Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: PEAK OILFIELD SERVICES

Unprogrammed Other inspection · Safety discipline

On , OSHA opened an unprogrammed Other safety inspection of PEAK OILFIELD SERVICES in MABEE FOUNDATION "D" 6.5 MILES NE DIRECTION FROM MIDLAND; SENDERO RIG # 6, MIDLAND, TX 79702 (NAICS 213112). OSHA activity number 339635302.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Peak Oilfield Services — free Get an email when a new federal OSHA severe-injury report for Peak Oilfield Services is published. One employer, no account, unsubscribe in one click.
Site address
MABEE FOUNDATION "D" 6.5 MILES NE DIRECTION FROM MIDLAND; SENDERO RIG # 6
City
MIDLAND
State
TX
ZIP
79702
Mailing
1502 10TH ST. PO BOX548, BRIDGEPORT, TX 76426
Inspection type
Unprogrammed Other (I)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
213112
Employees
4
Ownership type
A

2 citations on file for this inspection.

1910.304 G05

Serious Gravity 5 3 instances 2 exposed
Issued
Aug 21, 2014
Abate by
Sep 3, 2014
Penalty
Initial $4,000 · Current $4,000
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective.  On or about March 10, 2014, and at times prior thereto, the path to ground on the Peak Oilfield Services trailer no. 22999 that was at setup at Mabee Foundation "D"  6.5 miles NE from Midland servicing Sendero Rig No. 6 was not effective.  This condition exposed employees to electrical hazards.
Recent events (1)
  • — Z (S) $4000

1910.305 G02 III

Serious Gravity 5 1 instance 2 exposed
Issued
Aug 21, 2014
Abate by
Sep 3, 2014
Penalty
Initial $5,000 · Current $5,000
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws.   On or about March 10, 2014, and at times prior thereto, a Peak Oil Services mobile home trailer no. 22999 was installed using an multi-conductor 120/240 VAC electrical power lines that was brought into the trailer's "J Box" without the use of a proper strain relief device that will prevent electrical wires from being pulled from terminal connectors.  This condition exposed employees to electrical hazards.