Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: ZAREENA INVESTMENTS INC

Follow-up inspection · Safety discipline

On , OSHA opened a follow-up safety inspection of ZAREENA INVESTMENTS INC in 2725 PAT BOOKER RD, UNIVERSAL CITY, TX 78148 (NAICS 812320). OSHA activity number 340379874.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Zareena Investments INC — free Get an email when a new federal OSHA severe-injury report for Zareena Investments INC is published. One employer, no account, unsubscribe in one click.
Site address
2725 PAT BOOKER RD
City
UNIVERSAL CITY
State
TX
ZIP
78148
Mailing
2725 PAT BOOKER RD, UNIVERSAL CITY, TX 78148
Inspection type
Follow-up (F)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
812320
Employees
25
Ownership type
A

6 citations on file for this inspection.

1910.305 A02 II

Serious Gravity 10 1 instance 4 exposed
Issued
Jul 22, 2015
Abate by
Aug 1, 2015
Penalty
Initial $3,080 · Current $1,232 Reduced
29 CFR 1910.305(a)(2)(ii): Temporary wiring shall be removed immediately upon completion of the project or purpose for which the wiring was installed:    Clothes pick up/drop off area: On or about January 23, 2015 and at times prior thereto, employees were exposed to shock hazards of 120 volts when coming in contact with metal clothes racks that had an extension cord running through the metal tubing.
Recent events (2)
  • — I (S) $1232
  • — Z (S) $3080

1910.305 G01 III

Serious Gravity 10 1 instance 4 exposed
Issued
Jul 22, 2015
Abate by
Aug 1, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iii): If used as permitted in paragraphs (g)(1)(ii)(C), (g)(1)(ii)(G), or (g)(1)(ii)(I) of this section, the flexible cord was not energized from an approved receptacle outlet:  Clothes pick up/drop off area: On or about January 23, 2015 and at times prior thereto, employees were exposed to shock hazards of 120 volts of electricity when coming in contact with metal clothes racks that had an extension cord, which was plugged into a surge protector, running through the metal tubing.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.264 C04 III A

Repeat Gravity 10 3 instances 14 exposed
Issued
Jul 22, 2015
Abate by
Aug 11, 2015
Penalty
Initial $6,160 · Current $2,464 Reduced
29 CFR 1910.264(c)(4)(iii)(a): All steam pipes that are within 7 feet of the floor or working platform, and with which the worker may come into contact, were not insulated or covered with a heat-resistive material or otherwise properly guarded:       On or about January 23, 2015, and at times prior thereto, employees were exposed to burn hazards from steam pipes that were not insulated or properly guarded:       (a) Garment touch-up station, touch-up press machine (make and model not found): while using the press machine; which had inadequate insulation on the steam pipes that measured 262.8 degrees Fahrenheit.         (b)  Main production area, Unipress machine (make and model not found):  while walking alongside the Unipress machine; which had inadequate insulation on the steam pipes that measured 239.8 degrees Fahrenheit.     (c) Boiler room, West wall:  while conducting routine maintenance on the reservoir tank (make and model not found) that does not have any insulation on the supply lines of the tank that measured 208.0 degrees Fahrenheit.     Zareena Investments Inc, was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.264(c)(4)(iii)(a), which was contained in OSHA inspection number 957538, citation number 1, item number 2 and was affirmed as a final order on August 11, 2014, with respect to a workplace located at 2725 Pat Booker Rd, Universal City, TX 78148.
Recent events (2)
  • — I (R) $2464
  • — Z (R) $6160

1910.303 G02 I

Repeat Gravity 10 3 instances 2 exposed
Issued
Jul 22, 2015
Abate by
Aug 11, 2015
Penalty
Initial $6,160 · Current $2,464 Reduced
29 CFR 1910.303(g)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by approved cabinets or other forms of approved enclosures, or other means listed under this provision:        On or about January 23, 2015, and at times prior thereto, employees were exposed to 230 volts of electrical current from open cabinets with live electrical parts:         (a) Compressor room, Northeast corner: while turning on/off the Ingersoll-Rand compressor (Model:2545E10V, Serial:902846, 230 volts) that has a missing cover; exposing electrical parts.       (b) Boiler room, middle of the boiler room: while pushing the reset button on the Hurst boiler (Model: Cyclone, Serial: V86-150-TF21, 12 volts) that has a missing cover; exposing electrical parts.    Zareena Investments Inc, was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.303(g)(2)(i), which was contained in OSHA inspection number 957538, citation number 1, item number 4 and was affirmed as a final order on August 11, 2014, with respect to a workplace located at 2725 Pat Booker Rd, Universal City, TX 78148.
Recent events (2)
  • — I (R) $2464
  • — Z (R) $6160

1910.305 B01 I

Repeat Gravity 10 1 instance 14 exposed
Issued
Jul 22, 2015
Abate by
Aug 11, 2015
Penalty
Initial $6,160 · Current $2,464 Reduced
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings were not protected from abrasion, and openings through which conductors enter shall be effectively closed:     In the main production area, electrical conduit routed along the Northeast wall, on or about January 23, 2015 and at times prior thereto, employees walking in the main production area, were exposed to 120 volt electrical conductors that were not properly installed in the LB electrical fitting.    Zareena Investments Inc, was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.305(b)(1)(i), which was contained in OSHA inspection number 957538, citation number 1, item number 5 and was affirmed as a final order on August 11, 2014, with respect to a workplace located at 2725 Pat Booker Rd, Universal City, TX 78148.
Recent events (2)
  • — I (R) $2464
  • — Z (R) $6160

1910.305 B02 I

Repeat Gravity 10 3 instances 14 exposed
Issued
Jul 22, 2015
Abate by
Aug 11, 2015
Penalty
Initial $6,160 · Current $2,464 Reduced
29 CFR 1910.305(b)(2)(i): All pull boxes, junction boxes, and fittings shall be provided with covers identified for the purpose. If metal covers are used, they shall be grounded. In completed installations, each outlet box did not have a cover, faceplate, or fixture canopy. Covers of outlet boxes having holes through which flexible cord pendants pass shall be provided with bushings designed for the purpose or shall have smooth, well-rounded surfaces on which the cords may bear:       On or about January 23, 2015, and at times prior thereto, employees were exposed to 120 volts of electrical current from open junction boxes with live electrical conductors:       (a) In the main production area, on the Southeast wall: while turning on a light switch that had a broken cover; exposing electrical conductors.       (b) Compressor room, Northeast corner wall: while turning on/off the Ingersoll-Rand compressor (Model:2545E10V, Serial:902846) that has a missing cover on the electrical supply junction box; exposing electrical conductors.       (c) In the main production area, Unipress machine: while using the Unipress machine (Model: STF, Serial: 0575509) that has a bent metal cover on the supply junction box; exposing electrical conductors.    Zareena Investments Inc, was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.305(b)(2)(i), which was contained in OSHA inspection number 957538, citation number 1, item number 7 and was affirmed as a final order on August 11, 2014, with respect to a workplace located at 2725 Pat Booker Rd, Universal City, TX 78148.
Recent events (2)
  • — I (R) $2464
  • — Z (R) $6160

View Zareena Investments INC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340379874.