OSHA Inspection: FARM SERVICE AGENCY

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of FARM SERVICE AGENCY in 2145 BASIN ST SW, SUITE A, EPHRATA, WA 98823 (NAICS 522298). OSHA activity number 338975287.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Farm Service Agency — free Get an email when a new federal OSHA severe-injury report for Farm Service Agency is published. One employer, no account, unsubscribe in one click.
Establishment
FARM SERVICE AGENCY
Site address
2145 BASIN ST SW, SUITE A
City
EPHRATA
State
WA
ZIP
98823
Mailing
2145 BASIN ST SW, SUITE A, EPHRATA, WA 98823
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
522298
Employees
8
Ownership type
D

4 citations on file for this inspection.

1910.303 B02

Serious Gravity 1 6 instances 8 exposed
Issued
Apr 15, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled equipment was not installed and used in accordance with any instructions included in the listing or labeling:    a)  Office Suite, where electrical equipment not used as listed or labeled included:    1. FLM Office, where a relocatable power tap was used to supply power to the Holmes floor heater and the white fan.   2. CED Office, where a relocatable power tap was used to supply power to the Holmes floor heater.  3. IT Cubicle, where two relocatable power taps were daisy chained and used to supply power to computer equipment.  4. FLO Office, where a relocatable power tap was used to supply power to the Sunbeam floor heater.  5. PT Cubicle, where a relocatable power tap was daisy chained with an extension cord and used to supply power to computer equipment.  6. Appraiser Office, where a relocatable power tap was used to supply power to the Holmes floor heater, the Brentwood water kettle, and the Betty Crocker cup warmer.
Recent events (1)
  • — Z (S) $0

1910.37 B02

Other-than-serious 3 instances 8 exposed
Issued
Apr 15, 2013
Abate by
May 31, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit":    a) Office Suite, where the designated emergency exit doors not equipped with exit signs included:    1. Front Entrance  2. Map Room  3. Shared Conference room
Recent events (1)
  • — Z (O) $0

1910.303 G01 II

Other-than-serious 1 instance 8 exposed
Issued
Apr 15, 2013
Abate by
May 31, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(ii): Working space for equipment likely to require examination, adjustment, servicing, or maintenance while energized was used for storage:    a)  Storage Room, where items including shredders and a filing cabinet were stored in front of the electrical panel.
Recent events (1)
  • — Z (O) $0

1960.25 C

Other-than-serious 1 instance 8 exposed
Issued
Apr 15, 2013
Abate by
May 31, 2013
Penalty
Initial $0 · Current $0
29 CFR 1960.25(c): The Agency did not inspect annually, all areas in each workplace, including office operations:    a) Facility, where an annual inspection of the workplace had not been conducted.
Recent events (1)
  • — Z (O) $0

View Farm Service Agency's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 338975287.