GLENDALE LUKE AFB, AZ —
OSHA Inspection: LUKE AIR FORCE BASE
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of LUKE AIR FORCE BASE in ENGINE PROPULSION MAINTANENCE AND REPAIR - F-16 FIGHTER AIRCRAFT BLDG 931, GLENDALE LUKE AFB, AZ 85309 (NAICS 928110). OSHA activity number 339228223.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- LUKE AIR FORCE BASE
- Site address
- ENGINE PROPULSION MAINTANENCE AND REPAIR - F-16 FIGHTER AIRCRAFT BLDG 931
- City
- GLENDALE LUKE AFB
- State
- AZ
- ZIP
- 85309
- Mailing
- 14440 W. STARFIGHTER ST., BLDG 918/912, LUKE AFB, AZ 85309
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 928110
- Employees
- 54
- Ownership type
- D
Citations
3 citations on file for this inspection.
1910.304 G05
- Issued
- Sep 26, 2013
- Abate by
- Oct 8, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous and effective. a) Luke Air Force Base, Engine Propulsion Maintanence and Repair: On July 17, 2013, and at times prior thereto, the electrical wall outlet in the Engine Propulsion Maintanence and Repair building's office had a faulty ground exposing workers to accidental electrical shock hazards.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G01 IV A
- Issued
- Sep 26, 2013
- Abate by
- Oct 8, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: a) Luke Air Force Base, Engine Propulsion, Maintenance and Repair: On or about July 17, 2013, flexible cords were used as a substitute for a fixed wiring structures on the jet engine repair stations exposing workers to shock and electrocution hazards.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 F02
- Issued
- Sep 26, 2013
- Abate by
- Oct 8, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: a) Luke Air Force Base, Engine Propulsion Maintanence and Repair: On July 17, 2013, and at times prior thereto, each branch circuit was not marked to indicate its purpose or location. Employees are exposed to electrical and mechanical hazards during emergencies requiring the shut off of circuits and/or equipment.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Luke AIR Force Base
View Luke AIR Force Base's full OSHA safety record →
More inspections in this industry (NAICS 928110)
More inspections in AZ
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339228223.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.