Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,194,531Inspections Most recent open 2026-08-11 Last loaded 2026-08-14

OSHA Inspection: NATIONAL PARK SERVICE CHANNEL ISLANDS NATIONAL PARK

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of NATIONAL PARK SERVICE CHANNEL ISLANDS NATIONAL PARK in 1691 SPINNAKER DRIVE, VENTURA, CA 93001 (NAICS 712190). OSHA activity number 338990948.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch National Park Service Channel Islands National Park for free Get an email when a new federal OSHA severe-injury report for National Park Service Channel Islands National Park is published. One employer, no account, unsubscribe in one click.
Site address
1691 SPINNAKER DRIVE
City
VENTURA
State
CA
ZIP
93001
Mailing
1901 SPINNAKER DRIVE, VENTURA, CA 93001
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
712190
Employees
6
Ownership type
Federal government (D)

7 citations on file for this inspection.

1910.37 A04

Serious Gravity 5 3 instances 6 exposed
Issued
May 29, 2013
Abate by
Jun 24, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.37(a)(4): Safeguard(s) designed to protect employees during an emergency (e.g., sprinkler systems, alarm systems, fire doors, exit lighting), were not in proper working order at all times.  a) Second floor, above door - On or about 4/2/2013, a self-illuminating emergency exit sign was not in proper working order.  b) Emergency route stairwell 1 - On or about 4/2/2013, self-illuminating emergency exit signs were not in proper working order.  c) Emergency route stairwell 2 - On or about 4/2/2013, a self-illuminating emergency exit sign was not in proper working order.
Recent events (1)
  • · Z (S) $0

1910.159 C10

Serious Gravity 5 1 instance 6 exposed
Issued
May 29, 2013
Abate by
Jun 24, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.159(c)(10): The minimum vertical clearance of 18 inches between automatic sprinkler systems sprinklers and the material below was not maintained:  Park ranger  storage room - On or about 4/2/2013, the employer did not maintain a minimum vertical clearance of 18 inches between automatic sprinkler systems sprinklers and boxes.
Recent events (1)
  • · Z (S) $0

1910.303 B02

Serious Gravity 5 4 instances 6 exposed
Issued
May 29, 2013
Abate by
Jun 24, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  a) Admin cubicle - On or about 4/2/2013, two surge protectors were daisy chained together.   b) Human resources office - On or about 4/2/2013, an extension cord was daisy-chained to a surge protector.  c) Budget office - On or about 4/2/2013, two surge protectors were daisy chained together.   d) Park ranger desk - On or about 4/2/2013, two surge protectors were daisy chained together.
Recent events (1)
  • · Z (S) $0

1910.303 G01 II

Serious Gravity 5 1 instance 2 exposed
Issued
May 29, 2013
Abate by
Jun 24, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:  Break room - On or about 4/2/2013, the area in front of an electrical panel was used to store a water bottle rack.
Recent events (1)
  • · Z (S) $0

1910.305 G01 IV A

Serious Gravity 5 2 instances 6 exposed
Issued
May 29, 2013
Abate by
Jun 24, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:  a) Conference room - On or about 4/2/2013, an extension cord was used as permanent wiring.  b) Human resources office - On or about 4/2/2013, an extension cord was used as permanent wiring.
Recent events (1)
  • · Z (S) $0

1910.305 J02 IV

Serious Gravity 5 3 instances 6 exposed
Issued
May 29, 2013
Abate by
Jun 24, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.305(j)(2)(iv): A receptacle installed in a wet or damp location was not suitable for the location:  a) Break room - On or about 4/2/2013, an electrical outlet near a sink was not protected by GFCI.   b) Admin restroom - On or about 4/2/2013, an electrical outlet near a sink was not protected by GFCI.   c) Park ranger restroom - On or about 4/2/2013, an electrical outlet near a sink was not protected by GFCI.
Recent events (1)
  • · Z (S) $0

1910.334 A02 III

Serious Gravity 5 1 instance 6 exposed
Issued
May 29, 2013
Abate by
Jun 24, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.334(a)(2)(iii): When an attachment plug is to be connected to a receptacle (including an on a cord set), the relationship of the plug and receptacle contacts was not checked to ensure that they are of proper mating configurations:  Conference room - On or about 4/2/2013, an extension cord with no ground connection was used in conjunction with grounded electrical equipment and the ground pin was exposed.
Recent events (1)
  • · Z (S) $0

View National Park Service Channel Islands National Park's full OSHA safety record →