Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: TOTAL PETROCHEMICALS & REFINING USA, INC

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of TOTAL PETROCHEMICALS & REFINING USA, INC in 105 ONTARIO STREET, STRATFORD, CT 06615 (NAICS 325110). OSHA activity number 339563868.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Total Petrochemicals & Refining USA, INC — free Get an email when a new federal OSHA severe-injury report for Total Petrochemicals & Refining USA, INC is published. One employer, no account, unsubscribe in one click.
Site address
105 ONTARIO STREET
City
STRATFORD
State
CT
ZIP
06615
Mailing
105 ONTARIO STREET, STRATFORD, CT 06615
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
325110
Employees
1600
Ownership type
A

4 citations on file for this inspection.

1910.106 B02 VI B

Serious Gravity 1 3 instances 18 exposed
Issued
Mar 4, 2014
Abate by
May 19, 2014
Penalty
Initial $3,000 · Current $2,000 Reduced
29 CFR 1910.106(b)(2)(vi)(b): Where vent pipe outlets for tanks storing Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), are adjacent to buildings or public ways, they were not located so that the vapors are released at a safe point outside of buildings and not less than 12 feet above the adjacent ground level. In order to aid their dispersion, vapors were not discharged upward or horizontally away from closely adjacent walls. Vent outlets were not located so that flammable vapors were not trapped by eaves or other obstructions and shall be at least five feet from building openings.    Jobsite:  The employer did not ensure that the vent pipes from the heptane tanks 51, 52 & 53 were vented more than 12 feet above the ground and greater than 5 feet from the building entrances/exits.
Recent events (2)
  • — I (S) $2000
  • — Z (S) $3000

1910.120 Q03 III

Other-than-serious 1 instance 1 exposed
Issued
Mar 4, 2014
Abate by
Mar 10, 2014
Penalty
Initial $4,000 · Current $3,500 Reduced
29 CFR 1910.120(q)(3)(iii): Based on the hazardous substances and/or conditions present, the individual in charge of the ICS did not implement appropriate emergency operations and did not ensure that the personal protective equipment worn was appropriate for the hazards encountered:      Facility:  The employer and/or the individual in charge of ICS did neither implement appropriate emergency operations nor ensure through visual observation and/or instruction that the personal protectinve equipment (PPE) worn by the employee engaged in emergency response activities and exposed to heptane which presented a potential inhalation hazard was appropriate type for the hazard encountered.
Recent events (2)
  • — I (O) $3500
  • — Z (S) $4000

1910.120 Q03 IV

Deleted Serious Gravity 5 1 instance 1 exposed
Issued
Mar 4, 2014
Abate by
Mar 10, 2014
Penalty
Initial $4,000 · Current $0 Reduced

Hazardous substances 1371

29 CFR 1910.120(q)(3)(iv): Employees engaged in emergency response and exposed to hazardous substances presenting an inhalation hazard or potential inhalation hazard, did not wear positive-pressure self-contained breathing apparatus until such time that the individual in charge of the incident command system determined through the use of air monitoring that a decreased level of respiratory protection would not result in hazardous exposures to employees:   Facility:  The employees, engaged in emergency response activities and exposed to heptane which presented a potential inhalation hazard were not wearing positive-pressure self-contained breathing apparatus while engaged in emergency response activities.
Recent events (2)
  • — I (S) $0
  • — Z (S) $4000

1910.120 Q06 I

Serious Gravity 5 1 instance 2 exposed
Issued
Mar 4, 2014
Abate by
Mar 12, 2014
Penalty
Initial $4,000 · Current $3,500 Reduced
29 CFR 1910.120(q)(6)(i): First responders at the awareness level did not have sufficient training or have sufficient experience to objectively demonstrate competency in the areas covered by 29 CFR 1910.120(q)(6)(i)(A) through (q)(6)(i)(F):    Facility:  The employees, responded as first responders to the hepane spill in a recovery and clean up mode did not have sufficient training and experience to objectively and safely demonstrate competence in the areas and situations.
Recent events (2)
  • — I (S) $3500
  • — Z (S) $4000