PECOS, TX —
OSHA Inspection: PEAK OILFIELD SERVICES
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of PEAK OILFIELD SERVICES in 20.6 MILES SOUTHEAST OF PECOS, TX., PECOS, TX 79772 (NAICS 213112). OSHA activity number 339606972.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- PEAK OILFIELD SERVICES
- Site address
- 20.6 MILES SOUTHEAST OF PECOS, TX.
- City
- PECOS
- State
- TX
- ZIP
- 79772
- Mailing
- 2911 S. COUNTY RD., 1260, MIDLAND, TX 79706
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 213112
- Employees
- 4500
- Ownership type
- A
Citations
8 citations on file for this inspection.
1910.304 G05
- Issued
- Aug 13, 2014
- Abate by
- Sep 2, 2014
- Penalty
- Initial $3,740 · Current $3,740
General-duty citation text
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective: On or about February 26, 2014 and at times prior thereto, employees were working on a rig site, Bison Rig #80. The directional driller's trailer and a Magnum 100 electrical generator were not grounded properly. This exposed employees to electrical hazards.
Recent events (1)
- — Z (S) $3740
1910.305 D02
- Issued
- Aug 13, 2014
- Abate by
- Sep 2, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(d)(2): Panelboards were not mounted in cabinets, cutout boxes, or enclosures designed for the purpose and/or were not dead front: On or about February 26, 2014 and at times prior thereto, employees were working on a rig site, Bison Rig #80. The panel board on the trailer that was housing the directional drillers had no dead front. This condition exposed employees to electrical hazards.
Recent events (1)
- — Z (S) $0
1910.305 G01 IV C
- Issued
- Aug 13, 2014
- Abate by
- Sep 2, 2014
- Penalty
- Initial $3,740 · Current $3,740
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(C): Flexible cords and cables were used where run through doorways, windows, or similar openings: On or about February 26, 2014 and at times prior thereto, employees were working on a rig site, Bison Rig #80. The septic pump power cord was pinched between the wall of the containment and its wooden cover. This exposed employees to electrical shock hazards.
Recent events (1)
- — Z (S) $3740
1910.305 G02 III
- Issued
- Aug 13, 2014
- Abate by
- Sep 2, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws: On or about February 26, 2014 and at times prior thereto, employees were working on a rig site, Bison Rig #80. The circuit breaker panel box on the toilet facility trailer #870040 had the strain relief broken on the cable. This condition exposed employees to electrical shock hazards.
Recent events (1)
- — Z (S) $0
1910.303 B02
- Issued
- Aug 13, 2014
- Abate by
- Sep 2, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: On or about February 26, 2014 and at times prior thereto, employees were working on a rig site, Bison Rig #80. Behind the trailers, there were 4 yellow 50 foot 12 AWG extension cords and 1 blue 50 foot 12 AWG extension cord connected together. This exposed employees to electrical shock hazards.
Recent events (1)
- — Z (O) $0
1910.305 B02 I
- Issued
- Aug 13, 2014
- Abate by
- Sep 2, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose: On or about February 26, 2014 and at times prior thereto, employees were working on a rig site, Bison Rig #80. The circuit breaker panel box on the trailer that housed the directional drillers was missing a cover. This exposed employees to electrical shock hazards.
Recent events (1)
- — Z (O) $0
1910.305 G02 II
- Issued
- Aug 13, 2014
- Abate by
- Sep 2, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(ii): Flexible cords were not used in continuous lengths without splice or tap: On or about February 26, 2014 and at times prior thereto, employees were working on a rig site, Bison Rig #80. Trailer # 960673 which housed the directional drillers had a black 4-AWG cable which had insulation damage. This exposed employees to electrical shock hazards.
Recent events (1)
- — Z (O) $0
1910.334 A01
- Issued
- Aug 13, 2014
- Abate by
- Sep 2, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.334(a)(1): Flexible electric cords were fastened with staples or otherwise hung in such a fashion as could damage the outer jacket or insulation: On or about February 26, 2014 and at times prior thereto, employees were working on a rig site, Bison Rig #80. The company man trailer #960752 had a yellow 50 foot extension cord underneath the trailer which was being held up by poultry netting, this did not ensure it from being damaged. This condition exposed employees to potential electrical hazards.
Recent events (1)
- — Z (O) $0
More inspections at Peak Oilfield Services
View Peak Oilfield Services's full OSHA safety record →
More inspections in this industry (NAICS 213112)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339606972.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.