OSHA Inspection: LUKE AIR FORCE BASE

Follow-up inspection · Health discipline

On , OSHA opened a follow-up health inspection of LUKE AIR FORCE BASE in COMPONENT MAINTENACE SQUADRON JET ENGINE SHOP, BLDG 931, LUKE AFB, AZ 85309 (NAICS 488190). OSHA activity number 339897878.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Luke AIR Force Base — free Get an email when a new federal OSHA severe-injury report for Luke AIR Force Base is published. One employer, no account, unsubscribe in one click.
Establishment
LUKE AIR FORCE BASE
Site address
COMPONENT MAINTENACE SQUADRON JET ENGINE SHOP, BLDG 931
City
LUKE AFB
State
AZ
ZIP
85309
Mailing
56TH FIGHTER WING BLDG 461, LUKE AFB, AZ 85309
Inspection type
Follow-up (F)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
488190
Employees
54
Ownership type
D

2 citations on file for this inspection.

1910.303 A

Serious Gravity 1 1 instance 54 exposed
Issued
Dec 1, 2014
Abate by
Dec 24, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.303(a): The conductors and/or equipment required or permitted by this subpart were not approved:  (a) Jet Engine Shop, Bldg 931: On or about August 12, 2014 and at times prior thereto, the 15 foot power-supply cords of the Relocatable Power Taps (RPTs) were replaced with 50 foot cords.  Note: Per the UL White Book (Relocatable Power Taps (XBYS)), "The length of the power-supply cord ........ should not exceed 25 ft (7.62 m) not be less than 1.5 ft (0.46 m).
Recent events (1)
  • — Z (S) $0

1910.303 B02

Serious Gravity 1 2 instances 54 exposed
Issued
Dec 1, 2014
Abate by
Dec 24, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  (a) Jet Engine Shop, Bldg 931: On or about August 12, 2014 and at times prior thereto, Relocatable Power Taps (RPTs) supplied power to "Port-A-Cool" evaporative coolers which are 12.0 amp high draw loads.   Note: Per the UL White Book (Relocatable Power Taps (XBYS)), RPTs are designed for a high concentration of low powered loads.   (b) Jet Engine Shop, Bldg 931: On or about August 12, 2014 and at times prior thereto, Relocatable Power Taps (RPTs) were secured to the legs of jet engine stands.  Note: Per the UL White Book (Relocatable Power Taps (XBYS)), "Relocatable power taps are not intended to be permanently secured to building structures, tables, work benches or similar structures, nor are they intended to be used as a substitute for fixed wiring".
Recent events (1)
  • — Z (S) $0

View Luke AIR Force Base's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339897878.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.