CLEVELAND, OH —
OSHA Inspection: AUTOMATED PACKAGING SYSTEMS, INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of AUTOMATED PACKAGING SYSTEMS, INC. in 13555 MCCRAKEN RD., CLEVELAND, OH 44125 (NAICS 323112). OSHA activity number 338981764.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- AUTOMATED PACKAGING SYSTEMS, INC.
- Site address
- 13555 MCCRAKEN RD.
- City
- CLEVELAND
- State
- OH
- ZIP
- 44125
- Mailing
- 10175 PHILIPP PKWY., STREETSBORO, OH 44241
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 323112
- Employees
- 115
- Ownership type
- A
Citations
5 citations on file for this inspection.
1910.23 C01
- Issued
- Sep 16, 2013
- Penalty
- Initial $2,550 · Current $1,785 Reduced
General-duty citation text
29 CFR 1910.23(c)(1): Open-sided floor(s) or platform(s) 4 feet or more above the adjacent floor or ground level were not guarded by standard railings (or the equivalent as specified in 29 CFR 1910.23(e) (3) (i) through (v)), on all open sides: On and before 03/28/2013 the work platform, located adjacent to the office area, was missing a four (4) foot section of the lower railing.
Recent events (2)
- — I (S) $1785
- — Z (S) $2550
1910.212 A01
- Issued
- Sep 16, 2013
- Abate by
- Oct 3, 2013
- Penalty
- Initial $4,250 · Current $2,975 Reduced
General-duty citation text
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks: On or before 03/28/2013, the employer did not ensure that various equipment or machinery used at the site was effectively guarded. The unguarded equipment includes: a. The unused portion of the blade above the work table, of the (vertical) band saw, located in the maintenance department; b. The rotating chuck of the automated lathe, located in the maintenance department; c. The ingoing nip point, on the out-put side of Winders 1-3, located in the Extruder department.
Recent events (2)
- — I (S) $2975
- — Z (S) $4250
1910.212 A03 II
- Issued
- Sep 16, 2013
- Abate by
- Oct 3, 2013
- Penalty
- Initial $3,400 · Current $2,380 Reduced
General-duty citation text
29 CFR 1910.212(a)(3)(ii): The point(s) of operation of machinery were not guarded to prevent employee(s) from having any part of their body in the danger zone(s) during operating cycle(s): On and before 03/28/2013 the arbor press, located in the maintenance department, was not equipped with point of operation guarding.
Recent events (2)
- — I (S) $2380
- — Z (S) $3400
1910.151 C
- Issued
- Sep 16, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.151(c): Where employees were exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body were not provided within the work area for immediate emergency use: The employer did not ensure that an eyewash or quick drenching unit was available in the immediate work area of the battery charging/changing station for emergency use by an employee tasked with adding water to sulfuric acid batteries.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.303 E
- Issued
- Sep 16, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(e): Markings were not provided on electrical equipment giving voltage, current, wattage, and other ratings as necessary: Labeling to identify the voltage, current, wattage, and other required ratings was not marked on electrical equipment located at the facility. The electrical equipment includes: a. The 480 volt battery charger feeds, located in the battery changing/charging area; b. The 480 volt electrical control disconnect for the lathe, located in the maintenance department.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Automated Packaging Systems, INC.
View Automated Packaging Systems, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 323112)
More inspections in OH
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 338981764.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.