Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: UNGERER & COMPANY

Referral inspection · Health discipline

On , OSHA opened a referral health inspection of UNGERER & COMPANY in 110 N COMMERCE WAY, BETHLEHEM, PA 18017 (NAICS 311942). OSHA activity number 339094815.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Ungerer & Company — free Get an email when a new federal OSHA severe-injury report for Ungerer & Company is published. One employer, no account, unsubscribe in one click.
Establishment
UNGERER & COMPANY
Site address
110 N COMMERCE WAY
City
BETHLEHEM
State
PA
ZIP
18017
Mailing
110 N COMMERCE WAY, BETHLEHEM, PA 18017
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
311942
Employees
96
Ownership type
A

6 citations on file for this inspection.

1910.106 E03 V A

Serious Gravity 5 1 instance 20 exposed
Issued
Jul 19, 2013
Abate by
Sep 5, 2013
Penalty
Initial $1,913 · Current $1,913

Hazardous substances 1060

29 CFR 1910.106(e)(3)(v)(a): Areas as defined in paragraph (e)(3)(i) of this section using Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), were not ventilated at a rate of at least 1 cubic foot per minute per square foot of solid floor area:   a) Fragrance Solutions Room: The room containing tanks of ethyl alcohol as part of the fragrance process has a ventilation rate less than the required 1 cubic foot per minute per square foot of floor area exposing employees to fire and burn hazards, on or about May 31, 2013.    Abatement certification required within 10 days after abatement date.  The certification shall include a statement that abatement is complete, date and method of abatement, and states that employees and their representatives were informed of this abatement.
Recent events (2)
  • — I (S) $1912.5
  • — Z (S) $1912.5

1910.106 E09 I

Serious Gravity 5 1 instance 20 exposed
Issued
Jul 19, 2013
Abate by
Aug 14, 2013
Penalty
Initial $6,300 · Current $6,300
29 CFR 1910.106(e)(9)(i): Spills were not cleaned up promptly:   a) Fragrance Solutions Room: Spill kits and other appropriate spill clean-up equipment were not readily available for employees to properly clean-up a flammable liquid spill exposing employees to fire and burn hazards, on or about May 31, 2013.     Abatement certification and documentation required within 10 days after abatement date. The certification shall include a statement that abatement is complete, the date and method of abatement, and state that employees and their representatives were informed of this abatement.  Abatement documentation shall include documents demonstrating that abatement is complete, such as evidence of the purchase or repair of equipment, photograph or video evidence of abatement or other written records.
Recent events (2)
  • — I (S) $6300
  • — Z (S) $6300

1910.120 Q06

Serious Gravity 5 1 instance 20 exposed
Issued
Jul 19, 2013
Abate by
Aug 14, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.120(q)(6): The employer did not provide training in accordance with 29 CFR 1910.120(q)(6)(i) through (q)(6)(v) for employees who participated in or were expected to participate in emergency response:   Or in the alternative:   29 CFR 1910.1200(h)(3)(iii): Employee training did not include the measures employees can take to protect themselves from chemical hazards, including specific procedures the employer had implemented to protect employees from exposure to hazardous chemicals, such as appropriate work practices, emergency procedures and personal protective equipment to be used:     a) Fragrance Solutions Room: Employees were not provided training on proper procedures and equipment required to safely clean up spills of flammable liquids exposing them fire, burn and health hazards, on or about May 31, 2013.    Abatement certification and documentation required within 10 days after abatement date. The certification shall include a statement that abatement is complete, the date and method of abatement, and state that employees and their representatives were informed of this abatement.  Abatement documentation shall include documents demonstrating that abatement is complete, such as evidence of the purchase or repair of equipment, photograph or video evidence of abatement or other written records.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.106 E06 II

Serious Gravity 5 1 instance 20 exposed
Issued
Jul 19, 2013
Abate by
Aug 14, 2013
Penalty
Initial $1,913 · Current $1,913
29 CFR 1910.106(e)(6)(ii): Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), was dispensed into containers unless the nozzle and container are electrically interconnected.   a) Fragrance Solutions Room: Mixed terpenes, a flammable liquid, was transferred between 55 gallon drums by gravity flow through an open valve, exposing employee to fire and burn hazards, on or about May 31, 2013.   Abatement certification required within 10 days after abatement date.  The certification shall include a statement that abatement is complete, date and method of abatement, and states that employees and their representatives were informed of this abatement.
Recent events (2)
  • — I (S) $1912.5
  • — Z (S) $1912.5

1910.307 C02 I

Serious Gravity 5 1 instance 20 exposed
Issued
Jul 19, 2013
Abate by
Sep 15, 2013
Penalty
Initial $1,575 · Current $1,575
29 CFR 1910.307(c)(2)(i): Equipment in hazardous (classified) location(s) was not approved for the class of location:    a) Fragrance Solutions Room: Employees were exposed to fire and burn hazards while using a Tennant 480 ES floor scrubber to clean up a flammable liquid spill, on or about May 31, 2013.    No abatement certification or documentation required.
Recent events (2)
  • — I (S) $1575
  • — Z (S) $1575

1910.307 G02 I

Serious Gravity 5 1 instance 20 exposed
Issued
Jul 19, 2013
Abate by
Sep 15, 2013
Penalty
Initial $1,575 · Current $1,575
29 CFR 1910.307(g)(2)(i): Locations were not classified based on the properties of the flammable vapors, liquids, or gases that present and the likelihood that a flammable or combustible concentration or quantity was present.     a) Fragrance Solutions Room: A Tennant 480 ES floor scrubber was used in a Division 1, Class 2 room to clean-up a flammable liquid spill which is not in accordance with the UL listing exposing employees to fire and burn hazards, on or about May 31, 2013.      No abatement certification or documentation required.
Recent events (2)
  • — I (S) $1575
  • — Z (S) $1575

View Ungerer & Company's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339094815.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.