Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: ZAREENA INVESTMENTS INC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of ZAREENA INVESTMENTS INC in 2725 PAT BOOKER RD, UNIVERSAL CITY, TX 78148 (NAICS 812320). OSHA activity number 339575383.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Zareena Investments INC — free Get an email when a new federal OSHA severe-injury report for Zareena Investments INC is published. One employer, no account, unsubscribe in one click.
Site address
2725 PAT BOOKER RD
City
UNIVERSAL CITY
State
TX
ZIP
78148
Mailing
2725 PAT BOOKER RD, UNIVERSAL CITY, TX 78148
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
812320
Employees
25
Ownership type
A

8 citations on file for this inspection.

1910.147 C01

Serious Gravity 5 1 instance 1 exposed
Issued
Jul 17, 2014
Abate by
Aug 6, 2014
Penalty
Initial $2,000 · Current $2,000
29 CFR 1910.147(c)(1): Energy control program. The employer did not establish a program consisting of energy control procedures, employee training and periodic inspections to ensure that before any employee performs any servicing or maintenance on a machine or equipment where the unexpected energizing, startup or release of stored energy could occur and cause injury, the machine or equipment shall be isolated from the energy source and rendered inoperative:    In the boiler room, main Hurst boiler that provides steam for the facility, on or about February 5, 2014 and at times prior thereto, an employee engaged in maintenance on the Hurst boiler (Model: Cyclone, Serial: V86-150-TF21) steam supply lines, was exposed to hazards associated with unexpected release of stored steam.
Recent events (1)
  • — Z (S) $2000

1910.264 C04 III A

Serious Gravity 10 3 instances 13 exposed
Issued
Jul 17, 2014
Abate by
Aug 6, 2014
Penalty
Initial $2,800 · Current $2,800
29 CFR 1910.264(c)(4)(iii)(a): All steam pipes that are within 7 feet of the floor or working platform, and with which the worker may come into contact, were not insulated or covered with a heat-resistive material or otherwise properly guarded:     On or about on or about February 5, 2014, and at times prior thereto, employees were exposed to burn hazards from steam pipes that were not insulated or properly guarded:     (a) Garment touch-up station, touch-up press machine (make and model not found): while using the press machine; which had inadequate insulation on the steam pipes.     (b) Steam pipes routed along the Northeast wall, main production area: while walking alongside the wall next to the steam pipes that had inadequate insulation.     (c) Boiler room, West wall: while conducting routine maintenance on the reservoir tank (make model not found) that does not have any insulation on the supply lines of the tank.
Recent events (1)
  • — Z (S) $2800

1910.264 D02 I A

Serious Gravity 5 1 instance 1 exposed
Issued
Jul 17, 2014
Abate by
Aug 6, 2014
Penalty
Initial $2,000 · Current $2,000
29 CFR 1910.264(d)(2)(i)(a): No safeguard, safety appliance, or device attached to, or forming an integral part of any machinery shall be removed or made ineffective except for the purpose of making immediate repairs or adjustments. Any such safeguard, safety appliance, or device removed or made ineffective during the repair or adjustment of such machinery was not replaced immediately upon the completion of such repairs or adjustments:     In the garment washing station, on the south wall, on or about February 5, 2014 and at times prior thereto, employees were exposed to an amputation hazard while loading and operating the IPSO Washer (Model: IPH60MP21121NRNUSA, Serial: 008265) without the guard in place.
Recent events (1)
  • — Z (S) $2000

