KENT, WA —
OSHA Inspection: BONNEVILLE POWER ADMINISTRATION-COVINGTON DISTRICT
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of BONNEVILLE POWER ADMINISTRATION-COVINGTON DISTRICT in 28401 COVINGTON WAY SE, KENT, WA 98042 (NAICS 221121). OSHA activity number 339663015.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- BONNEVILLE POWER ADMINISTRATION-COVINGTON DISTRICT
- Site address
- 28401 COVINGTON WAY SE
- City
- KENT
- State
- WA
- ZIP
- 98042
- Mailing
- 28401 COVINGTON WAY SE, KENT, WA 98042
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 221121
- Employees
- 35
- Ownership type
- D
Citations
9 citations on file for this inspection.
1910.23 E02
- Issued
- Apr 15, 2014
- Abate by
- May 18, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.23(e)(2): Stair rails did not consist of a top rail, intermediate rail and/or posts, with the vertical height not more than 34 inches (86.36 cm) nor less than 30 inches (76.2 cm) from upper surface of top rail to surface of tread in line with face of riser at forward edge of tread: a) Untanking Tower, Electricians bull room; The staircase to the overhead storage area was missing a midrail or additional posts.
Recent events (1)
- — Z (S) $0
1910.213 B03
- Issued
- Apr 15, 2014
- Abate by
- May 18, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.213(b)(3): Provisions were not made to prevent woodworking machine(s) from automatically restarting upon restoration of power after power failure: a) FMW Shop in Warehouse; A Central Machinery table saw (model no. 45804) did not have an anti-restart device to prevent the saw from automatically restarting if there were a power loss and subsequent restoration of power.
Recent events (1)
- — Z (S) $0
1910.303 G02 II
- Issued
- Apr 15, 2014
- Abate by
- May 18, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(2)(ii): In locations where electric equipment was likely to be exposed to physical damage, enclosures or guards were not so arranged and of such strength as to prevent such damage: a) HMEM Car Port/Outside Covered Storage Area; An extension cord in use was underneath a pallet and a vehicle tire, which crushed the cord.
Recent events (1)
- — Z (S) $0
1910.1001 J04 IV
- Issued
- Apr 15, 2014
- Abate by
- May 18, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.1001(j)(4)(iv): 1910.1001(j)(v): Signs identifying the presence, location and work practices to not disturb the ACM and/or PACM contained within the area were not posted at the entrance where employees were reasonably expected to enter. a) Control House; Communications Rooms A&B the 9x9 floor tiles contain asbestos and three were no caution signs indicating the tiles contained asbestos.
Recent events (1)
- — Z (S) $0
1910.37 A03
- Issued
- Apr 15, 2014
- Abate by
- May 18, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed: a) PSC Storage Area in Warehouse; A wooden beam, cart and plastic storage container were stored in front of a marked exit discharge door. Bonneville Power Administration was previously cited for a violation of this standard which was contained in OSHA inspection no. 900028 citation 2, item 1, issued on April 26, 2013 with respect to a workplace at Keizer, Oregon.
Recent events (1)
- — Z (R) $0
1910.303 B02
- Issued
- Apr 15, 2014
- Abate by
- May 18, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: (a) Warehouse/ TLM, Realty Office; A refrigerator, Proctor Silex toaster, Hamilton Beach kettle and Black and Decker coffee pot were plugged into a relocatable power tap (RPT). The UL listing states that relocatable power taps are designed for low amperage computer and audiovisual types of equipment, and not appliances. This exposes employees to possible electrical fire hazards. (b) Warehouse/ TLM, Realty Office, cubicle by break area; A black RPT was plugged inot a white RPT which powered computer equipment. The UL listing states that relocatable power taps are designed to be plugged into an outlet, and not daisy chained and plugged into other relocatable power taps or extension cords. This exposes employees to possible electrical fire hazards. (c) District Office cubicle: A Holmes heater was plugged into a black RPT. The UL listing states that relocatable power taps are designed for low amperage computer and audiovisual types of equipment, and not appliances. This exposes employees to possible electrical fire hazards. (d) Untanking Tower, Submaintenance computer area; A computer was plugged into an orange extension cord, violating the extension cords UL listing and labeling for temporary power. (e) Untanking Tower, Submaintenance computer area; A white relocatable power tap with a light was plugged into a yellow and black extension cord. The UL listing states that relocatable power taps are designed to be plugged into an outlet, and not daisy chained and plugged into other relocatable power taps or extension cords. This exposes employees to possible electrical fire hazards. (f) Untanking Tower, Submaintenance computer area; A white relocatable power tap with a light was re-wired into a baloney cord and the device was not tested for intrinsic electrical safety. This exposes employees to possible electrical fire hazards. (g) Untanking Tower, Environmental Office; A Lasco heater was plugged into a relocatable power tap. The UL listing states that relocatable power taps are designed for low amperage computer and audiovisual types of equipment, and not appliances. This exposes employees to possible electrical fire hazards. Bonneville Power Administration was previously cited for a violation of this standard which was contained in OSHA inspection no. 908523 citation 1, item 1, issued on September 27, 2013 with respect to a workplace at Vancouver, Washington. Bonneville Power Administration was previously cited for a violation of this standard which was contained in OSHA inspection no. 542122 citation 1, item 4, issued on October 2, 2012 with respect to a workplace at Olympia, Washington.
Recent events (1)
- — Z (R) $0
1910.22 A01
- Issued
- Apr 15, 2014
- Abate by
- May 18, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.22(a)(1): All places of employment, passageways, storerooms or service rooms were not kept clean and orderly or in a sanitary condition. a) PSC Workshop building, Communications Building F; The ceiling tiles were falling and in disarray, visible dirt and debris was on the carpeted floor, and the equipment was in disarray.
Recent events (1)
- — Z (O) $0
1910.36 G02
- Issued
- Apr 15, 2014
- Abate by
- May 18, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.36(g)(2): Exit access(es) were not at least 28 inches (71.1 cm) wide at all points. a) Warehouse/ TLM, PSC Storage Area; There was a 19.5 inch aisleway between a metal bracket and spools of wire. b) HMEM Garage; There was a 23 inch aisleway between an oil and and a flammable locker. c) SPC/PSC Modular, Copy Room; There was a 22 inch aisleway between a metal shelf and the wall in the area which lead to the heater and breaker panel. d) SPC/PSC Modular; There was a 20.5 inch aisleway in between two desks in the center of the office, which lead to other work areas and bookcases.
Recent events (1)
- — Z (O) $0
1910.303 G01 II
- Issued
- Apr 15, 2014
- Abate by
- May 18, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage: a) HMEM Garage; A can and ladder were stored underneath the breaker panel. b) Untanking Tower; Conduit poles were stored in front of a breaker panel in the main area. c) SPC/PSC Modular; Boxes and a vacuum were stored underneath the breaker panel.
Recent events (1)
- — Z (O) $0
More inspections at Bonneville Power Administration-Covington District
View Bonneville Power Administration-Covington District's full OSHA safety record →
More inspections in this industry (NAICS 221121)
More inspections in WA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339663015.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.