UNIVERSAL CITY, TX —
OSHA Inspection: ZAREENA INVESTMENTS INC
Follow-up inspection · Safety discipline
At a glance
On , OSHA opened a follow-up safety inspection of ZAREENA INVESTMENTS INC in 2725 PAT BOOKER RD, UNIVERSAL CITY, TX 78148 (NAICS 812320). OSHA activity number 340379874.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ZAREENA INVESTMENTS INC
- Site address
- 2725 PAT BOOKER RD
- City
- UNIVERSAL CITY
- State
- TX
- ZIP
- 78148
- Mailing
- 2725 PAT BOOKER RD, UNIVERSAL CITY, TX 78148
What kind of inspection was it?
- Inspection type
- Follow-up (F)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 812320
- Employees
- 25
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.305 A02 II
- Issued
- Jul 22, 2015
- Abate by
- Aug 1, 2015
- Penalty
- Initial $3,080 · Current $1,232 Reduced
General-duty citation text
29 CFR 1910.305(a)(2)(ii): Temporary wiring shall be removed immediately upon completion of the project or purpose for which the wiring was installed: Clothes pick up/drop off area: On or about January 23, 2015 and at times prior thereto, employees were exposed to shock hazards of 120 volts when coming in contact with metal clothes racks that had an extension cord running through the metal tubing.
Recent events (2)
- — I (S) $1232
- — Z (S) $3080
1910.305 G01 III
- Issued
- Jul 22, 2015
- Abate by
- Aug 1, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iii): If used as permitted in paragraphs (g)(1)(ii)(C), (g)(1)(ii)(G), or (g)(1)(ii)(I) of this section, the flexible cord was not energized from an approved receptacle outlet: Clothes pick up/drop off area: On or about January 23, 2015 and at times prior thereto, employees were exposed to shock hazards of 120 volts of electricity when coming in contact with metal clothes racks that had an extension cord, which was plugged into a surge protector, running through the metal tubing.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.264 C04 III A
- Issued
- Jul 22, 2015
- Abate by
- Aug 11, 2015
- Penalty
- Initial $6,160 · Current $2,464 Reduced
General-duty citation text
29 CFR 1910.264(c)(4)(iii)(a): All steam pipes that are within 7 feet of the floor or working platform, and with which the worker may come into contact, were not insulated or covered with a heat-resistive material or otherwise properly guarded: On or about January 23, 2015, and at times prior thereto, employees were exposed to burn hazards from steam pipes that were not insulated or properly guarded: (a) Garment touch-up station, touch-up press machine (make and model not found): while using the press machine; which had inadequate insulation on the steam pipes that measured 262.8 degrees Fahrenheit. (b) Main production area, Unipress machine (make and model not found): while walking alongside the Unipress machine; which had inadequate insulation on the steam pipes that measured 239.8 degrees Fahrenheit. (c) Boiler room, West wall: while conducting routine maintenance on the reservoir tank (make and model not found) that does not have any insulation on the supply lines of the tank that measured 208.0 degrees Fahrenheit. Zareena Investments Inc, was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.264(c)(4)(iii)(a), which was contained in OSHA inspection number 957538, citation number 1, item number 2 and was affirmed as a final order on August 11, 2014, with respect to a workplace located at 2725 Pat Booker Rd, Universal City, TX 78148.
Recent events (2)
- — I (R) $2464
- — Z (R) $6160
1910.303 G02 I
- Issued
- Jul 22, 2015
- Abate by
- Aug 11, 2015
- Penalty
- Initial $6,160 · Current $2,464 Reduced
General-duty citation text
29 CFR 1910.303(g)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by approved cabinets or other forms of approved enclosures, or other means listed under this provision: On or about January 23, 2015, and at times prior thereto, employees were exposed to 230 volts of electrical current from open cabinets with live electrical parts: (a) Compressor room, Northeast corner: while turning on/off the Ingersoll-Rand compressor (Model:2545E10V, Serial:902846, 230 volts) that has a missing cover; exposing electrical parts. (b) Boiler room, middle of the boiler room: while pushing the reset button on the Hurst boiler (Model: Cyclone, Serial: V86-150-TF21, 12 volts) that has a missing cover; exposing electrical parts. Zareena Investments Inc, was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.303(g)(2)(i), which was contained in OSHA inspection number 957538, citation number 1, item number 4 and was affirmed as a final order on August 11, 2014, with respect to a workplace located at 2725 Pat Booker Rd, Universal City, TX 78148.
Recent events (2)
- — I (R) $2464
- — Z (R) $6160
1910.305 B01 I
- Issued
- Jul 22, 2015
- Abate by
- Aug 11, 2015
- Penalty
- Initial $6,160 · Current $2,464 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings were not protected from abrasion, and openings through which conductors enter shall be effectively closed: In the main production area, electrical conduit routed along the Northeast wall, on or about January 23, 2015 and at times prior thereto, employees walking in the main production area, were exposed to 120 volt electrical conductors that were not properly installed in the LB electrical fitting. Zareena Investments Inc, was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.305(b)(1)(i), which was contained in OSHA inspection number 957538, citation number 1, item number 5 and was affirmed as a final order on August 11, 2014, with respect to a workplace located at 2725 Pat Booker Rd, Universal City, TX 78148.
Recent events (2)
- — I (R) $2464
- — Z (R) $6160
1910.305 B02 I
- Issued
- Jul 22, 2015
- Abate by
- Aug 11, 2015
- Penalty
- Initial $6,160 · Current $2,464 Reduced
General-duty citation text
29 CFR 1910.305(b)(2)(i): All pull boxes, junction boxes, and fittings shall be provided with covers identified for the purpose. If metal covers are used, they shall be grounded. In completed installations, each outlet box did not have a cover, faceplate, or fixture canopy. Covers of outlet boxes having holes through which flexible cord pendants pass shall be provided with bushings designed for the purpose or shall have smooth, well-rounded surfaces on which the cords may bear: On or about January 23, 2015, and at times prior thereto, employees were exposed to 120 volts of electrical current from open junction boxes with live electrical conductors: (a) In the main production area, on the Southeast wall: while turning on a light switch that had a broken cover; exposing electrical conductors. (b) Compressor room, Northeast corner wall: while turning on/off the Ingersoll-Rand compressor (Model:2545E10V, Serial:902846) that has a missing cover on the electrical supply junction box; exposing electrical conductors. (c) In the main production area, Unipress machine: while using the Unipress machine (Model: STF, Serial: 0575509) that has a bent metal cover on the supply junction box; exposing electrical conductors. Zareena Investments Inc, was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.305(b)(2)(i), which was contained in OSHA inspection number 957538, citation number 1, item number 7 and was affirmed as a final order on August 11, 2014, with respect to a workplace located at 2725 Pat Booker Rd, Universal City, TX 78148.
Recent events (2)
- — I (R) $2464
- — Z (R) $6160
More inspections at Zareena Investments INC
View Zareena Investments INC's full OSHA safety record →
More inspections in this industry (NAICS 812320)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340379874.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.