CORPUS CHRISTI, TX —
OSHA Inspection: CITGO REFINING AND CHEMICALS COMPANY L.P.
Follow-up inspection · Safety discipline
At a glance
On , OSHA opened a follow-up safety inspection of CITGO REFINING AND CHEMICALS COMPANY L.P. in 1802 NUECES BAY BLVD, CORPUS CHRISTI, TX 78407 (NAICS 324110). OSHA activity number 338970924.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- CITGO REFINING AND CHEMICALS COMPANY L.P.
- Site address
- 1802 NUECES BAY BLVD
- City
- CORPUS CHRISTI
- State
- TX
- ZIP
- 78407
- Mailing
- P.O. BOX 9176, CORPUS CHRISTI, TX 78469
What kind of inspection was it?
- Inspection type
- Follow-up (F)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 324110
- Employees
- 545
- Ownership type
- A
Citations
2 citations on file for this inspection.
1910.304 F01 IV
- Issued
- Jun 11, 2013
- Abate by
- Jul 29, 2013
- Penalty
- Initial $15,000 · Current $7,000 Reduced
General-duty citation text
29 CFR 1910.304(f)(1)(iv): Overcurrent devices for circuits rated 600 volts, nominal, or less, were not readily accessible to each employee or authorized building management. The employer does not protect employees from the hazards associated with blocked electrical equipment. This violation was observed on or about April 30, 2013 at the Citgo Refining & Chemical Company LP, in the East Plant 1 Alky Unit, in areas, such as, but not limited to: a. In the Old Alky Comfort Station, the 120/208V, 225 ampere, lighting panel A6810087, has black plastic spools, a carton box, and a chair in front of the energized panel. b. In the Alky Change House, the electrical panel ID# 83-DP-101, has table, microwave and laundry driers in front of the energized panel. The Citgo Refining & Chemicals Company L.P. was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910. 303(g)(1)(ii), which was contained in OSHA inspection number #313467136, citation number #01, item number #10 and was affirmed as a final order on February 7, 2011 with respect to a workplace located at 1802 Nueces Bay Blvd. Corpus Christi, TX 78469 Pursuant to 29 C.F.R. 1903.19, within ten (10) calendar days of the abatement date the employer must submit documentation(s) showing that it is in compliance with the standard, including explanation(s) of how the employer is to ensure electrical equipment is not blocked.
Recent events (2)
- — I (S) $7000
- — Z (R) $15000
1910.303 B02
- Issued
- Jun 11, 2013
- Abate by
- Jun 28, 2013
- Penalty
- Initial $200 · Current $3,500
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: The employer does not protect each employee from electric shock and/or fire hazards. This violation was observed on or about April 30, 2013 at the CITGO Refining & Chemical Company LP, in the East Plant 1-Alky Unit 83, in the Alky Cumene comfort station where two surge protected power strips are interconnected or "daisy chained" to provide more outlets. The Citgo Refining & Chemicals Company L.P. was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910. 305(g)(1)(iv)(A), which was contained in OSHA inspection number #313467136, citation number #01, item number #13 and was affirmed as a final order on February 7, 2011 with respect to a workplace located at 1802 Nueces Bay Blvd.Corpus Christi, TX 78469 Pursuant to 29 C.F.R. 1903.19, within ten (10) calendar days of the abatement date the employer must submit documentation(s) showing that it is in compliance with the standard, including explanation(s) of how the employer is to ensure power strips are not interconnected.
Recent events (2)
- — I (O) $3500
- — Z (R) $200
More inspections at Citgo Refining and Chemicals Company L.P.
View Citgo Refining and Chemicals Company L.P.'s full OSHA safety record →
More inspections in this industry (NAICS 324110)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 338970924.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.