1910.303 G02 I

Serious Gravity 10 3 instances 2 exposed
Issued
Jul 17, 2014
Abate by
Aug 6, 2014
Penalty
Initial $2,800 · Current $2,800
29 CFR 1910.303(g)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by approved cabinets or other forms of approved enclosures, or other means listed under this provision:      On or about on or about February 5, 2014, and at times prior thereto, employees were exposed to open cabinets with live electrical parts:     (a) In the garment washing station, on the south wall: while using the IPSO Washer (Model: IPH60MP21121NRNUSA, Serial: 008265, 200-240 volts, 7.1 amps); which had missing covers; exposing electrical parts.     (b) Compressor room, Northeast corner: while turning on/off the Ingersoll-Rand compressor (Model:2545E10V, Serial:902846, 230 volts) that has a missing cover; exposing electrical parts.     (c) Boiler room, middle of the boiler room: while pushing the reset button on the Hurst boiler (Model: Cyclone, Serial: V86-150-TF21, 12 volts) that has a missing cover; exposing electrical parts.
Recent events (1)
  • — Z (S) $2800

1910.305 B01 I

Serious Gravity 10 1 instance 13 exposed
Issued
Jul 17, 2014
Abate by
Aug 6, 2014
Penalty
Initial $2,800 · Current $2,800
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings were not protected from abrasion, and openings through which conductors enter shall be effectively closed:   In the main production area, electrical conduit routed along the Northeast wall, on or about February 5, 2014 and at times prior thereto, employees walking in the main production area; were exposed to 120 volt electrical conductors that were not properly installed in the LB electrical fitting.
Recent events (1)
  • — Z (S) $2800

1910.305 B01 II

Serious Gravity 10 2 instances 2 exposed
Issued
Jul 17, 2014
Abate by
Aug 6, 2014
Penalty
Initial $2,800 · Current $2,800
29 CFR 1910.305(b)(1)(ii): Unused openings in cabinets, boxes, and fittings were not effectively closed:     On or about on or about February 5, 2014, and at times prior thereto, employees were exposed to live electrical parts from unused openings in breaker panels:     (a) In the main office, on the East wall: while turning on the facility lights using a breaker in panel A, that had 7 missing covers.     (b) In the main office, on the East wall: while turning on the facility lights using a breaker in panel B, which had 17 missing covers.
Recent events (1)
  • — Z (S) $2800

1910.305 B02 I

Serious Gravity 10 3 instances 13 exposed
Issued
Jul 17, 2014
Abate by
Aug 6, 2014
Penalty
Initial $2,800 · Current $2,800
29 CFR 1910.305(b)(2)(i): All pull boxes, junction boxes, and fittings shall be provided with covers identified for the purpose. If metal covers are used, they shall be grounded. In completed installations, each outlet box did not have a cover, faceplate, or fixture canopy. Covers of outlet boxes having holes through which flexible cord pendants pass shall be provided with bushings designed for the purpose or shall have smooth, well-rounded surfaces on which the cords may bear:     On or about on or about February 5, 2014, and at times prior thereto, employees were exposed to open junction boxes with live electrical conductors:     (a) In the main production area, on the Southeast wall: while turning on a light switch that had a broken cover; exposing electrical conductors.     (b) Compressor room, Northeast corner wall: while turning on/off the Ingersoll-Rand compressor (Model:2545E10V, Serial:902846) that has a missing cover on the electrical supply junction box; exposing electrical conductors.     (c) In the main production area, Unipress machine: while using the Unipress machine (Model: STF, Serial: 0575509) that has a bent metal cover on the supply junction box; exposing electrical conductors.
Recent events (1)
  • — Z (S) $2800

1910.305 G02 III

Serious Gravity 10 1 instance 2 exposed
Issued
Jul 17, 2014
Abate by
Aug 6, 2014
Penalty
Initial $2,800 · Current $2,800
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief is provided that will prevent pull from being directly transmitted to joints or terminal screws:     In the garment washing station, on the south wall, on or about February 5, 2014 and at times prior thereto, employees were exposed to an electrical hazard while loading and operating the IPSO Washer (Model: IPH60MP21121NRNUSA, Serial: 008265) that did not have strain relief on the 200-240V flexible power feed cord.
Recent events (1)
  • — Z (S) $2800

View Zareena Investments INC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339575383.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.