On , OSHA opened a planned safety inspection of GILLINDER BROTHERS, INC. in ERIE & LIBERTY STREETS, PORT JERVIS, NY 12771 (NAICS 327212). OSHA activity number 338974876.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Gillinder Brothers, INC. — free Get an email when a new federal OSHA severe-injury report for Gillinder Brothers, INC. is published. One employer, no account, unsubscribe in one click.
Site address
ERIE & LIBERTY STREETS
City
PORT JERVIS
State
NY
ZIP
12771
Mailing
P.O. BOX 1007, PORT JERVIS, NY 12771
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
327212
Employees
75
Ownership type
A

6 citations on file for this inspection.

5(a)(1)

Serious Gravity 5 3 instances 3 exposed
Issued
Aug 19, 2013
Abate by
Aug 29, 2013
Penalty
Initial $3,500 · Current $1,400 Reduced
OSH ACT of 1970 Section (5)(a)(1): The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to struck-by hazards in the event of a hoist failure:     a) Mixing area- On or about 03/21/13- An overhead carrier beam rail and attachments (orange hoist) used to lift a mixing bin containing raw materials for glass making, was not rated, tested or inspected.     b) Machine shop- On or about 03/21/13-An overhead carrier beam rail and attachments (red hoist) used to lift machine parts was not rated, tested or inspected.     c) Machine shop- On or about 03/21/13- An overhead carrier beam rail and attachments (blue hoist) used to lift machine parts was not rated, tested or inspected.
Recent events (2)
  • — I (S) $1400
  • — Z (S) $3500

1910.212 A01

Serious Gravity 10 1 instance 1 exposed
Issued
Aug 19, 2013
Abate by
Aug 29, 2013
Penalty
Initial $4,900 · Current $1,960 Reduced
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks:     a) Machine shop- On or about 03/21/13- Employee operating a Tur-63 Turett lathe was exposed to contact with the rotating chuck while hand sanding a metal glass mold.
Recent events (2)
  • — I (S) $1960
  • — Z (S) $4900

1910.134 C02 I

Other-than-serious 1 instance 1 exposed
Issued
Aug 19, 2013
Abate by
Aug 29, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.134(c)(2)(i): Respirator users were not provided with the information contained in Appendix D to 29 CFR 1910.134 when the employer determined that any voluntary respirator use was permissible:  a) Mixing area- On or about 03/21/13- Employee voluntarily use an N95 respirator was not provided appendix D of the OSHA standard.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.147 C04 I

Other-than-serious 3 instances 3 exposed
Issued
Aug 19, 2013
Abate by
Aug 29, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.147(c)(4)(i): Procedures were not developed, documented and utilized for the control of potentially hazardous energy when employees were engaged in activities covered by this section:  a) Manufacturing plant- On and before 03/25/13 -- Procedures were not developed for employees performing maintenance on equipment requiring sequential steps for energy control (lockout-tagout) and/or control of multiple energy sources, including but not limited to:  Ingersol-Rand air compressor, Sullair compressor, and Lher machine.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.147 C06 I

Other-than-serious 1 instance 2 exposed
Issued
Aug 19, 2013
Abate by
Aug 29, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.147(c)(6)(i): The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirement of this standard were being followed:  a) Throughout facility -- On and before 03/25/13 -- The empoyer had not conducted periodic inspections of the energy control procedures since 1996.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.147 C07 I A

Other-than-serious 1 instance 4 exposed
Issued
Aug 19, 2013
Abate by
Aug 29, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.147(c)(7)(i)(A): Authorized employee(s) did not receive training in the recognition of applicable hazardous energy sources, the type and magnitude of the energy available in the workplace, and the methods and means necessary for energy isolation:   a) Throughout facility- On and before 03/25/13 -- Authorized employees performing maintenance activity on machines and equipment, including but not limited to:  Lehr machine, air compressors, and glass furnance, were not trained in energy control (lockout-tagout) procedures.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Gillinder Brothers, INC.'s full OSHA safety record →