposed
Issued
May 30, 2013
Abate by
Jul 17, 2013
Penalty
Initial $5,500 · Current $0 Reduced
29 CFR 1910.119(d)(3)(ii): The employer did not document that equipment complies with recognized and generally accepted good engineering practices:   Employees were exposed to hazards associated with release of ammonia in that the employer did not ensure that the linear liquid indicators were fitted with check-type shutoff valves as required in IIAR 2-2008, Section 12.1.2.
Recent events (2)
  • · I (S) $0
  • · Z (S) $5500

View Hiland Dairy Foods, LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 338930662.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.