MOUNTAIN VIEW, AR —
OSHA Inspection: SCOTT STEWART
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of SCOTT STEWART in 602 EAST WEBB STREET, MOUNTAIN VIEW, AR 72560 (NAICS 321991). OSHA activity number 339174906.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- SCOTT STEWART
- Site address
- 602 EAST WEBB STREET
- City
- MOUNTAIN VIEW
- State
- AR
- ZIP
- 72560
- Mailing
- 602 EAST WEBB STREET, MOUNTAIN VIEW, AR 72560
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 321991
- Employees
- 3
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.303 G02 I
- Issued
- Jul 31, 2013
- Abate by
- Aug 8, 2013
- Penalty
- Initial $2,800 · Current $2,800
General-duty citation text
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i): On or about July 9th, 2013 and times prior thereto, the employer operated electrical equipment with exposed conductors in the following instances: a. Main breaker panel for the site did not have a cover b. The air compressor for the site had exposed conductors on the pressure switch relay These conditions exposed employees to the hazard of electrical shock.
Recent events (1)
- — Z (S) $2800
1910.305 B02 I
- Issued
- Jul 31, 2013
- Abate by
- Aug 8, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy: On or about July 9th, 2013 and times prior thereto, the electrical outlet box that flexible cords were plugged into located in the open work area of the corrugated building did not have a cover, exposing employees to the hazard of electrical shock.
Recent events (1)
- — Z (S) $0
1910.305 G01 IV A
- Issued
- Jul 31, 2013
- Abate by
- Sep 13, 2013
- Penalty
- Initial $1,200 · Current $1,200
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: On or about July 9th, 2013 and times prior thereto, employer had in use flexible cords in lieu of permanent wiring of the structure in the storage room and saw areas where overhead lights were powered by extension cords. This condition exposed employees to the hazards associated with fire.
Recent events (1)
- — Z (S) $1200
1910.305 G01 IV B
- Issued
- Jul 31, 2013
- Abate by
- Aug 8, 2013
- Penalty
- Initial $2,000 · Current $2,000
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(B): Flexible cords and/or cables were run through holes in walls, ceilings, or floors: On or about July 9th, 2013 and times prior thereto, employer had powered an air compressor by running a flexible cord through a hole in the metal corrugated building wall. This condition exposed employees to the hazard of electrical shock and fire.
Recent events (1)
- — Z (S) $2000
1910.305 J02 II
- Issued
- Jul 31, 2013
- Abate by
- Aug 8, 2013
- Penalty
- Initial $2,000 · Current $2,000
General-duty citation text
29 CFR 1910.305(j)(2)(ii): Receptacles, cord connectors, and attachment plugs were not constructed so that a receptacle or cord connector would not accept an attachment plug with a different voltage or current rating than that for which the device was intended: On or about July 9th, 2013 and times prior thereto, employer had modified a 220 volt plug to accept a 110 volt feed. This configuration exposed employees to the hazards of electrical shock and fire.
Recent events (1)
- — Z (S) $2000
1910.22 A01
- Issued
- Jul 31, 2013
- Abate by
- Aug 22, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.22(a): 29 CFR 1910.22(a)(1): Place(s) of employment were not kept clean and orderly, or in a sanitary condition: On or about July 9th, 2013 and times prior thereto, the area in front of the main breaker panel was clutter with materials and debris, exposing employees to trip and fall hazards.
Recent events (1)
- — Z (O) $0
More inspections at Scott Stewart
View Scott Stewart's full OSHA safety record →
More inspections in this industry (NAICS 321991)
More inspections in AR
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339174906.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.