Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: SCOTT STEWART

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of SCOTT STEWART in 602 EAST WEBB STREET, MOUNTAIN VIEW, AR 72560 (NAICS 321991). OSHA activity number 339174906.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Scott Stewart — free Get an email when a new federal OSHA severe-injury report for Scott Stewart is published. One employer, no account, unsubscribe in one click.
Establishment
SCOTT STEWART
Site address
602 EAST WEBB STREET
City
MOUNTAIN VIEW
State
AR
ZIP
72560
Mailing
602 EAST WEBB STREET, MOUNTAIN VIEW, AR 72560
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
321991
Employees
3
Ownership type
A

6 citations on file for this inspection.

1910.303 G02 I

Serious Gravity 10 2 instances 2 exposed
Issued
Jul 31, 2013
Abate by
Aug 8, 2013
Penalty
Initial $2,800 · Current $2,800
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i):    On or about July 9th, 2013 and times prior thereto, the employer operated electrical equipment with exposed conductors in the following instances:      a.  Main breaker panel for the site did not have a cover       b. The air compressor for the site had exposed conductors on the pressure switch relay   These conditions exposed employees to the hazard of electrical shock.
Recent events (1)
  • — Z (S) $2800

1910.305 B02 I

Serious Gravity 10 1 instance 2 exposed
Issued
Jul 31, 2013
Abate by
Aug 8, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy:   On or about July 9th, 2013 and times prior thereto, the electrical outlet box that flexible cords were plugged into  located in the open work area of the corrugated building did not have a cover, exposing employees to the hazard of electrical shock.
Recent events (1)
  • — Z (S) $0

1910.305 G01 IV A

Serious Gravity 1 1 instance 2 exposed
Issued
Jul 31, 2013
Abate by
Sep 13, 2013
Penalty
Initial $1,200 · Current $1,200
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:   On or about July 9th, 2013 and times prior thereto, employer had in use flexible cords in lieu of permanent wiring of the structure in the storage room and saw areas where overhead lights were powered by extension cords.    This condition exposed employees to the hazards associated with fire.
Recent events (1)
  • — Z (S) $1200

1910.305 G01 IV B

Serious Gravity 5 1 instance 2 exposed
Issued
Jul 31, 2013
Abate by
Aug 8, 2013
Penalty
Initial $2,000 · Current $2,000
29 CFR 1910.305(g)(1)(iv)(B): Flexible cords and/or cables were run through holes in walls, ceilings, or floors:   On or about July 9th, 2013 and times prior thereto, employer had powered an air compressor by running a flexible cord through a hole in the metal corrugated building wall.  This condition exposed employees to the hazard of electrical shock and fire.
Recent events (1)
  • — Z (S) $2000

1910.305 J02 II

Serious Gravity 5 1 instance 2 exposed
Issued
Jul 31, 2013
Abate by
Aug 8, 2013
Penalty
Initial $2,000 · Current $2,000
29 CFR 1910.305(j)(2)(ii): Receptacles, cord connectors, and attachment plugs were not constructed so that a receptacle or cord connector would not accept an attachment plug with a different voltage or current rating than that for which the device was intended:   On or about July 9th, 2013 and times prior thereto, employer had modified a 220 volt plug to accept a 110 volt feed.  This configuration exposed employees to the hazards of electrical shock and fire.
Recent events (1)
  • — Z (S) $2000

1910.22 A01

Other-than-serious 1 instance 2 exposed
Issued
Jul 31, 2013
Abate by
Aug 22, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.22(a): 29 CFR 1910.22(a)(1):  Place(s) of employment were not kept clean and orderly, or in a sanitary condition:   On or about July 9th, 2013 and times prior thereto, the area in front of the main breaker panel was clutter with materials and debris, exposing employees to trip and fall hazards.
Recent events (1)
  • — Z (O) $0

View Scott Stewart's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339174906.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.