OSHA Inspection: U.S. DEPARTMENT OF THE NAVY

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of U.S. DEPARTMENT OF THE NAVY in BUILDING 286 MCRD, PARRIS ISLAND, SC 29905 (NAICS 928110). OSHA activity number 339039430.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch U.S. Department of the Navy for free Get an email when a new federal OSHA severe-injury report for U.S. Department of the Navy is published. One employer, no account, unsubscribe in one click.
Site address
BUILDING 286 MCRD
City
PARRIS ISLAND
State
SC
ZIP
29905
Mailing
PO BOX 19580 ATTN: SAFD, PARRIS ISLAND, SC 29905
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Union (A)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
928110
Employees
13
Ownership type
Federal government (D)

7 citations on file for this inspection.

1910.23 A08

Serious Gravity 1 1 instance 1 exposed
Issued
Jul 10, 2013
Abate by
Jul 22, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.23(a)(8): Every floor hole into which persons can accidentally walk were not guarded:   a) Center of the basement: A hole cut into the concrete floor for a sump pump was not covered, exposing employees to tripping hazards.   ABATEMENT CERTIFICATION IS REQUIRED
Recent events (1)
  • · Z (S) $0

1910.157 E02

Serious Gravity 10 1 instance 3 exposed
Issued
Jul 10, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.157(e)(2): Portable fire extinguishers were not visually inspected at least monthly:   a) Northeast corner of the basement: A carbon dioxide portable fire extinguisher had not been inspected since 1997.
Recent events (1)
  • · Z (S) $0

1910.157 E03

Serious Gravity 10 1 instance 3 exposed
Issued
Jul 10, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.157(e)(3): Portable fire extinguishers were not subjected to an annual maintenance check.   a) Northeast corner of the basement: A carbon dioxide portable fire extinguisher had not had an annual maintenance check since 1995 or 1997.
Recent events (1)
  • · Z (S) $0

1910.303 B02

Serious Gravity 5 2 instances 3 exposed
Issued
Jul 10, 2013
Abate by
Jul 22, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:   a) Northeast end of the basement: Two 120 volt electrical conductors were capped off with wire nuts, but were left dangling out of the plastic conduit and exposed to damage rather than being connected to machinery or blanked off.    b) Southeast corner of the basement: An electrical hot water heater was located on the bare concrete floor that  was prone to flooding and it is not listed for installation in wet environments.   ABATEMENT CERTIFICATION IS REQUIRED
Recent events (1)
  • · Z (S) $0

1910.305 E01

Serious Gravity 10 4 instances 3 exposed
Issued
Jul 10, 2013
Abate by
Aug 12, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.305(e)(1): Cabinets, cutout boxes, fittings, boxes, and panel board enclosures in damp or wet locations were not installed to prevent moisture or water from entering and accumulating within the enclosures.     a) East wall of the basement: A 120 volt electrical panel board containing circuit breakers was installed in a manner which allowed water in a flooded basement to enter the panel.   b) North wall of the basement a duplex receptacle outlet,  though provided with weather proof covers was not installed in a manner to prevent water from entering.   c) North wall of the basement:  A Siemens-Allis switch box and supporting conduit are not installed in a manner so that water could not enter.   d) northeast end of the basement: Two 120 volt electrical conductors sticking out from the end of plastic conduit and having wire nuts placed on the end, was not installed in a manner to prevent water from entering.  ABATEMENT DOCUMENTATION IS REQUIRED
Recent events (1)
  • · Z (S) $0

1910.303 E

Serious Gravity 10 1 instance 13 exposed
Issued
Jul 10, 2013
Abate by
Aug 12, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.303(e): The manufacturer's name, trademark, or other descriptive marking by which the organization responsible for the product may be identified was not placed on the electrical equipment that was used nor were there markings provided on electrical equipment giving voltage, current, wattage, and other ratings as necessary.   a) West end first floor of Building 286: The main electrical panel for the building was located on the first floor and was devoid of any markings as to its voltage, purpose, manufacturer name or any other ratings.   ABATEMENT CERTIFICATION IS REQUIRED.
Recent events (1)
  • · Z (S) $0

1910.333 A01

Serious Gravity 10 1 instance 1 exposed
Issued
Jul 10, 2013
Abate by
Jul 22, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.333(a)(1): Live parts to which an employee was exposed were not deenergized before the employee worked on or near them:   a) East wall of the basement: An electrical employee worked on an open 120 volt electrical panel without first deenergizing that panel.   ABATEMENT CERTIFICATION IS REQUIRED
Recent events (1)
  • · Z (S) $0

View U.S. Department of the Navy's full OSHA safety record →