OSHA Inspection: CLOVERLEAF COLD STORAGE COMPANY

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of CLOVERLEAF COLD STORAGE COMPANY in 1165 INDUSTRIAL DRIVE, NAPOLEON, OH 43545 (NAICS 493110). OSHA activity number 339593212.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Cloverleaf Cold Storage Company — free Get an email when a new federal OSHA severe-injury report for Cloverleaf Cold Storage Company is published. One employer, no account, unsubscribe in one click.
Site address
1165 INDUSTRIAL DRIVE
City
NAPOLEON
State
OH
ZIP
43545
Mailing
1165 INDUSTRIAL DRIVE, NAPOLEON, OH 43545
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
493110
Employees
15
Ownership type
A

3 citations on file for this inspection.

1910.119 D03 I B

Serious Gravity 10 15 instances 15 exposed
Issued
Jul 23, 2014
Abate by
Sep 15, 2014
Penalty
Initial $7,000 · Current $3,850 Reduced

Hazardous substances 0170

29 CFR 1910.119(d)(3)(i)(B): The employer's piping and instrument diagrams were not accurate and did not represent equipment that was existing and was part of the process:    Cloverleaf Cold Storage Company, Napoleon, Ohio:  As of and prior to February 20, 2014, the employer did not ensure that their P&IDs were up-to-date and accurate.  Inaccuracies included but were not limited to:      a) The relief vent for relief header RV-638, P&ID 7W5-612, was not included on the diagram.      b) The relief vent for relief header RV-646, P&ID 7W5-612, was not included on the diagram.      c)  Piping system, RV-610 is no longer connected to RV-609 on P&ID 7W5-171.      d)  The pressure relief valve protecting vessel SD-302, P&ID 7W5 VB-320, was indicated as being a single relief valve but a dual relief valve was installed on the vessel.      e)  The pressure relief valve protecting vessel SD-303, P&ID 7W5 VB-321, was indicated as being a single relief valve but a dual relief valve was installed on the vessel.      f)  The pressure relief valve protecting vessel SD-304, P&ID 7W5 VB-322, was indicated as being a single relief valve but a dual relief valve was installed on the vessel.      g)  The pressure relief valve protecting vessel SD-305, P&ID 7W5 VB-323, was indicated as being a single relief valve but a dual relief valve was installed on the vessel.      h)  The pressure relief valve protecting vessel SD-306, P&ID 7W5 VB-324, was indicated as being a single relief valve but a dual relief valve was installed on the vessel.      i)  The pressure relief valve protecting vessel SD-307, P&ID 7W5 VB-325, was indicated as being a single relief valve but a dual relief valve was installed on the vessel.      j)  The pressure relief valve protecting vessel SD-308, P&ID 7W5 VB-326, was indicated as being a single relief valve but a dual relief valve was installed on the vessel.      k)  The pressure relief valve protecting vessel SD-309, P&ID 7W5 VB-327, was indicated as being a single relief valve but a dual relief valve was installed on the vessel.      l)  The pressure relief valve protecting vessel SD-310, P&ID 7W5 VB-328, was indicated as being a single relief valve but a dual relief valve was installed on the vessel.   m)  The pressure relief valve protecting vessel SD-311, P&ID 7W5 VB-329, was indicated as being a single relief valve but a dual relief valve was installed on the vessel.      n)  The pressure relief valve protecting vessel SD-3012, P&ID 7W5 VB-330, was indicated as being a single relief valve but a dual relief valve was installed on the vessel.      o)  The pressure relief valve protecting vessel SD-313, P&ID 7W5 VB-331, was indicated as being a single relief valve but a dual relief valve was installed on the vessel.      q)  The P&IDs did not reflect that twenty-two manual valves were capped or plugged to prevent ammonia release.  The valves included but were not limited to, valves L6, L7, and L8 on P&ID 7W5-1010, valves G9 and G10 on P&ID 7W5-855, and valves D1 on each of the evaporators.
Recent events (2)
  • — I (S) $3850
  • — Z (S) $7000

1910.119 F01 I A

Serious Gravity 10 12 instances 15 exposed
Issued
Jul 23, 2014
Abate by
Sep 15, 2014
Penalty
Initial $7,000 · Current $3,850 Reduced

Hazardous substances 0170

29 CFR 1910.119(f)(1)(i)(A):   The employer did not develop and implement written operating procedures that provided clear instructions for safely conducting activities involved in each covered process consistent with the process safety information for and did not address at least the following element: initial startup.    Cloverleaf Cold Storage Company, Napoleon, Ohio:  As of and prior to February 20, 2014, the employer did not develop and implement written operating procedures for normal operations that provide clear instructions for operating the ammonia refrigeration system including but not limited to:      a)  The procedure, SOP-LT-510, for operation of LT-510 ammonia compressor did not provide specific information on which valves to open and which valves to close when pumping out the compressor.      b)  The procedure, SOP-LT-511, for operation of LT-511 ammonia compressor did not provide specific information on which valves to open and which valves to close when pumping out the compressor.      c)  The procedure, SOP-LT-512, for operation of LT-512 ammonia compressor did not provide specific information on which valves to open and which valves to close when pumping out the compressor.      d)  The procedure, SOP-HT-610, for operation of HT-610 ammonia compressor did not provide specific information on which valves to open and which valves to close when pumping out the compressor.      e)  The procedure, SOP-HT-611, for operation of HT-611 ammonia compressor did not provide specific information on which valves to open and which valves to close when pumping out the compressor.      f)  The procedure, SOP-HT-612, for operation of HT-612 ammonia compressor did not provide specific information on which valves to open and which valves to close when pumping out the compressor.      g)  The procedure, SOP-HT-613, for operation of HT-613 ammonia compressor did not provide specific information on which valves to open and which valves to close when pumping out the compressor.      h)  The procedure, SOP-7W5-500, for operation of ammonia liquid accumulator, 7W5-500, and pumps, did not provide specific information on which valves to open and which valves to close during startup.      i)  The procedure, SOP-HE-920, for operation of ammonia heat exchanger, HE-920, did not provide specific information on which valves to open and which valves to close during startup.      j)  The procedure, SOP-HE-1010, for operation of ammonia heat exchanger, HE-1010, did not provide specific information on which valves to open and which valves to close during startup.      k)  The procedure, SOP-LT-511, for operation of LT-511 ammonia compressor incorrectly directs the person to ensure that valve L3 is closed.  There is no valve on compressor LT-511 designated as L3.      l)  The procedure, SOP-HT-611, for operation of HT-611 ammonia compressor incorrectly directs the person to open pump out valve G2.  There is no valve on compressor HT-611 designated as G2.      m)  The procedure, SOP-HE-920, for operation of ammonia heat exchanger, HE-920 on P&ID 7W5-920, incorrectly directs the person to open valve L5.  There is no valve on HE-920 designated as L5.
Recent events (2)
  • — I (S) $3850
  • — Z (S) $7000

1910.119 L01

Other-than-serious 1 instance 15 exposed
Issued
Jul 23, 2014
Abate by
Sep 15, 2014
Penalty
Initial $0 · Current $0

Hazardous substances 0170

29 CFR 1910.119(l)(1): The employer did not implement procedures to manage changes to process chemicals, technology, equipment, and procedures, and changes to facilities that affect a covered process:     Cloverleaf Cold Storage Company, Napoleon, Ohio:  As of and prior to May 20, 2014, the employer did not ensure that the management of change procedure was implemented for changes made to the ammonia system.  Changes that were made to the system include, but were not limited to:        a)  The emergency stop controls located inside the building near the mechanical room (engine room) were removed.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0