GLENDALE LUKE AFB, AZ —
OSHA Inspection: LUKE AIR FORCE BASE
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of LUKE AIR FORCE BASE in LRS - AF WAREHOUSE OPERATION, GLENDALE LUKE AFB, AZ 85309 (NAICS 928110). OSHA activity number 339228348.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- LUKE AIR FORCE BASE
- Site address
- LRS - AF WAREHOUSE OPERATION
- City
- GLENDALE LUKE AFB
- State
- AZ
- ZIP
- 85309
- Mailing
- 14440 W. STARFIGHTER ST., BLDG 918/912, LUKE AFB, AZ 85309
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 928110
- Employees
- 26
- Ownership type
- D
Citations
4 citations on file for this inspection.
1910.303 G01
- Issued
- Sep 26, 2013
- Abate by
- Oct 8, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment to permit ready and safe operation and maintenance of such equipment: (a) Luke Air Force Base, LRS-AF Warehouse: On or about July 17, 2013 and at times prior thereto, the main electrical switches in the warehouse were blocked by storage units. Sufficient access and working space was not provided and maintained about the electrical switches to permit ready and safe operation and maintenance of such equipment and could result in serious electrical injuries.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.304 G05
- Issued
- Sep 26, 2013
- Abate by
- Oct 8, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous and effective. a) Luke Air Force Base, LRS - AF Warehouse: On July 17, 2013, and at times prior thereto, the electrical wall outlet opposite the main electrical panels in the warehouse building had a false ground. Employees were exposed to electrical hazards and injuries when using the wall plug to power equipment and tools.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1926.602 D
- Issued
- Sep 26, 2013
- Abate by
- Oct 8, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.602(d): The employer did not certify that each operator had been trained and evaluated as required by 1910.178(l) of this chapter: The powered industrial truck operator's performance was not evaluated at least once every three years. a) Luke Air Force Base, LRS-AF Warehouse: On or about July 17, 2013, industrial truck operators did not received an evaluation of operator's performance every three years. Powered industrial truck operators were only trained initially when employed at this facility. Workers are exposed to serious injuries or death from being struck-by or crushed by forklifts at the warehouse.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 F02
- Issued
- Sep 26, 2013
- Abate by
- Oct 8, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: a) Luke Air Force Base, LRS - AF Warehouse.: On July 17, 2013, at times prior thereto, each branch circuit was not marked to indicate its purpose or location. Employees were exposed to electrical and mechanical hazards that require emergency shut-off of electrical circuits.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Luke AIR Force Base
View Luke AIR Force Base's full OSHA safety record →
More inspections in this industry (NAICS 928110)
More inspections in AZ
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339228348.